2014-07-29 07:56:34 | PLUMBING PLAN REVIEW |
| PERMIT:14070851 |
| ADD: 1815 PALM BEACH LAKES BLVD (STAR BUCKS & PEI WEI) |
| CONT:EMJ |
| TEL: LEXIE 348-4805 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JULY 29/2014 |
| |
| ACTION: PLUMBING PROVISO |
| |
| THIS GREASE INTERCEPTOR HAS BEEN DESIGNED UNDER THE |
| 2010 FBC-PLUMBING CODE SECTION CONCRETE VAULT TYPE |
| INTERCEPTORS (TABLE 1003.5.1). |
| |
| THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| FAHRENHEIT (65.56 DEGREES CELSIUS). |
| |
| IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE |
| INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| MUNICIPAL CODE OF ORDINANCES. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |