2014-07-14 11:40:37 | BUILDING PLAN REVIEW |
| PERMIT: 14070297 |
| ADD: 515 37TH ST |
| CONT: BOUCHER GAS SERVICES |
| TEL: (561)964-8547 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 14/2014 |
| ACTION: DENIED |
| |
| 1) THERE IS NOT ENOUGH INFORMATION PROVIDED AS TO THE |
| LOCATION OF THE NEW PROPOSED GAS POOL WATER HEATER. |
| |
| 1A) THE SURVEY INDICATES BEHIND THE GARAGE 6'-0" TO THE |
| PREOPERTY LINE. WHERE IS THE POOL GAS HEATER TO BE |
| INSTALLED DISTANCE FROM THE STRUCTURE AND FROM THE |
| PROPERTY LINE? |
| |
| 1B) THE EXISITNG GARAGE, IS THE EXTERIOR WALLS CBS |
| WALL, OR WOOD FRAME WITH WOOD SIDING OR STUCCO? |
| |
| 1C) THE EXISTING GARAGE, IS THERE A OVERHANG WHERE THE |
| PROPOSED GAS POOL HEATER IS TO BE LOCATED OR SPANISH |
| STYLE WITH NO OVER HANG? |
| |
| 1D) THE SUBMITTED DOCUMENTS DOES NOT INDICATE IF THE |
| UNIT WILL BE OUTFITTED WITH A OUTDOOR STACK OR A |
| STACKLESS POOL GAS HEATER? |
| |
| THE MANUFACTURERS SPECIFICATIONS SHEET 12 INDICATES IF |
| THE UNIT IS INSTALLED WITH THE OUTDOOR STACK IS USED |
| THE AFFECT IS UNOBSTRUCTED, WILL NEED TO BE KEPT AWAY |
| FROM EAVE/ OVER HANG. IF A STCKLESS TOP IS USED 3'-0" |
| FROM COMBUSTIBLES MUST BE MAINTAINED. |
| |
| IF THE STACKLESS TYPE UNIT IS TO BE INSTALLED THERE ARE |
| ISSUES, SINCE THE UNIT HAS TO BE KEPT 3'FT AWAY FROM |
| COMBUSTIBLES, THE UNIT IS 2 FT WIDE, THE ZONING |
| REGULATIONS WILL ONLY ALLOW YOU TO SET THIS UNIT 3FT |
| INTO THE 5FT SET BACK REQUIREMENT. ANOTHER WORDS IT CAN |
| ONLY BE 2 FT FROM THE PROPERTY LINE. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3. ADDITIONAL |
| INFORMATION IS REQUIRED TO DETERMINE IF THIS POO GAS |
| HEATER CAN BE INSTALLED IN THE DESIRED LOCATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |