Plan Review Details - Permit 14071105
Plan Review Stops For Permit 14071105
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-03-13 Cont ID  
Sent By jwitmer Date 2015-03-13 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2015-03-13 Time 08:28 Sent To  
Notes
2015-03-13 08:29:29BUILDING PLAN REVIEW
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: FRI. MARCH FRI> 13/ 2015
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: DEFERRED SUBMITTAL,THE THEATER
 SEATING SHOW RAISED SEATING, THE S6 SHEET SHOWS GEO
 FOAM NO MANUFACTURERS SPECS WERE SUBMITTED NOR DOES THE
 PLANS INDICATE THE END OF THE FOAM ARE ENCAPSULATED BY
 CONCRETE ON THE SIDES. FBC-B 2603.4.1.1. THE STRUCTURAL
 ENGINEER HAS SHOWN ON SHEET S-6 THE FOAM BEING TOTALLY
 ENCLOSED. THE CONTRACTOR HAS NOT SUBMITTED PRODUCT
 TESTING REPORTS AND MANUFACTURERS SPECS FOR THE
 STRUCTURAL FOAM, NOR HAS IT BEEN REVIEWED BY THE
 ENGINEER OF RECORD FOR APPROVAL, BY SHOP DRAWING STAMP,
 APPROVED OR APPROVED WITH COMMENT.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL, REQUEST BY THE
 DESIGNER OF RECORD COMPONENT & CLADDING PRODUCT
 APPROVALS, MAY BE SUBMITTED AFTER PERMIT ISSUANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STAND
  
 3) BUILDING PROVISO. DEFERRED SUBMITTAL, REQUEST BY THE
 DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-01-07 Cont ID  
Sent By jwitmer Date 2015-01-07 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2015-01-07 Time 11:52 Sent To  
Notes
2015-01-07 13:09:52BUILDING PLAN REVIEW
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: FRI. JAN. WED. 07/2015
 ACTION: DENIED
  
 1) BUILDING PROVISO: DEFERRED SUBMITTAL,THE THEATER
 SEATING SHOW RAISED SEATING, THE S6 SHEET SHOWS GEO
 FOAM NO MANUFACTURERS SPECS WERE SUBMITTED NOR DOES THE
 PLANS INDICATE THE END OF THE FOAM ARE ENCAPSULATED BY
 CONCRETE ON THE SIDES. FBC-B 2603.4.1.1. THE STRUCTURAL
 ENGINEER HAS SHOWN ON SHEET S-6 THE FOAM BEING TOTALLY
 ENCLOSED. THE CONTRACTOR HAS NOT SUBMITTED PRODUCT
 TESTING REPORTS AND MANUFACTURERS SPECS FOR THE
 STRUCTURAL FOAM, NOR HAS IT BEEN REVIEWED BY THE
 ENGINEER OF RECORD FOR APPROVAL, BY SHOP DRAWING STAMP,
 APPROVED OR APPROVED WITH COMMENT.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL, REQUEST BY THE
 DESIGNER OF RECORD COMPONENT & CLADDING PRODUCT
 APPROVALS, MAY BE SUBMITTED AFTER PERMIT ISSUANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STAND
  
 3) BUILDING PROVISO. DEFERRED SUBMITTAL, REQUEST BY THE
 DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 _______________________________________________________
 ________
 10) NEW COMMENT!!!!! THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING, AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 500 OCCUPANTS & 5,000 SQ.
 FT. IN AREA. PLEASE SEE NEW COMMENTS THAT WILL BE
 REQUIRED AS A THRESHOLD BUILDING. THIS MORNING I
 E-MAILED MATTHEW SLATTER THE REQUIREMENTS FOR A
 THRESHOLD BUILDING AND FORMS THAT WILL BE REQUIRED TO
 BE SIGNED.
  
 10A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 10B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. PLEASE FILE OUT
 FORMS BY ALL INTERESTED PARTIES.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 10C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 10D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 10D)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 10E) NOTICE!!!! PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
  
 10F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 10G) COMPLIED. NOTE SINCE THIS IS A THRESHOLD PROJECT
 (3) SETS OF PLANS, REPORTS, AND PRODUCT APPROVALS WILL
 BE REQUIRED, A 3RD SET WILL BE FOR THE THRESHOLD
 INSPECTORS USE.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By jwitmer Date 2014-11-21 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2014-11-21 Time 09:51 Sent To  
Notes
2014-11-21 15:22:29BUILDING PLAN REVIEW
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. NOV.21/2014
 ACTION: DENIED
  
 1A) COMPLIED WITH CORRECTED ADDRESS.
  
