Plan Review Details - Permit 14070978
Plan Review Stops For Permit 14070978
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 07:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 06:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-09-16 Cont ID  
Sent By dhayes Date 2014-09-16 Time 14:43 Rev Time 0.00
Received By dhayes Date 2014-09-16 Time 14:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 13:56 Rev Time 0.00
Received By dhayes Date 2014-09-03 Time 13:56 Sent To  
Notes
2014-09-03 14:20:26DATE: 9/3/2014
 PROJECT: SUSHI YAMA
 PERMIT#: 14070978
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS.
  
 1) PROVIDE POWER RISER DIAGRAM INDICATING THE LOCATION
 OF THE ELECTRICAL SERVICE ON THE BUILDING AND THE SIZE
 OF THE DISCONNECTS AND FEEDERS.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE
 BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE
 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 5) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR
 AIR CONDITIONING AND REFRIGERATION EQUIPMENT.
  
 6) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. SEE NEC 210.63,
 210.8(A)(3), AND 406.8(B)(1),
  
 7) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN
 HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE
 SEQUESNCE OF EVENTS UPON ACTIVATION.
  
 8) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD
 FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM,
 NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-12 Cont ID  
Sent By dhayes Date 2014-08-12 Time 14:01 Rev Time 0.00
Received By dhayes Date 2014-08-12 Time 12:08 Sent To  
Notes
2014-08-12 14:01:32DATE: 8/6/2014
 PROJECT: SUSHI YAMA
 PERMIT#: 14070978
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 107.2.1 PLEASE PROVIDE
 ADDITIONAL DETAIL TO THE PLANS AS FOLLOWS:
  
 2) PROVIDE ALLL CIRCUITRY ON THE FLOOR PLAN AND PANEL
 SCHEDULE, INCLUDE THE EXISTING OUTLETS, AND AS WELL AS
 THE NEW OUTLETS AND DISCONNECTS AS REQUIRED TO MATCH
 THE EQUIPMENT PLAN AS INDICATED ON SHEET 5.
  
 3) PROVIDE POWER RISER DIAGRAM, AND THE LOCATION OF THE
 ELECTRICAL SERVICE ON THE BUILDING.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE
 BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE
 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 7) PROVIDE A LIGHTING PLAN, INDICATE ALL GENERAL
 PURPOSE LIGHTING TASK LIGHTING, SPECIALTY LIGHTING,
 SECURITY LIGHTING, EXIT AND EMERGENCY LIGHTING TO
 COORDINATE WITH THE LIFE SAFETY PLAN.
  
 8) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR
 AIR CONDITIONING AND REFRIGERATION EQUIPMENT.
  
 9) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. SEE NEC 210.63,
 210.8(A)(3), AND 406.8(B)(1),
  
 10) PROVIDE LIGHTING CONTROL. FBC-ENERGY
 A. 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS
 LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS.
  
 B. 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 11) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN
 HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE
 SEQUESNCE OF EVENTS UPON ACTIVATION. WHAT IT CONTROLS
 AND HOW IT CONTROLS IT.
  
 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD
 FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM,
 NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By pleduc Date 2014-08-20 Time   Rev Time 0.00
Received By pleduc Date 2014-08-20 Time 15:04 Sent To  
Notes
2014-08-20 15:17:42PREVIOUSLY SUBMITTED COMMENTS:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 DUE TO THE RENOVATIONS, AN EVALUATION OF THE FIRE ALARM
 AND SPRINKLER SYSYEMS IS REQUIRED FOR CODE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-30 Cont ID  
Sent By pleduc Date 2014-07-30 Time   Rev Time 0.00
Received By pleduc Date 2014-07-30 Time 12:33 Sent To  
Notes
2014-07-30 13:13:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 DUE TO THE RENOVATIONS, AN EVALUATION OF THE FIRE ALARM
 AND SPRINKLER SYSYEMS IS REQUIRED FOR CODE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 07:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 06:35 Sent To  
Notes
2014-08-04 07:35:18GAS PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 DATE: MON. AUG. 04/ 2014
 ACTION: DENIED
  
