Plan Review Details - Permit 14070976
Plan Review Stops For Permit 14070976
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2014-11-18 Cont ID  
Sent By tklarge Date 2014-11-18 Time 12:42 Rev Time 0.00
Received By tklarge Date 2014-11-18 Time 12:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-11-10 Cont ID  
Sent By tklarge Date 2014-11-10 Time 12:06 Rev Time 0.00
Received By tklarge Date 2014-11-10 Time 09:54 Sent To  
Notes
2014-11-10 10:28:431) THE GAS SIZING TABLE FOR THE SCH.40 PIPE IS FROM A
 WEBSITE TITLED "ENGINEERING TOOLBOX." THIS IS NOT A
 RECOGNIZED SIZING METHOD IN ACCORDANCE WITH THE 2010
 FL. GAS CODE SEC.402.3.SUBMIT A COPY OF THE APPLICABLE
 GAS TABLE FROM THE 2010 FGC.
 2) SHT.1 OF THE GAS DRAWING SHOWS A 3/4" GALVANIZED
 LINE SUPPLYING THE GAS RANGES AND SHT. 2 SHOWS A 1" AND
 A 1 1/4" WARDFLEX LINE SUPPLYING THE DRYERS. CLARIFY.
 3) THE MIN. SIZE SCH. 40 PIPE TO SUPPLY BOTH RANGES
 SHALL BE 1 " PER TABLE 402.4 (2). THE MAX. LOAD ON A
 3/4" PIPE IS 104,000.
 4) BASED ON THE TOTAL BTU LOAD OF THE SYSTEM, THE MAIN
 GAS LINE FROM THE METER SHALL BE 2" IN ACCORDANCE WITH
 TABLE 402.4 (2) OF THE 2010 FGC. A MAX. OF 532,000
 BTU'S IS PERMITED ON AN 1 1/2 SCH. 40 LINE.
 5) INDICATE THE LOCATION OF THE METER ON THE GAS
 DRAWING.
 6) THE 1 "WARDFLEX LINE SUPPLYING THE LINE TO THE TWO
 RANGES IS UNDERSIZED ACCORDING TO THE WARDFLEX TABLE
 THAT WAS SUBMITTED.
 7) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2010
 FGC SEC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-10-20 Cont ID  
Sent By tklarge Date 2014-10-20 Time 14:35 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 14:35 Sent To  
Notes
2014-10-20 14:37:351) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLES
 FOR THE PIPE MATERIAL FROM THE 2010 FGC.
 2) SHOW THE TOTAL DISTANCE OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET PER THE 2010 FGC
 SEC.402.4.1.
 3) SHOW THE TOTAL BTU LOAD ON THE SYSTEM. WPB AMEND. TO
 2010 FGC SEC. 107.2.1.
 4)IDENTIFY ALL THE APPLIANCES ON THE GAS DRAWING. WPB
 AMEND. TO 2010 FGC SEC. 107.2.1.
 5) INDICATE THE OPERATING PRESSURE (PSI) OF THE SYSTEM.
 WPB AMEND. TO 2010 FGC SEC. 107.2.1.
 6) SOME OF THE BTU LOADS ARE HARD TO READ.
 7) SHOW THE CORRESPONDING EHD FOR THE DIFFERENT SIZE OF
 THE CSST.
 8) PART OF THE INFO ON THE TOP OF THE GAS PIPING
 DRAWING IS CUT OFF.
 9) DETAILS # 1& #2 - WHAT ARE THE 3/4" CAPPED OFF LINES
 FOR ON THE GAS PIPING DRAWING.
 10) WHAT IS THE 75,000 BTU LOAD SHOWN AT THE TOP OF THE
 PAGE FOR DETAILS #1 & # 2 ? THE PIPING PLAN SHOWS THE
 APPLIANCE AS 150,000 BTU'S.
 11) WHAT TYPE OF APPLIANCE IS DETAIL #1 & DETAIL #2.
 THIS DRAWING IS CONFUSION.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-01 Cont ID  
Sent By gsalfeld Date 2014-08-01 Time 15:18 Rev Time 0.00
Received By gsalfeld Date 2014-08-01 Time 14:46 Sent To  
Notes
2014-08-01 15:18:34FUEL GAS PLAN REVIEW
 PERMIT: 14070976
 ADD: 815 UPLAND RD
 CONT: MASTER PLAN INC.
 TEL: 954 692 4816
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 9/1/2014
 ACTION: DENIED
  
  
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS. ALL OF THE PIPEING IS NOT CLEARLY
 MARKED , MISSING DIMENSIONS FOR SECTIONS OF PIPE
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. JOBSITE
 CONDITIONS DO NOT REFLECT THE MATERIAL AS SHOWN ON
 PLANS. PIPE DIAMETER TO BE INCREASED OR A 2 PSI SYSTEM.
 REGULATORS WILL BE REQUIRED AT APPLIANCE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) TOTAL
 BTU ARE INCORECT
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) TOTAL DEVELOPED LENGTH
 OF PIPE IS INCORECT.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 8. SEPERATE PERMIT REQUIRED FOR GAS FOR TRACKING /
 INSPECTIONS.
  
 9. 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING
 BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR
 UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN
 SECTION R315.1.3.
 R315.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED
 BY PROVIDING FOR ONE OF THE FOLLOWING ALARM
 INSTALLATIONS:
 (1) A HARD-WIRED CARBON MONOXIDE ALARM.
 (2) A BATTERY-POWERED CARBON MONOXIDE ALARM.
 (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
 (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 GARY SALFELDER PLAN REVIEW
 561 805 6694
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2014-11-18 Cont ID  
Sent By tklarge Date 2014-11-18 Time 12:41 Rev Time 0.00
Received By tklarge Date 2014-11-18 Time 12:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-10 Cont ID  
Sent By tklarge Date 2014-11-10 Time 12:06 Rev Time 0.00
Received By tklarge Date 2014-11-10 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-10 Cont ID  
Sent By tklarge Date 2014-10-20 Time 09:53 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 12:12 Sent To  
Notes
2014-10-20 12:12:54TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-01 Cont ID  
Sent By gsalfeld Date 2014-08-01 Time 15:19 Rev Time 0.00
Received By gsalfeld Date 2014-07-25 Time 16:53 Sent To  
Notes
2014-07-25 16:53:57REVISION SENT TO JIM WITMER'S DESK FOR REVIEW. JG.