 1B) COMPLIED.
  
 2) COMPLIED. NEW SITE PLAN.
  
 3) COMPLIED. 3 ORIGINAL SOILS REPORTS.
  
 4) 2ND REQUEST. COVERSHEET: THE BUILDING CODE ANALYSIS
 INDICATES THIS BUILDING TO BE A FIRE SPRINKLERED
 BUILDING. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.:107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.5
 . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS. THE DESIGNER OF RECORD HAS TAKEN AREA
 INCREASES WITH THE INSTALLATION OF A NFPA 13 SYSTEM,
 2010 FBC-B 504.2., 903.2.1.2 AND 903.2.1.3.
  
 5) COMPLIED. FITNESS CENTER WITH EQUIPMENT LAYOUT.
  
 6) SHEET A-1.0:
 6A) COMPLIED. FIRE BOX SIZING.
  
 6B) 2ND REQUEST. THE THEATER SEATING SHOW RAISED
 SEATING, THE S6 SHEET SHOWS GEO FOAM NO MANUFACTURERS
 SPECS WERE SUBMITTED NOR DOES THE PLANS INDICATE THE
 END OF THE FOAM ARE ENCAPSULATED BY CONCRETE ON THE
 SIDES. FBC-B 2603.4.1.1. THE STRUCTURAL ENGINEER HAS
 SHOWN ON SHEET S-6 THE FOAM BEING TOTALLY ENCLOSED. THE
 CONTRACTOR HAS NOT SUBMITTED PRODUCT TESTING REPORTS
 AND MANUFACTURERS SPECS FOR THE STRUCTURAL FOAM, NOR
 HAS IT BEEN REVIEWED BY THE ENGINEER OF RECORD FOR
 APPROVAL, BY SHOP DRAWING STAMP, APPROVED OR APPROVED
 WITH COMMENT.
  
 7) COMPLIED. 12/02/14
 . THE CONTRACTOR HAS NOT SUBMITTED THE MANUFACTURERS
 SPEC AND REPORT WHERE THIS PRODUCT CAN BE USED AND
 LIMITATIONS OF SAID PRODUCT.
 SHEET A4.1 INDICATES THE USE OF ICYNENE INSULATION AS
 WELL AS THE COVER SHEET ALSO HAS NOTES FOR ICYNENE.
 ICYNENE IS TO BE INSTALLED UNDER THE ROOF DECK. PLEASE
 SUBMIT THE FULL ICYNENE REPORT LISTED ERS 1826 FOR
 REVIEW; 2010 FBC-B 2603.4.1.6. PLEASE PROVIDE WHICH
 AREAS ARE GOING TO HAVE ICYNENE TYPE INSULATION AND
 WHICH AREAS OF THE ROOFING ARE GOING TO HAVE ROOF TOP
 INSULATION ON TOP OF THE ROOF DECK AS DEPICTED IN
 DETAILS B-E. THE ENERGY SPECS INDICATE A R-33, PLEASE
 PROVIDE HOW MUCH INSULATION IT WILL TAKE TO PROVIDE
 THIS VALUE.
  
 .
  
 8) SEMI- COMPLIED. SHEETA-2.2 & A-4.1. SHEET A-2.2
 DETIAL # 1 SHOWS THE USE OF 1 INCH RIGID INSULATION
 BOARD AND THE 5/8 INCH DRYWALL EXTENDING 6 IN. ABOVE
 THE CEILING LEAVING THE INSULATION BOARD EXPOSED ABOVE
 THE CEILING. PLEASE PROVIDE COMPLIANCE WITH 2603.4
 THERMAL BARRIERS OR 2603.4.1. PROVIDE THE MANUFACTURERS
 SPEC SHEET FOR THE 1 INCH RIGID INSULATION, INCLUDE
 FLAME SPREAD & SMOKE DEVELOPMENT.
  
 9A) DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF
 RECORD.
 MISSING PRODUCT APPROVALS, MAY BE SUBMITTED AS DEFERRED
 SUBMITTALS UPON WRITTEN REQUEST:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STAND
  
 9B)DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF
 RECORD.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) NEW COMMENT!!!!! THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING, AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 500 OCCUPANTS & 5,000 SQ.
 FT. IN AREA. PLEASE SEE NEW COMMENTS THAT WILL BE
 REQUIRED AS A THRESHOLD BUILDING. THIS MORNING I
 E-MAILED MATTHEW SLATTER THE REQUIREMENTS FOR A
 THRESHOLD BUILDING AND FORMS THAT WILL BE REQUIRED TO
 BE SIGNED.
  
