Plan Review Details - Permit 14070924
Plan Review Stops For Permit 14070924
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-24 Cont ID  
Sent By jwitmer Date 2014-08-24 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2014-08-24 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 10:06 Rev Time 0.00
Received By rlecky Date 2014-09-09 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-22 Cont ID  
Sent By rlecky Date 2014-08-22 Time 11:08 Rev Time 0.00
Received By rlecky Date 2014-08-22 Time 10:29 Sent To  
Notes
2014-08-22 11:12:27 
 14070924
 222 LAKEVIEW AVE. #1700
 TENANT IMPROVEMENT
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 SHOW ALL EXISTING FEEDERS WITH WIRE AND CONDUIT SIZE.
 PROVIDE THE WIRE AND CONDUIT SIZE PROPOSED FOR THE
 RELOCATED PANELS. SHOW THE LOCATION OF THE SECONDARY
 OVER CURRENT PROTECTION REQUIRED AT THE TRANSFORMER FOR
 THE FEEDER AND THE PANEL BOARDS. THE RISER PLAN AND THE
 PANEL BOARD SCHEDULES DO NOT SEEM TO MATCH. NEC 215.5,
 240.4, 240.21, 240.21(C)
  
 PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-04 Cont ID  
Sent By scaldero Date 2014-08-04 Time 08:36 Rev Time 0.00
Received By scaldero Date 2014-08-04 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 10:06 Rev Time 0.00
Received By rlecky Date 2014-09-08 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-24 Cont ID  
Sent By jwitmer Date 2014-08-24 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2014-07-28 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-16 Cont ID  
Sent By hmoser Date 2014-08-16 Time 07:42 Rev Time 0.00
Received By hmoser Date 2014-08-16 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-08-24 Cont ID  
Sent By jwitmer Date 2014-08-24 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2014-08-24 Time 13:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 16:36 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 16:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 14:19 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 14:19 Sent To  
Notes
2014-10-01 14:27:011ST REVIEW: FBC 2010
  
 THE SIGNATURE DOCUMENTS AND SIGNATURE REPORTS SUBMITTED
 WERE INCOMPLETE. THE INFORMATION FOR THE MEPAND FP
 DESIGNS WAS ACCEPTABLE. THERE IS NO SIGNATURE REPORT
 PROVIDED FOR THE A, CVR, & D SHEETS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-30 Cont ID  
Sent By ajones Date 2014-07-30 Time 09:44 Rev Time 0.00
Received By ajones Date 2014-07-30 Time 09:44 Sent To  
Notes
***NONE***