 SHEET 5 LIST GAS APPLIANCES, NO OTHER INFORMATION WAS
 PROVIDED FOR REVIEW. A SEPARATE GAS PERMIT WIL BE
 REQUIRED. GAS PERMIT APPLICATION REQUIREMENTS,
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-19 Time 09:44 Rev Time 0.00
Received By tklarge Date 2014-09-18 Time 07:00 Sent To  
Notes
2014-09-19 09:48:079/19/14- APPROVED/OUT FRONT UNDER LARGE "S". TKL.
2014-09-19 07:01:34SENT TO T LARGE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2014-09-18 Time   Rev Time 0.00
Received By dhayes Date 2014-09-16 Time 14:43 Sent To E
Notes
2014-09-18 12:14:069/18/14-DENIED- E-MAOLED CONTRACTOR/PLANS PLACED UNDER
 LARGE "S". TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 13:57 Rev Time 0.00
Received By dhayes Date 2014-08-19 Time 14:40 Sent To  
Notes
2014-08-19 14:40:25B28
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-12 Cont ID  
Sent By dhayes Date 2014-08-12 Time 14:01 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 10:27 Sent To  
Notes
2014-07-28 10:27:30SENT TO B11 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2014-08-26 Time   Rev Time 1.00
Received By   Date   Time   Sent To  
Notes
2014-08-26 15:04:26ANSUL PERMIT AND TESTING REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 08:36 Sent To  
Notes
2014-08-04 09:01:02MECHANICAL PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 DATE: MON. AUG. 04/ 2014
 ACTION: DENIED
  
 1) NO MECHANICAL SHEETS PROVIDED, SHEET # 1 DOES HAVE
 MECHANICAP NOTES, SHEET # 5 NOTES 11 & 20 INDICATE A
 ANSUL SYSTEM AND TYPE I HOOD, NO INFORMATION AS TO MAKE
 UP AIR FOR THE NEW GAS APPLIANCES, ... 2010 FBC-FUEL
 GAS SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304S.
  
 2) 2010 FBC-M. 420.3.14.13 SPACES HAVING EXHAUST HOODS
 SHALL HAVE SUFFICIENT MAKE-UP SUPPLY AIR SUCH THAT THE
 REQUIRED PRESSURE RELATIONSHIP WILL NOT BE AFFECTED BY
 THE OPERATION OF THE HOOD. 503.2.5.2.2.1
 NON-RESIDENTIAL KITCHEN SPACES.
 NON-RESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS
 OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED
 BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1. BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR
 BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE
 PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING
 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES
 SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING
 HOURS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-19 Time 09:43 Rev Time 0.00
Received By tklarge Date 2014-09-19 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-09-18 Cont ID  
Sent By tklarge Date 2014-09-18 Time 12:02 Rev Time 0.00
Received By tklarge Date 2014-09-17 Time 06:12 Sent To  
Notes
2014-09-18 12:08:481) THE CALCULATIONS YOU HAVE PROVIDED FOR THE SIZING OF
 THE GREASE INTERCEPTOR ARE INADEQUATE. THE GALLONS OF
 WASTE PER SEAT THAT YOU HAVE USED (10 GALS.) IS
 INADEQUATE. YOU WILL NEED TO USE A FACTOR OF 25 GALS.
 OER SEAT. THIS WILL REQUIRE 2-1200 GALLON TANKS IN
 SERIES TO COMPLY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 07:43 Sent To  
Notes
2014-08-27 08:32:54PLUMBING PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND EVIEW
 DATE: WED. AUG. 27/ 2014
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
 1)2ND REQUEST. SHEET 7 GREASY WASTE ISOMETRIC. SHOW THE
 COMPLETE GREASY WASTE NO BREAK LINES, ALSO SHOW WHAT IS
 BEING ELIMINATED FROM THE GREASY WASTE SYSTEM.IS THE
 COMPLETE GREASY WASTE INTERCEPTOR ABOVE GROUND, BELOW
 GROUND, PROVIDE SIZING OF THE EXISTING GREASE
 INTERCEPTOR, FLOW CONTROL DEVICE AND VENTING 2010 FBC-P
 1003.3.4.1 & 1003.3.4.2.
 MISSING IN THE WASH UP ROOM (3) COMPARTMENT
 SINK,SERVICE SINK, HAND SINK AND DISHWASHER AND THE (1)
 REMAINING TRENCH DRAIN UNDER THE 3 COMPARMENT SINK.
 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR
 OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 2) 2ND REQUEST MISSING REQUIRED FIXTURES. SHEET 7
 PLEASE PROVIDE THE FORMULA USED FOR SIZING OF THE
 EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR SHALL
 BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE SECTION
 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW CONTROL
 (1003.3.4.2) OR FOR CONCRETE VAULT TYPE INTERCEPTORS
 (TABLE 1003.5.1).
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3
 COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE
 SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8.
  