 10A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 10B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. PLEASE FILE OUT
 FORMS BY ALL INTERESTED PARTIES.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 10C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 10D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 10D)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 10E) NOTICE!!!! PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
  
 10F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 10G) NOTE SINCE THIS IS A THRESHOLD PROJECT (3) SETS OF
 PLANS, REPORTS, AND PRODUCT APPROVALS WILL BE REQUIRED,
 A 3RD SET WILL BE FOR THE THRESHOLD INSPECTORS USE.
  
 11A) NOTICE THIS BUILDING CAN NO LONGER BE CLASSIFIED
 AS A BUILDING CATEGORY II WITH A OCCUPANT LOAD OF 762
 OCCUPANTS. ASCE 7-10 TABLE 1.5-1 RISK AS WELL AS 2010
 FBC-B TABLE 1604.5. BUILDINGS FOR PUBLIC ASSEMBLY WITH
 OCCUPANT LOADS GREATER THAN 300.
 CATEGORIES LIST THIS AS A CATEGORY III WHICH WILL
 INCREASE THE PRESSURES SINCE THE WIND SPEED VULT WILL
 BE 180 MPH.
  
 THIS WILL EFFECT SHEET S-6 WITH ALL PRESSUES FLAT ROOF,
 SLPOED ROOFS (5:12 PITCH) AS WELL AS WALL PRESSURES IN
 ZONES 4 & 5. PLEASE UPDATE CHARTS. INDICATE IF
 PRESSURES ARE VULT OR VASD. THERE ARE ALSO PRESSURES
 THAT ARE TAKEN FROM RAS 128 FOR BUILDINGS THAT ARE LESS
 THAN 40 FT IN HEIGHT, EXPOSURE "C" FOR A FLAT ROOF,
 PLEASE NOTE THESE PRESSURES CAN ONLY BE USED FOR
 BUILDING CATEGORY II BUILDINGS.
  
 11B) SHEET S-6 ALSO IS MISSING THE WALL PRESSURES FOR
 WALL ZONES 4 & 5. COMPONENTS & CLADDING PRESSURES
 POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 12-13) COMPLIED.
  
 14) NEW COMMENT: THE COMBINED OCCUPANT LOAD OF
 BUILDING, POOL AND POOL DECK IS 1,247 SHOW COMPLIANCE
 WITH:
 2010 FBC-B F] 907.2.1.1 SYSTEM INITIATION IN GROUP A
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 1,000 OR MORE.
 ACTIVATION OF THE FIRE ALARM IN GROUP A OCCUPANCIES
 WITH AN OCCUPANT LOAD OF 1,000 OR MORE SHALL INITIATE A
 SIGNAL USING AN EMERGENCY VOICE/ALARM COMMUNICATIONS
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 EXCEPTION: WHERE APPROVED, THE PRERECORDED ANNOUNCEMENT
 IS ALLOWED TO BE MANUALLY DEACTIVATED FOR A PERIOD OF
 TIME, NOT TO EXCEED 3 MINUTES, FOR THE SOLE PURPOSE OF
 ALLOWING A LIVE VOICE ANNOUNCEMENT FROM AN APPROVED,
 CONSTANTLY ATTENDED LOCATION.
  
 15) ENERGY GAUGE FORM 506-2010 ONLY ONE REPORT WAS
 SUBMITTED, NOTE THAT THE ENGINEEER SEALED THE REPORT
 BUT DID NOT SIGN NOR DATE THE REPORT. 61G15-23.002(2)
 FL. ADMIN. CODE.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 16:45 Rev Time 0.00
Received By tklarge Date 2014-08-26 Time 13:00 Sent To  
Notes
2014-08-26 16:45:03BUILDING PLAN REVIEW
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: TUES. AUGUST 26/2014
 ACTION: DENIED
  
 1A) THE PLANS NEED TO HAVE THE CORRECT ADDRESS OF 1517
 CAMERON SAMUEL LN. ON ALL PLANS. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 1B) THE STRUCTURAL PLANS HAVE STICKERS ON PLANS AND
 HAND WRITTEN NOTES. NO SSTICKEERS ARE TO BE PLACED ON
 THE PLANS. 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 2) THE PLAN INDEX INDICATES THERE IS A SITE PLAN A-0.1,
 MISSING FROM THE SET OF PLANS, PLEASE INCLUDE THE SITE
 PLAN:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
  
 3) STRUCTURAL SHEET S-6 INDICATES A SOILS REPORT WAS
 COMPLETED BY D & N DRILLING ENGINEERING 1/20/2014.
 PLEASE SUBMIT 2 ORIGINAL SIGNED & SEALED REPORTS.
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 4) COVERSHEET: THE BUILDING CODE ANALYSIS INDICATES
 THIS BUILDING TO BE A FIRE SPRINKLERED BUILDING.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.:107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.5
 . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 5) THE COVERSHEET INDICATES THE OCCUPANCY IN THE
 FITNESS CENTER NEITHER SHEET A-1.0 NOR A-1.1 SHOW
 EQUIPMENT LAYOUT IN THE GYM, THEN
 15 SQ FT / OCCUPANT WILL BE TAKEN FOR THE SPACE. 2010
 FBC-B 1004.1.1.
  
 6) SHEET A-1.0:
 6A) SHEET A-1.0 VERSES THE STRUCTURAL SHEET S3, THE
 FIRE BOX IN THE ARCHITECTURAL SHEET SHOWS A 3X8 AND THE
 STRUCTURAL SHEET SHOWS A 3X6 FOOT FIRE BOX. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED, DISCREPANCY IN
 PLANS.
  
 6B) THE THEATER SEATING SHOW RAISED SEATING, THE S6
 SHEET SHOWS GEO FOAM NO MANUFACTURERS SPECS WERE
 SUBMITTED NOR DOES THE PLANS INDICATE THE END OF THE
 FOAM ARE ENCAPSULATED BY CONCRETE ON THE SIDES. FBC-B
 2603.4.1.1.
  
 7) SHEET A4.1 INDICATES THE USE OF ICYNENE INSULATION
 AS WELL AS THE COVER SHEET ALSO HAS NOTESFOR ICYNENE.
 PLEASE SUBMIT THE FULL ICYNENE REPORT LISTED ERS 1826
 FOR REVIEW; 2010 FBC-B 2603.4.1.6. PLEASE PROVIDE WHICH
 AREAS ARE GOING TO HAVE ICYNENE TYPE INSULATION AND
 WHICH AREAS OF THE ROOFING ARE GOING TO HAVE ROOF TOP
 INSULATION ON TOP OF THE ROOF DECK AS DEPICTED IN
 DETAILS B-E. THE ENERGY SPECS INDICATE A R-33, PLEASE
 PROVIDE HOW MUCH INSULATION IT WILL TAKE TO PROVIDE
 THIS VALUE.
  
 8) SHEET A4.1 ALSO SHOWS EXTERIOR WALL CONSTRUCTION IN
 DETAILS C& D, NO INSULATION IS DEPICTED IN THESE
 DETAILS, THE ENERGY CALCULATIONS INDICATE A R VALUE OF
 8.0. ENERGY 502..2 PERSCRIPTIVE.
  
 9) MISSING PRODUCT APPROVALS, MAY BE SUBMITTED AS
 DEFERRED SUBMITTALS UPON WRITTEN REQUEST:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STAND
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 11A) SHEET S-6 DOES HAVE ROOF PRESSURES ZONE #1 @ 24.6,
 ZONE @ 38.8 & ZONE 3 @ 67.1 THESE PRESSUES DO NOT
 INDICATE IF VULT, VASD, WHAT THE MEAN ROOF HEIGHT?
 THERE ARE ALSO PRESSURES THAT ARE TAKEN FROM RAS 128
 FOR BUILDINGS THAT ARE LESS THAN 40 FT IN HEIGHT,
 EXPOSURE "C" FOR A FLAT ROOF, VASD FOR 20 SQ FTPLEASE
 PROVIDE THE VALUES FOR 10 SQ FTTHEY ARE TAKEN FOR THE
 FASTENERS OF THE ROOFING PRODUCT WORSE CASE AT 10 SQ.
 FT.
  
 11B) SHEET S-6 DOES NOT PROVIDE WHAT THE PRESSURES ARE
 FOR 5:12 PITCH ROOF? COMPONENTS & CLADDING PRESSURES
 POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 11C) SHEET S-6 ALSO IS MISSING THE WALL PRESSURES FOR
 WALL ZONES 4 & 5. COMPONENTS & CLADDING PRESSURES
 POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 12) SHEET S-6 NOTES FOR BUCK ATTACHMENT REFERANCE THE
 FBC-R 4409.10.1 RESIDENTIAL CODE, THIS IS CONSIDERED A
 COMMERCIAL BUILDING.
  
