Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2014-07-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-07-10 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-07-10 |
Time |
15:23 |
Sent To |
|
|
Notes |
2014-07-10 15:27:29 | ***PROVISO*** | | ***ISSUED AT CONTRACTOR'S RISK**** | | | | AT INSPECTION, PROVIDE A FLOOR PLAN WHICH SHOWS | | LOCATIONS OF SINGLE HUNG AND HORIZONTAL ROLLER WINDOWS. | | | | FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS, THE | | CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE | | REDUCED BY MORE THAN 5%. | | | | 38" HIGH BEDROOM WINDOWS ARE SHOWN ON THE FLOOR PLAN. | | HORIZONTAL ROLLER WINDOWS ARE ASSUMED TO BE INSTALLED | | IN THESE LOCATIONS. | | | | IF THE 38" HIGH BEDROOM WINDOWS ARE TO HAVE SINGLE HUNG | | WINDOWS INSTALLED, SUBMIT A REVISION WITH CALCULATIONS | | TO SHOW THAT THE CLEAR OPENING IS NOT REDUCED BY MORE | | THAN 5%. | | | | |
|
|