Plan Review Details - Permit 14070577
Plan Review Stops For Permit 14070577
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By skennedy Date 2014-10-16 Time 13:26 Rev Time 0.00
Received By skennedy Date 2014-10-16 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By skennedy Date 2014-09-04 Time 11:21 Rev Time 0.00
Received By skennedy Date 2014-09-04 Time 11:21 Sent To  
Notes
2014-09-04 11:41:571ST REVIEW: FBC 2010
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2. BASED ON EXPOSURE D.
 PAGE S-2.0 INDICATES EXPOSURE C. THIS PROPERTY HAS A D
 EXPOSURE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) &
 R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION PLUS 6" .
 PROVIDE FLOOD DESIGN INFORMATION TO THE PROPOSED SURVEY
 AND PROVIDE FLOOD ELEVATION CERTIFICATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-04 Cont ID  
Sent By sciard Date 2014-09-04 Time 13:26 Rev Time 0.00
Received By sciard Date 2014-09-04 Time 13:26 Sent To  
Notes
2014-09-04 13:28:13N.E.C. 210.8(A)2. GFCI PROTECTION ALL RECPATCLES IN
 GARAGE INCLUDING GDO.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-16 Cont ID  
Sent By skennedy Date 2014-10-16 Time 14:23 Rev Time 0.00
Received By skennedy Date 2014-10-14 Time 12:14 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-04 Cont ID  
Sent By sciard Date 2014-09-04 Time 13:30 Rev Time 0.00
Received By sciard Date 2014-07-17 Time 13:18 Sent To  
Notes
2014-07-17 13:19:10INCOMING SENT TO R19. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 15:27 Rev Time 0.00
Received By skennedy Date 2014-11-03 Time 15:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-10-16 Cont ID  
Sent By skennedy Date 2014-10-16 Time 10:32 Rev Time 0.00
Received By skennedy Date 2014-10-16 Time 10:32 Sent To  
Notes
2014-10-16 10:33:33SEE COMMENTS FROM 09/04/2014.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By skennedy Date 2014-09-04 Time 12:38 Rev Time 0.00
Received By skennedy Date 2014-09-04 Time 12:38 Sent To  
Notes
2014-09-04 12:38:43PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2014-08-20 Time   Rev Time 0.50
Received By   Date   Time   Sent To  
Notes
2014-11-03 15:33:01REVIEW BY JOHN ARITON
2014-08-20 14:25:45PLANS AND ENERGY APPROVED

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-10-21 Cont ID  
Sent By shill Date 2014-10-21 Time 11:42 Rev Time 0.00
Received By shill Date 2014-10-16 Time 10:46 Sent To  
Notes
2014-10-21 10:34:39****PROVISO***
 ****PROVIDE "CONSTRUCTION DRAWINGS" ELEVATION
 CERTIFICATE AND REVISED SURVEY/SITE PLAN PRIOR TO FIRST
 INSPECTION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2010 RESIDENTIAL 322:
  
 1. ITEM A9(A), PLAN SHOWS AN 800 SF GARAGE. REVISE
 ELEVATION CERTIFICATE TO BE CONSISTENT WITH PROPOSED
 CONSTRUCTION.
  
 ELEVATION CERTIFICATE REFERS TO AN EXISTING GARAGE AND
 A PROPOSED DETACHED GARAGE. BASED ON THE PLAN, THIS IS
 ONE STRUCTURE.
  
 2. B8, FLOOD ZONE IS SHOWN AS B/A5. PLEASE REVISE
 SURVEY TO DEPICT THE FLOOD ZONE LINE (CRS MANUAL,
 432.O(3) ). REVISE SURVEY/SITE PLAN TO INCLUDE THE
 PROPOSED ADDITION (WITH ELEVATIONS) AND LOCATION AND
 ELEVATION OF ALL MECHANICAL AND UTILITY EQUIPMENT
 SERVICING THE BUILDING. ALSO REVISE THE SITE
 PLAN/SURVEY TO NOTE THAT THE SHED IS TO BE REMOVED.
  
 3. C2(E) SHOWS GARAGE AT 8', PLANS PROPOSE 7.5', PLEASE
 CORRELATE.
  
 COMMENTS SECTION STATES THAT GARAGE SQUARE FOOT AREA IS
 ROUNDED AND ACCESS UNAVAILABLE. A COMPLETED ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 4. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE AND
 PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND WILL BE REQUIRED FOR "FINISHED
 CONSTRUCTION" ELEVATION CERTIFICATE.
  
 5. SECTION D, COMMENTS, INCLUDE SOURCE OF
 LATITUDE/LONGITUDE.
  
 6. ORIGINAL SIGNED, SEALED ELEVATION CERTIFICATES WILL
 BE REQUIRED - BUILDING UNDER CONSTRUCTION, FINISHED
 CONSTRUCTION.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-08-30 Cont ID  
Sent By tklarge Date 2014-08-30 Time   Rev Time  
Received By tklarge Date 2014-08-30 Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-10-16 Cont ID  
Sent By skennedy Date 2014-10-16 Time 13:26 Rev Time 0.00
Received By skennedy Date 2014-10-16 Time 13:26 Sent To  
Notes
2014-10-16 13:27:13ROOFING

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-14 Cont ID  
Sent By skennedy Date 2014-10-16 Time 14:23 Rev Time 0.00
Received By sgraham Date 2014-10-14 Time 15:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-18 Cont ID  
Sent By sgraham Date 2014-07-18 Time 10:35 Rev Time 0.00
Received By sgraham Date 2014-07-18 Time 10:35 Sent To  
Notes
2014-07-18 10:36:417/18/14 SEPARATE PERMIT REQUIRED FOR FENCE, GATE AND