 13) SHEET S-6 WIRE LATH @ WIRE FASTENERS PLEASE PROVIDE
 WHERE WIRE STAPLES CAN BE USED FOR FASTENING WIRE LATH
 WITH A 1 1/2 EMBEDMEMT. 2510.3 INSTALLATION.
 INSTALLATION OF THESE MATERIALS SHALL BE IN COMPLIANCE
 WITH ASTM C 926 AND ASTM C 1063. 3/8 INCH RIB LATH IS
 TO BE NAILED AT EVERY RIB.
 ASTM C 1063 7.10.2.3 EXPANDED 3/8 IN REIB LATH AND
 SHEET EXPANDED METAL LATH SHALL BE ATTACHED TO
 HORIZONTAL AND VERTICAL WOOD FRAMING MEMBRS WITH NAILS
 OR STAPLES TO PROVIDE AT LEAST 1 3/4 INCH PENETRTION
 INTO HORIZONTAL WOOD FRAMING MEMBERS AND 3/4 INCH
 PENETRATION INTO VERTICAL FRAMING MEMBERS.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-06 Cont ID  
Sent By rlecky Date 2014-11-06 Time 10:54 Rev Time 0.00
Received By rlecky Date 2014-11-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-14 Cont ID  
Sent By rlecky Date 2014-08-14 Time 13:35 Rev Time 0.00
Received By rlecky Date 2014-08-14 Time 12:34 Sent To  
Notes
2014-08-14 13:51:18 
 14071105
 1517 CAMERON SAMUEL LANE
 CLUBHOUSE BUILDING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. PROVIDE A FIXTURE SCHEDULE FOR THE
 LIGHTING SYSTEM. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PANEL P1 AND P2 MAY NOT BE LOCATED IN A STORAGE ROOM.
 PANEL BOARDS SHALL BE LOCATED IN DEDICATED SPACES. NEC
 240.24(D), 110.26 (A) THRU (G).
  
 RECEPTACLES LOCATED OUTSIDE ADJACENT TO THE LOGGIA
 REQUIRE GFCI PROTECTION. NEC 210.8
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6700
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2014-08-13 Cont ID  
Sent By cranford Date 2014-08-13 Time 10:52 Rev Time 0.25
Received By cranford Date 2014-08-13 Time 10:52 Sent To B
Notes
2014-08-13 10:52:33BUILDING PLANS ONLY. ENGINEERING REVIEW NOT REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-12-16 Cont ID  
Sent By pleduc Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 17:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-31 Cont ID  
Sent By pleduc Date 2014-10-31 Time   Rev Time 0.00
Received By pleduc Date 2014-10-29 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-04 Cont ID  
Sent By pleduc Date 2014-08-04 Time   Rev Time 0.00
Received By pleduc Date 2014-07-31 Time 10:21 Sent To  
Notes
2014-08-01 09:18:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 SHEET LS-1 SHOWS A THEATER LOBBY WITH EXIT PATH PASSING
 THROUGH IT. THE THEATER LOBBY SHALL COMPLY WITH THE
 REQUIRNEMENTS OF NFPA 101, CHAPTER 12, NEW ASSEMBLY
 OCCUPANCIES, 12.1.7.2 WAITING SPACES. STANDING OR
 WAITING IN THE AREA OF THE EXIT PATHWAY BY REQUIRMENT
 SHALL BE RESTRICTED. THE MEANS OF RESTRICTION SHALL BE
 REVIEWED AND APPROVED THROUGH THE OFFICE OF THE FIRE
 MARSHAL.
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
  
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-07 Cont ID  
Sent By jwitmer Date 2015-01-07 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2014-12-10 Time 17:26 Sent To  
Notes
2014-12-10 17:26:38RE-SUBMITTAL SENT TO C35 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-21 Cont ID  
Sent By jwitmer Date 2014-11-21 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2014-10-20 Time 14:40 Sent To  
Notes
2014-10-28 14:41:37INCOMING SENT TO C-25. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By tklarge Date 2014-09-03 Time 08:08 Rev Time 0.00
Received By tklarge Date 2014-07-30 Time 17:14 Sent To  
Notes
2014-07-30 17:14:21C05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-01-13 Cont ID  
Sent By jwitmer Date 2015-01-13 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2015-01-13 Time 09:27 Sent To  
Notes
2015-01-13 09:29:08PALM BCH CTY IMPACT FEESRECEIPT # 2015-0113-49
  
