Plan Review Stops For Permit 14071106 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-11-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-14 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-11-14 |
Time |
08:54 |
Sent To |
|
|
Notes |
2014-11-14 10:18:45 | ****PROVISO**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ENGINEER IS TO OBTAIN CERTIFICATE OF AUTHORIZATION | | FOR THE COMPANY HOFFMAN ENGINEERS, PC. APPLICATION HAS | | BEEN SUBMITTED, ENGINEER TO FOLLOW THROUGH AND OBTAIN | | LICENSE. | | | | 2. PHOTOMETRIC PLAN IS FOR 56 LIGHT FIXTURES. VALUE HAS | | BEEN ADJUSTED ACCORDINGLY. IF CONTRACTOR IS NOT | | INSTALLING 56 LIGHT FIXTURES, REVISE SITE PLAN TO | | CLARIFY LOCATION(S) OF LIGHTS INSTALLED. | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-11-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-08 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-11-08 |
Time |
11:49 |
Sent To |
|
|
Notes |
2014-11-08 11:54:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | RE: STRUCTURAL CALCS | | | | 1. CALCS ARE OK, BUT A PHOTOCOPY WAS PROVIDED. | | | | ENGINEER MISUNDERSTOOD PREVIOUS LIST. I WAS NOT STATING | | THAT THE INSTALLATION **IS** IN EXPOSURE D. I WAS | | REQUESTING INFORMATION FOR THE ENGINEER OR CONTRACTOR | | TO PROVIDE FOR THAT DETERMINATION TO BE CONFIRMED. THE | | SITE PLAN DOES NOT SHOW DISTANCE TO PROPERTY LINES OR | | TO CLEAR LAKE, OR PROPOSED LOCATION IN RELATION TO | | CLEAR LAKE. THE PAGES FROM ASCE7-10 ARE NOT NECESSARY; | | WE HAVE THEM IN OUR OFFICE. A PROPER SITE PLAN OR | | AERIAL AS PREVIOUSLY REQUESTED WOULD SUFFICE. | | | | 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS | | LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH | | AN ENGINEERING COMPANY, FS 471, FAC61G15-23. | | | | 2ND REVIEW, NOT ADDRESSED. A FOREIGN ENTITY | | REGISTRATION WITH SUNBIZ.ORG WAS PROVIDED. THIS IS NOT | | AN ENGINEERING LICENSE; THIS CAN ONLY BE OBTAINED | | THROUGH FLORIDA BOARD OF PROFESSIONAL ENGINEERS/DBPR. | | EITHER PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER | | (REQUIRED TO BE A PART OF THE TITLE BLOCK) OR SUBMIT | | APPLICATION. CONTACT FBPE AT 850-521-0500 FOR MORE | | INFORMATION. | | | | 3RD REVIEW, NOT ADDRESSED. THE FOREIGH ENTITY | | REGISTRATION WAS INCORPORATED INTO THE SIGNED AND | | SEALED PLAN WITH THE WORDS "FLORIDA C.O.A." IN FRONT OF | | THE CORPORATE REGISTRATION NUMBER. THIS HAS BEEN | | DISCUSSED AT LENGTH WITH THE ENGINEER'S OFFICE AND THEY | | HAVE AGREED TO APPLY. PLEASE NOTIFY WHEN THIS | | APPLICATION HAS BEEN PROCESSED, AND THE PERMIT WILL BE | | ISSUED AFTER RECEIPT OF ORIGINAL SIGNED AND SEALED | | ENGINEERING. | | | | 3. OK | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS | | THESE COMMENTS. | | | | IF CONTRACTOR OR ENGINEER DO NOT WISH TO WAIT FOR THE | | TWO ABOVE ISSUES TO BE RESOLVED, THE PERMIT WILL BE | | ISSUED BUT THE TWO ISSUES (SUBMITTAL OF PHOTOCOPIES, | | LACK OF C OF A) WILL BE REFERRED TO FBPE RATHER THAN | | DELAYING THIS PERMIT. ***IT IS MY UNDERSTANDING THAT | | THE ENGINEER HAS ALREADY OVERNIGHTED ORIGINAL PLANS TO | | ME AND THE APPLICATION TO FBPE.*** | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-10-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-10-11 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-10-11 |
Time |
14:14 |
Sent To |
|
|
Notes |
2014-10-11 14:19:48 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | RE: STRUCTURAL CALCS | | | | 1. DESIGN CRITERIA IS TO INCLUDE EXPOSURE | | CLASSIFICATION, FBC 1603.1.4. | | | | 2ND REVIEW, BOTH EXPOSURE B AND C ARE STATED. PROVIDE | | AN AERIAL SHOWING LOCATION OF FIXTURES WITH DIMENSIONS | | TO CLEAR LAKE. IT APPEARS THAT SOME MAY BE LOCATED IN | | EXPOSURE D, AND ALL ARE AT A MINIMUM EXPOSURE C AS THE | | LOT LENGTH IS LESS THAN 1500'. | | | | 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS | | LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH | | AN ENGINEERING COMPANY, FS 471, FAC61G15-23. | | | | 2ND REVIEW, NOT ADDRESSED. A FOREIGN ENTITY | | REGISTRATION WITH SUNBIZ.ORG WAS PROVIDED. THIS IS NOT | | AN ENGINEERING LICENSE; THIS CAN ONLY BE OBTAINED | | THROUGH FLORIDA BOARD OF PROFESSIONAL ENGINEERS/DBPR. | | EITHER PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER | | (REQUIRED TO BE A PART OF THE TITLE BLOCK) OR SUBMIT | | APPLICATION. CONTACT FBPE AT 850-521-0500 FOR MORE | | INFORMATION. | | | | 3. OK | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS | | THESE COMMENTS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-09-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-15 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-13 |
Time |
17:12 |
Sent To |
|
|
Notes |
2014-09-15 11:40:38 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | RE: STRUCTURAL CALCS | | | | 1. DESIGN CRITERIA IS TO INCLUDE EXPOSURE | | CLASSIFICATION, FBC 1603.1.4. | | | | 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS | | LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH | | AN ENGINEERING COMPANY, FS 471, FAC61G15-23. | | | | 3. CALCS SHOULD BE IN A FORMAT ACCEPTABLE TO FBPE, SEE | | FAC61G15-23.002. EITHER EACH SHEET IS TO BE SIGNED AND | | SEALED OR AN INDEX SHEET IDENTIFYING EACH PAGE SHOULD | | BE PROVIDED. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-09-10 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-10 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-10 |
Time |
09:31 |
Sent To |
B |
|
Notes |
2014-09-10 09:36:12 | TO MISC. 2 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-08-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-08-01 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-08-01 |
Time |
16:15 |
Sent To |
|
|
Notes |
2014-08-01 16:31:03 | DATE: 8/1/2014 | | PROJECT: | | PERMIT#: | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) ADDITIONAL INFORMATION REQUIRED. IF CORRECT | | ATTACHMENT OF FIXTURES IS THE INTENT OF THE PERMIT | | PROVIDE ATTACHMENT DETAILS. THE APPLICATION ALSO | | INDICATES INSTALLATION OF EXTERIOR LIGHTING TO BUILDING | | AND WIRING. DETAILS SUCH AS CIRCUITRY, WIRING MEATHODS | | ROUTING OF CONDUITS, PANEL SCHEDULES, LOAD CALCULATIONS | | INDICATING THE ADDITIONAL LOAD WITH THE INSTLALLATION | | OF THE NEW FIXTURES. IF ALL THESE FIXTURES WERE | | INSTALLED UNDER A SEPARATE PERMIT. PLEASE PROVIDE THAT | | PERMIT NUMBER SO THE DETAILS OF THE INSTALLATION CAN BE | | REFERENCED FROM THE PREVIOUS PERMIT. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | ITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-11-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-08 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-10-20 |
Time |
18:20 |
Sent To |
|
|
Notes |
2014-10-20 18:20:53 | RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-10-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-10-11 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-29 |
Time |
18:47 |
Sent To |
|
|
Notes |
2014-09-29 18:47:24 | RE-SUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-09-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-15 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-09 |
Time |
09:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-09-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-08-14 |
Time |
|
Rev Time |
|
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2014-07-30 10:24:57 | ROUTED TO ELECTRICAL LESS THAN $5 000 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-08-14 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2014-08-14 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2014-08-14 |
Time |
15:22 |
Sent To |
|
|
Notes |
|
|