Plan Review Details - Permit 14070713
Plan Review Stops For Permit 14070713
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By shill Date 2014-09-09 Time 10:42 Rev Time 0.00
Received By shill Date 2014-09-09 Time 10:42 Sent To FIRE
Notes
2014-09-09 10:48:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INCLUDE BUILDING TYPE ON THE PLAN, FBC 107. I
 BELIEVE THAT THIS IS A TYPE II NON COMBUSTIBLE
 STRUCTURE. SEE FBC 603, COMBUSTIBLES ALLOWED IN TYPE I
 & II CONSTRUCTION. REVISE PLAN TO CLEARLY SHOW WHICH
 EXEMPTION, IF ANY, THIS FALLS UNDER.
  
 AN OCCUPANCY CHANGE (FROM STORAGE TO ASSEMBLY) WAS DONE
 FOR THIS BUILDING AND ALL CONSTRUCTION IS TO COMPLY
 WITH THE MANDATORY BUILDING TYPE AS ALL AREA AND
 SPRINKLER INCREASES WERE NEEDED FOR THE CHANGE OF
 OCCUPANCY.
  
 2. PROVIDE A FLOOR PLAN SHOWING PROPOSED LOCATION AND
 HOW THIS PROPOSED IMPROVEMENT AFFECTS EGRESS TRAVEL,
 FBC CHAPTER 10.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By pleduc Date 2014-09-09 Time   Rev Time 0.00
Received By pleduc Date 2014-09-09 Time 15:32 Sent To PC
Notes
2014-09-09 15:51:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE PROPOSED SKATEBOARD RAMP REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE.
  
 THE PROPOSED RAMP IS MADE OF WOOD WITH HOLLOW VOIDS
 UNDERNEATH. THE NOISE LEVEL CREATED DURING USE MAY
 RENDER THE EXISTING FIRE ALARM NOTIFICATION VOLUMES
 INEFFECTIVE. ADDITIONAL NOTIFICATION DEVICES WITH
 HIGHER VOLUMES MAY BE REQUIRED. AN EVALAUTION AND
 TESTING IS REQUIRED BY A CERTIFIED FIRE ALARM
 CONTRACTOR.
  
 THE PROPOSED WOOD RAMP ADDS A SIGNIFICANT CONCENTRATED
 FIRE LOAD TO THE INSTALLED AREA. AN EVALUATION OF THE
 SPRINKLER SYSTEM AND SPRINKLER HEAD COVERAGE OF THE
 AREA BY A CERTIFIED FIRE SPRINKLER CONTRACTOR IS
 REQUIRED.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 A SITE PLAN IS NEEDED TO SHOW THE LOCATION OF THE
 PROPOSED RAMP IN THE PROPOSED ROOM OF INSTALLATION
 INCLUDING FLOOR DIMENSIONS AND EXITS.
  
 A LIFE SAFETY PLAN IS REQUIRED TO SHOW THE AREA OF
 INSTALLATION INCLUDING THE TOTAL BUILDING FOOTPRINT,
 OCCUPANY LOADS, EXIT PATHS, EXITS, AND EXIT DISCHARGES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By pleduc Date 2014-09-09 Time 15:51 Rev Time 0.00
Received By pleduc Date 2014-07-21 Time 16:51 Sent To PC
Notes
2014-09-09 10:49:29TO FIRE
  
2014-07-21 16:51:19SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-23 Cont ID  
Sent By sgraham Date 2014-07-23 Time 10:26 Rev Time 0.00
Received By sgraham Date 2014-07-23 Time 10:26 Sent To B
Notes
***NONE***