Plan Review Details - Permit 14070902
Plan Review Stops For Permit 14070902
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 11:53 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 11:35 Sent To  
Notes
2014-07-31 14:56:02RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS AND CONTRACTOR'S OVERHEAD
 AND PROFIT. UPDATE VALUATION AS REQUIRED.
  
 2- PROVIDE ACCORDION SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. INSTALLATION SCHEDULE SUBMITTED IS
 INCOMPLETE. NEED TO FILL THE INFORMATION IN ALL THE
 COLUMNS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 3- PAGE 14 OF 16 OF ACCORDION SHUTTERS DRAWINGS
 SUBMITTED ARE FOR DETAIL 10T TOP INSTALLATION AND
 DETAIL 10B BOTTOM INSTALLATION. CLARIFY HOW INSTALLING
 THE ACCORDION SHUTTERS PER DETAIL 10T TOP INSTALLATION.
 WHERE IS THE 1/8" X 4" ALUMINUM PLATE ATTACHED TO?.
 ACCORDING TO ELEVATIONS SUBMITTED, THERE ARE NOT
 CONDITIONS SHOWING A 10T TYPE OF INSTALLATION. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4-PERMIT APPLICATION CALL S FOR "INSTALL SHUTTERS (AND
 REMOVABLE)" . PLEASE CLARIFY HOW ACHIEVING THIS.
 ACCORDION SHUTTERS ARE TYPICALLY PERMANENT
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 ***NOTE: IF REMOVABLE PANELS ARE GOING TO BE INSTALLED,
 THEN PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By fmittner Date 2014-08-07 Time 13:49 Rev Time 0.00
Received By fmittner Date 2014-08-07 Time 13:49 Sent To  
Notes
2014-08-07 14:00:55ACCORDIAN SHUTTERS NOT PERMITTED IN HISTORIC DISTRICTS.
 FRIEDERIKE MITTNER LEFT VOICE MAIL WITH NICK BESSENROTH
 TO CHANGE PRODUCT APPROVALS. FILED UNDER SMALL PLANS
 DENIED "B". QUESTIONS CALL 822-1457.
2014-08-04 14:48:258/4/14 ZONING SENT TO FM. SG

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 15:06 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 15:06 Sent To  
Notes
2014-07-31 15:21:207/31/14 SENT TO ZONING SHELF FOR HISTORIC REVIEW. JG.
2014-07-24 09:55:36ROUTED TO BLDG $5000 & UNDER