 $8753.29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-01-07 Cont ID  
Sent By jwitmer Date 2015-01-07 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2015-01-07 Time 13:10 Sent To  
Notes
2015-01-07 13:10:48BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By jwitmer Date 2014-11-21 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2014-11-21 Time 10:47 Sent To  
Notes
2014-11-21 10:48:12BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 16:45 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2014-08-26 16:45:45BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-01-02 Cont ID  
Sent By hmoser Date 2015-01-02 Time 10:50 Rev Time 0.00
Received By hmoser Date 2015-01-02 Time 10:45 Sent To  
Notes
2015-01-02 10:49:58PASS PROVISO
 PROVIDE WELDING CERTS TO THE CITY
 BE FOR HE OR SHE STARTS TO WELD.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-04 Cont ID  
Sent By hmoser Date 2014-11-04 Time 09:21 Rev Time 0.00
Received By hmoser Date 2014-11-03 Time 14:17 Sent To  
Notes
2014-11-04 09:21:14PLAN DENIED
  
 1) MISSING FIRE DAMPERS IN SOCIAL ROOM AT KITCHEN WALL.
 PER SECTION 607.5.2 FIRE BARRIERS 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-18 Cont ID  
Sent By jdariton Date 2014-08-18 Time 11:10 Rev Time 0.00
Received By jdariton Date 2014-08-18 Time 11:30 Sent To  
Notes
2014-08-18 11:29:538/18/14
 NOTES:
 1.PAGE 9OF 9 OF THE ENERGY CALCULATIONS MUST BE
 COMPLETELY FILLED OUT.
 2.INDICATE ON THE A/C SCHEDULE THE EER/SEER OF THE A/C
 EQUIPMENT AS REQUIRED BY THE ENERGY CALCULATIONS.
 3.PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 THE FIRE PLACE.
 4..SHOW ON PLANS COMPETE DETAIL OF THE CONDENSING UNIT
 INSTALLATION ON THE ROOF AND INDICATE HOW THE STAND IS
 SECURED TO ROOF AND THE UNIT TO THE STAND.
 5.PROVIDE COMPLETE KITCHEN EXHAUST HOOD INSTALLATION
 DATAILS(TYPE 1) AS REQUIRED BY FMC SEC.506 AND 507.
 6.PROVIDE COMPLETE FIRE SUPPRESSION PLANS AS REQUIRED
 BY THE FMC SEC.509.
 7.SHOW ON PLANS THE DISCHARGE LOCATION OF THR
 CONDENSATE AS REQUIRED BY SEC.307 OF THE FMC AND
 SEC.1503.7 OF THE FBC.
  
 REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT
 561-805-6732.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-18 Cont ID  
Sent By tklarge Date 2014-12-18 Time 11:13 Rev Time 0.00
Received By tklarge Date 2014-12-18 Time 11:13 Sent To  
Notes
2014-12-18 11:13:37SEPARATE PERMIT REQD. FOR GAS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-02 Cont ID  
Sent By tklarge Date 2014-11-02 Time 08:05 Rev Time 0.00
Received By tklarge Date 2014-11-02 Time 07:42 Sent To  
Notes
2014-11-02 08:05:231) SHT.A-0.0 - BUILDING CODE BLOCK - YOU HAVE NOW
 CLASSIFIED THE STRUCTURE AS A "MIXED OCCUPANCY". THERE
 IS NO SUCH GENERAL CLASSIFICATION IN CHAPTER 3 OF THE
 FBC. THE DIFFERENT TYPES OF OCCUPANCIES MUST BE
 LISTED.MY PREVIOUS COMMENT ASKED TO CLARIFY AS TO HOW
 THE BUILDING COULD BE CLASSIFIED AS ONE TYPE OF
 OCCUPANCY WHEN IT WAS ACTUALLY A MIXED OCCUPANCY OF
 SEVERAL CLASSIFICATIONS. I DID NOT REQUEST THAT THE
 OCCUPANCY BE CHANGED, ONLY TO CLARIFY THE
 CLASSIFICATION THAT YOU PLACED ON THE STRUCTURE. IF YOU
 WOULD HAVE NOTED ON THE PREVIOUS SET THAT IT WAS THE
 MOST RESTRICTIVE I WOULD NOT HAVE RAISED THE QUESTION.
 2) 2ND REQUEST - SUBMIT A GAS RISER DIAGRAM FOR
 REVIEW.SHOW THE TYPE OF PIPING MATERIAL, LENGTHS OF
 EACH PIPE SECTION, BTU LOAD OF EACH APPLIANCE & TOTAL
 BTU LOAD ON THE SYSTEM, COMBUSTION AIR REQUIREMENTS,
 VENTING, LOCATION OF VALVES, REGULATORS, ETC. OR PLACE
 A NOTE ON BOTH SETS OF PLANS THAT GAS SHALL BE UNDER A
 SEPARATE PERMIT.
 3) 2ND REQUEST - SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS EQUIPMENT & APPLIANCES. APPLIANCES
 SHALL BE LISTED AND LABELED PER THE 2010 FGC SEC.301.3.
 4) THE REQUIRED CLEARANCE AROUNFD A WATER CLOSET SHALL
 BE A MINIMUM OF 60 INCHES MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. YOU HAVE A DIMENSION
 OF 5 FT. BY 4FT-6 INCHES WHICH DOES NOT COMPLY. REFER
 TO THE THE 2010 FL. ACCESS. CODE SEC. 604.3. YOU ONLY
 NEED TO SHOW THESE DIMENSIONS ONCE ON THE ENLARGED
 TOILET ROOM PLAN ON SHT.A-1.2.
 5) THE GREASE TRAP SHALL BE CONSTRUCTED IN ACCORDANCE
 WITH THE 2010 FPC SEC.1003.3.4. 2ND REQUEST. SUBMIT
 DETAILS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By tklarge Date 2014-09-02 Time   Rev Time  
Received By tklarge Date 2014-08-31 Time   Sent To  
Notes
2014-09-02 12:29:21WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHT. A-0.0- CODE SUMMARY BLOCK - REFERENCE IS MADE
 TO THE 2010 FLORIDA BUILDING CODE W/ BOCA RATON
 AMENDMENTS. REVISE THIS TO READ CITY OF WEST PALM
 BEACK.
 2) THE ADDRESS OF THE PROJECT ON THE APPLICATION DOES
 NOT MATCH THE ADDRESS ON THE PLANS. CORRECT THE PLANS
 TO REFLECT THE CORRECT ADDRESS.
 3) SHT. A-0.0- BUILDING CODE BLOCK- THIS PROJECT IS
 NOTED AS AN A-2 OCCUPANCY. IT IS ACTUALLY A MIXED
 OCCUPANCY OF SEVERAL CLASSIFICATIONS SUCH AS A-1, A-3,
 A-4, B,ETC. HOW CAN THIS BUILDING BE CLASSIFIED AS AN
 A-2 IN IT'S ENTIRETY? CLARIFY.2010FBC SEC.508.1
 4) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES SHALL BE
 BASED ON THE DIFFERENT OCCUPANCIES. 2010 FPC SEC.403.1.
 I AM QUESTIONING YOUR AREA PER PERSON CALCULATIONS ON
 SHT. A-0.0- UNTIL YOU REVISE THE OCCUPANCIES & OCCUPANT
 LOAD, THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 CANNOT BE DETERMINED
 A) CONCESSION AREA - WHERE ARE YOU GETTING THE 200 SQ.
 FT. PER PERSON FROM?
 B) BOWLING AREA- SHOULD BE 7 SQ. FT. PER PERSONPER FBC
 TABLE 1004.1
