Plan Review Details - Permit 14071106
Plan Review Stops For Permit 14071106
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-11-14 Cont ID  
Sent By shill Date 2014-11-14 Time 08:54 Rev Time 0.00
Received By shill Date 2014-11-14 Time 08:54 Sent To  
Notes
2014-11-14 10:18:45****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEER IS TO OBTAIN CERTIFICATE OF AUTHORIZATION
 FOR THE COMPANY HOFFMAN ENGINEERS, PC. APPLICATION HAS
 BEEN SUBMITTED, ENGINEER TO FOLLOW THROUGH AND OBTAIN
 LICENSE.
  
 2. PHOTOMETRIC PLAN IS FOR 56 LIGHT FIXTURES. VALUE HAS
 BEEN ADJUSTED ACCORDINGLY. IF CONTRACTOR IS NOT
 INSTALLING 56 LIGHT FIXTURES, REVISE SITE PLAN TO
 CLARIFY LOCATION(S) OF LIGHTS INSTALLED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-08 Cont ID  
Sent By shill Date 2014-11-08 Time 11:49 Rev Time 0.00
Received By shill Date 2014-11-08 Time 11:49 Sent To  
Notes
2014-11-08 11:54:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 RE: STRUCTURAL CALCS
  
 1. CALCS ARE OK, BUT A PHOTOCOPY WAS PROVIDED.
  
 ENGINEER MISUNDERSTOOD PREVIOUS LIST. I WAS NOT STATING
 THAT THE INSTALLATION **IS** IN EXPOSURE D. I WAS
 REQUESTING INFORMATION FOR THE ENGINEER OR CONTRACTOR
 TO PROVIDE FOR THAT DETERMINATION TO BE CONFIRMED. THE
 SITE PLAN DOES NOT SHOW DISTANCE TO PROPERTY LINES OR
 TO CLEAR LAKE, OR PROPOSED LOCATION IN RELATION TO
 CLEAR LAKE. THE PAGES FROM ASCE7-10 ARE NOT NECESSARY;
 WE HAVE THEM IN OUR OFFICE. A PROPER SITE PLAN OR
 AERIAL AS PREVIOUSLY REQUESTED WOULD SUFFICE.
  
 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS
 LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH
 AN ENGINEERING COMPANY, FS 471, FAC61G15-23.
  
 2ND REVIEW, NOT ADDRESSED. A FOREIGN ENTITY
 REGISTRATION WITH SUNBIZ.ORG WAS PROVIDED. THIS IS NOT
 AN ENGINEERING LICENSE; THIS CAN ONLY BE OBTAINED
 THROUGH FLORIDA BOARD OF PROFESSIONAL ENGINEERS/DBPR.
 EITHER PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER
 (REQUIRED TO BE A PART OF THE TITLE BLOCK) OR SUBMIT
 APPLICATION. CONTACT FBPE AT 850-521-0500 FOR MORE
 INFORMATION.
  
 3RD REVIEW, NOT ADDRESSED. THE FOREIGH ENTITY
 REGISTRATION WAS INCORPORATED INTO THE SIGNED AND
 SEALED PLAN WITH THE WORDS "FLORIDA C.O.A." IN FRONT OF
 THE CORPORATE REGISTRATION NUMBER. THIS HAS BEEN
 DISCUSSED AT LENGTH WITH THE ENGINEER'S OFFICE AND THEY
 HAVE AGREED TO APPLY. PLEASE NOTIFY WHEN THIS
 APPLICATION HAS BEEN PROCESSED, AND THE PERMIT WILL BE
 ISSUED AFTER RECEIPT OF ORIGINAL SIGNED AND SEALED
 ENGINEERING.
  
 3. OK
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
 THESE COMMENTS.
  
 IF CONTRACTOR OR ENGINEER DO NOT WISH TO WAIT FOR THE
 TWO ABOVE ISSUES TO BE RESOLVED, THE PERMIT WILL BE
 ISSUED BUT THE TWO ISSUES (SUBMITTAL OF PHOTOCOPIES,
 LACK OF C OF A) WILL BE REFERRED TO FBPE RATHER THAN
 DELAYING THIS PERMIT. ***IT IS MY UNDERSTANDING THAT
 THE ENGINEER HAS ALREADY OVERNIGHTED ORIGINAL PLANS TO
 ME AND THE APPLICATION TO FBPE.***
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 14:14 Rev Time 0.00
Received By shill Date 2014-10-11 Time 14:14 Sent To  
Notes
2014-10-11 14:19:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 RE: STRUCTURAL CALCS
  
 1. DESIGN CRITERIA IS TO INCLUDE EXPOSURE
 CLASSIFICATION, FBC 1603.1.4.
  
 2ND REVIEW, BOTH EXPOSURE B AND C ARE STATED. PROVIDE
 AN AERIAL SHOWING LOCATION OF FIXTURES WITH DIMENSIONS
 TO CLEAR LAKE. IT APPEARS THAT SOME MAY BE LOCATED IN
 EXPOSURE D, AND ALL ARE AT A MINIMUM EXPOSURE C AS THE
 LOT LENGTH IS LESS THAN 1500'.
  
