Plan Review Details - Permit 14070416
Plan Review Stops For Permit 14070416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By rmcdouga Date 2014-07-15 Time 06:50 Rev Time 0.00
Received By rmcdouga Date 2014-07-15 Time 06:50 Sent To  
Notes
2014-07-15 06:52:38RESEARCH OF THE GREEN CARDS INDICATE THAT THIS
 STRUCTURE ORIGINALLY HAD A TILE ROOF. THEREFORE, IT IS
 ACCEPTABLE TO RE-INSTALL A TILE ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-12 Cont ID  
Sent By rmcdouga Date 2014-07-12 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2014-07-12 Time 09:06 Sent To  
Notes
2014-07-12 09:14:092010 FBC
  
 DENIED BY BUILDING
  
 1) THE EXISTING ROOF COVERING IS ASPHALT SHINGLES AND
 THE PROPOSED ROOFING MATERIAL IS CONCRETE TILE. BECAUSE
 OF THE DIFFERENCE IN WEIGHT OF THE TWO ROOFING
 MATERIALS THE ROOF STRUCTURE WILL NEED TO BE EVALUATED
 BY A FLORIDA LICENSED ENGINEER TO DETERMINE THAT THE
 EXISTING STRUCTURE IS CAPABLE OF SUPPORTING THE
 ADDITIONAL DEAD LOAD. SUBMIT TWO COPIES OF THE SIGNED
 AND SEALED EVALUATION REPORT. FBCR 301.1 & CITY
 AMENDMENTS 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-07-11 Cont ID  
Sent By fmittner Date 2014-07-11 Time 16:28 Rev Time 0.00
Received By fmittner Date 2014-07-11 Time 16:28 Sent To  
Notes
***NONE***