 C) THEATRE LOBBY- SHOULD BE 5 SQ. FT. PER PERSON NET
 FOR STANDING AREA.
 5) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2010 FGC SEC.301.3.
 6) SUBMIT A GAS RISER FOR REVIEW. SHOW TYPE OF PIPING
 MATERIAL, LENGTHS OF EACH PIPE SECTION, BTU
 LOAD,COMBUSTION AIR, VENTING, LOCATION OF VALVES,
 METER, REGULATOR, ETC.2010 FGC SECS.304,402.1,.
 7) SHOW THE REQUIRED DIMENSIONS OF THE CLEAR FLOOR
 SPACES FOR THE HANDICAPPED URINAL AND FOR THE FIXTURES
 IN THE ACCESSIBLE TOILET ROOMS.2010 FAC SEC., 305.
 8) SHT. A-1.2- A MINIMUM 30" X 60 " CLEARANCE SHALL BE
 PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER
 COMPARTMENT PER THE 2010 FAC SEC.608.2.2.1.
 9) SHT.A-1.2- SHOW THE LOCATION OF THE GRAB BARS IN THE
 ACCESSIBLE SHOWERS.COMPLY W/ FAC SEC. 608.3.3.
 10) THE LOCATION OF THE SHOWER SPRAY UNIT (HEIGHT)
 SHALL COMPLY WITH THE 2010 FAC SEC.608.5.3. THE MAX.
 HEIGHT IS 48 INCHES ABOVE THE SHOWER FLOOR.
 11) SHT. A-1.2 - THERE IS A NOTE ON THE PLAN THAT
 REFERS TO INTERIOR DESIGN DRAWINGS FOR LOCATIONS AND
 MOUNTING HEIGHTS OF ITEMS IN THE RESTROOMS. THERE ARE
 NO INTERIOR DESIGN DRAWINGS IN THE PLANS. SUBMIT THESE
 DRAWINGS FOR REVIEW.
 12) SHT. A-1.2- THE REAR WALL AND SIDE WALL GRAB BARS
 SHALL COMPLY W/ THE 2010 FAC SECS. 604.5.1 & 604.5.2.
 13)SHT. A-1.2- THE MOUNTING HEIGHT OF THE TOILET PAPER
 DISPENSER SHALL COMPLY W/ THE 2010 FAC SEC.604.7.
 14) SHT. A-1.2.- THE DOOR FOR THE AMBULATORY
 COMPARTMENT STALL SHALL NOT SWING INTO THE STALL PERR
 THE 2010 FAC SEC.604.8.2.2.
 15) SHT.A-4.1- SUBMIT A STORM WATER RISER FOR REVIEW.
 THE SQUARE FOOTAGE OF THE AREAS OF THE SLOPED ROOFS
 THAT DRAIN ONTO THE FLAT ROOF SHALL BE INCLUDED IN THE
 TOAT SQUARE FOOTAGE FOR THE SIZING OF THE STORM SYSTEM.
 WPB ADMIN. AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 16) SHT. A-4.1- VERTICAL LEADER CALCULATIONS- WHERE
 DOES THE 114 SQ. FT. COME FROM?
 17) SHT. A-4.1 - SCUPPERS SHALL BE SIZED PER THE 2010
 FPC SEC.1106.7 & TABLE 1106.7. SUBMIT CALCULATIONS AS
 TO HOW YOU ARRIVED AT THE STATED SIZES.
 18) SHT. A-4.1-FLAT ROOF NOTES- NOTE #8- SCUPPERS SHALL
 NOT HAVE AN OPENING LESS THAN 4 INCHES PER THE 2010 FPC
 SEC.1107.3.
 19) SIZE ALL SECTIONS OF THE SANITARY RISER- ( WET
 SECTIONS OF URINALS, LAVS, HORIZONTAL BRANCH FOR THE
 DRINKING FOUNTAINS, SIZE ALL SECTIONS OF THE FIXTURE
 BRANCHES).
 20) THE DEVELOPED LENGTH FOR THE 2" VENT FROM THE MEN'S
 RESTROOM WATER CLOSETS TO WHERE IT CONNECTS TO THE 3"
 VTR APPEARS THAT IT MAY EXCEED 40 FT. IN LENGTH. IF SO,
 THE 2" VENT SHALL BE INCREASED TO 3" FOR IT'S ENTIRE
 LENGTH PER THE 2010 FPC SEC.916.2. SHOW THE DEVELOPED
 LENGTH ON THE SANITARY RISER.
 21) SHOCK ARRESTORS ARE REQUIRED ON THE REFRIGERATOR
 ICE LINE. 2010 FPC SEC.604.9.
 22) SUBMIT CONSTRUCTION SPECIFICATIONS FOR THE GREASE
 INTERCEPTOR.COMPLY W/2010 FPC SEC.1003.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-11-18 Cont ID  
Sent By ajones Date 2014-11-18 Time 17:44 Rev Time 0.00
Received By ajones Date 2014-11-18 Time 17:44 Sent To AD
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-05 Cont ID  
Sent By avann Date 2014-08-05 Time 17:23 Rev Time 0.00
Received By ajones Date 2014-08-05 Time 17:22 Sent To  
Notes
2014-08-05 17:23:288/5/14- FAILED- CHANGES TO THE APPROVED CLUBHOUSE
 REQUIRED A MINOR AMENDMENT TO THE RPD.
  
 ANGELLA VANN
 561-822-1441
 [email protected]
2014-08-01 09:52:298/1/14