 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED
 FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP.
  
 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE
 FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH
 AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE
 RECEPTOR IN ACCORDANCE WITH SECTION 802.2.
  
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 4) PROVISO: BE VARIFIED IN FIELD!!!! SHEET 7 SHOWS (3)
 COMPARTMENT SINKS, HAND SINKS, DISHWASHER WASTE(NOT
 SHOWN) WITH NO TRAPS. PLEASE REVIEW 2010 FBC-P 802.2
 INSTALLATION. ALL INDIRECT WASTE PIPING SHALL DISCHARGE
 THROUGH AN AIR GAP OR AIR BREAK INTO A WASTE RECEPTOR
 OR STANDPIPE. WASTE RECEPTORS AND STANDPIPES SHALL BE
 TRAPPED AND VENTED AND SHALL CONNECT TO THE BUILDING
 DRAINAGE SYSTEM. ALL INDIRECT WASTE PIPING THAT EXCEEDS
 2 FEET (610 MM) IN DEVELOPED LENGTH MEASURED
 HORIZONTALLY, OR 4 FEET (1219 MM) IN TOTAL DEVELOPED
 LENGTH, SHALL BE TRAPPED.
  
 5) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR
 POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES
 REQUIRING POTABLE WATER. ICE MACHINES, ICE CHEST WHICH
 REQUIRE INDIRECT WASTE AND COMPLIANCE TO WITH 802.1.3
 POTABLE CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO
 THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 6) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR
 POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES
 REQUIRING POTABLE WATER:
 SEE THE 2010 FBC-P:
 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED
 WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM.
 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE
 DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 06:36 Sent To  
Notes
2014-08-04 08:31:29PLUMBING PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 DATE: MON. AUG. 04/ 2014
 ACTION: DENIED
  
 1) SHEET 7 SHOWS THE GREASY WASTE ISOMETRIC, PLEASE
 SHOW THE COMPLETE GREASY WASTE TO THE GREASE
 INTERCEPTOR, MISSING THE WASH UP ROOM WITH (3)
 COMPARTMENT SINK,SERVICE SINK, HAND SINK AND
 DISHWASHER. 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. A GREASE
 INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE
 REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES AND
 EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS. FIXTURES AND
 EQUIPMENT SHALL INCLUDE POT SINKS, PRERINSE SINKS; SOUP
 KETTLES OR SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS
 OR SINKS INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD
 WASH UNITS AND DISHWASHERS WITHOUT PRERINSE
 SINKS.GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED.
  
 2) SHEET 7 PLEASE PROVIDE THE FORMULA USED FOR SIZING
 OF THE EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR
 SHALL BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE
 SECTION 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW
 CONTROL (1003.3.4.2) OR FOR CONCRETE VAULT TYPE
 INTERCEPTORS (TABLE 1003.5.1).
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3
 COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE
 SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8.
  
 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED
 FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP.
  
 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE
 FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH
 AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE
 RECEPTOR IN ACCORDANCE WITH SECTION 802.2.
  
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 4) SHEET 7 SHOWS (3) COMPARTMENT SINKS, HAND SINKS,
 DISHWASHER WASTE(NOT SHOWN) WITH NO TRAPS. PLEASE
 REVIEW 2010 FBC-P 802.2 INSTALLATION. ALL INDIRECT
 WASTE PIPING SHALL DISCHARGE THROUGH AN AIR GAP OR AIR
 BREAK INTO A WASTE RECEPTOR OR STANDPIPE. WASTE
 RECEPTORS AND STANDPIPES SHALL BE TRAPPED AND VENTED
 AND SHALL CONNECT TO THE BUILDING DRAINAGE SYSTEM. ALL
 INDIRECT WASTE PIPING THAT EXCEEDS 2 FEET (610 MM) IN
 DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 4 FEET (1219
 MM) IN TOTAL DEVELOPED LENGTH, SHALL BE TRAPPED.
  
 5) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER
 OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE
 WATER. ICE MACHINES, ICE CHEST WHICH REQUIRE INDIRECT
 WASTE AND COMPLIANCE TO WITH 802.1.3 POTABLE
 CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO THE
 BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 6) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER
 OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE
 WATER:
 SEE THE 2010 FBC-P:
 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED
 WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM.
 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE
 DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  