 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS
 LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH
 AN ENGINEERING COMPANY, FS 471, FAC61G15-23.
  
 2ND REVIEW, NOT ADDRESSED. A FOREIGN ENTITY
 REGISTRATION WITH SUNBIZ.ORG WAS PROVIDED. THIS IS NOT
 AN ENGINEERING LICENSE; THIS CAN ONLY BE OBTAINED
 THROUGH FLORIDA BOARD OF PROFESSIONAL ENGINEERS/DBPR.
 EITHER PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER
 (REQUIRED TO BE A PART OF THE TITLE BLOCK) OR SUBMIT
 APPLICATION. CONTACT FBPE AT 850-521-0500 FOR MORE
 INFORMATION.
  
 3. OK
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
 THESE COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-15 Cont ID  
Sent By shill Date 2014-09-15 Time 11:32 Rev Time 0.00
Received By shill Date 2014-09-13 Time 17:12 Sent To  
Notes
2014-09-15 11:40:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 RE: STRUCTURAL CALCS
  
 1. DESIGN CRITERIA IS TO INCLUDE EXPOSURE
 CLASSIFICATION, FBC 1603.1.4.
  
 2. CERTIFICATE OF AUTHORIZATION (ENGINEERING BUSINESS
 LICENSE) IS REQUIRED FOR PRACTICING ENGINEERING THROUGH
 AN ENGINEERING COMPANY, FS 471, FAC61G15-23.
  
 3. CALCS SHOULD BE IN A FORMAT ACCEPTABLE TO FBPE, SEE
 FAC61G15-23.002. EITHER EACH SHEET IS TO BE SIGNED AND
 SEALED OR AN INDEX SHEET IDENTIFYING EACH PAGE SHOULD
 BE PROVIDED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-10 Cont ID  
Sent By dhayes Date 2014-09-10 Time 09:35 Rev Time 0.00
Received By dhayes Date 2014-09-10 Time 09:31 Sent To B
Notes
2014-09-10 09:36:12TO MISC. 2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-01 Cont ID  
Sent By dhayes Date 2014-08-01 Time 16:16 Rev Time 0.00
Received By dhayes Date 2014-08-01 Time 16:15 Sent To  
Notes
2014-08-01 16:31:03DATE: 8/1/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION REQUIRED. IF CORRECT
 ATTACHMENT OF FIXTURES IS THE INTENT OF THE PERMIT
 PROVIDE ATTACHMENT DETAILS. THE APPLICATION ALSO
 INDICATES INSTALLATION OF EXTERIOR LIGHTING TO BUILDING
 AND WIRING. DETAILS SUCH AS CIRCUITRY, WIRING MEATHODS
 ROUTING OF CONDUITS, PANEL SCHEDULES, LOAD CALCULATIONS
 INDICATING THE ADDITIONAL LOAD WITH THE INSTLALLATION
 OF THE NEW FIXTURES. IF ALL THESE FIXTURES WERE
 INSTALLED UNDER A SEPARATE PERMIT. PLEASE PROVIDE THAT
 PERMIT NUMBER SO THE DETAILS OF THE INSTALLATION CAN BE
 REFERENCED FROM THE PREVIOUS PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-11-08 Cont ID  
Sent By shill Date 2014-11-08 Time 11:54 Rev Time 0.00
Received By shill Date 2014-10-20 Time 18:20 Sent To  
Notes
2014-10-20 18:20:53RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 14:19 Rev Time 0.00
Received By shill Date 2014-09-29 Time 18:47 Sent To  
Notes
2014-09-29 18:47:24RE-SUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-15 Cont ID  
Sent By shill Date 2014-09-15 Time 11:40 Rev Time 0.00
Received By shill Date 2014-09-09 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-15 Cont ID  
Sent By shill Date 2014-08-14 Time   Rev Time  
Received By shill Date   Time   Sent To  
Notes
2014-07-30 10:24:57ROUTED TO ELECTRICAL LESS THAN $5 000

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-14 Cont ID  
Sent By sgraham Date 2014-08-14 Time 15:22 Rev Time 0.00
Received By sgraham Date 2014-08-14 Time 15:22 Sent To  
Notes
***NONE***