2014-07-15 13:55:54 | PLUMBING PLAN REVIEW |
| PERMIT: 14070211 |
| ADD: 8100 IBIS BLVD |
| CONT: HUGHES CONSTRUCTION INDUSTRIES |
| TEL: (561)792-8004 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE:JULY 15/ 2014 |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED ARE SITE PLAN SHOWING THE LOCATION |
| OF THE PROPOSED (2) GREASE INTERCEPTORS AND SPECS ON A |
| SCHIER GREAT BASIN 250 GREASE INTERCEPTOR. THERE WAS NO |
| INFORMATION HOW THESE GREASE INTERCEPTORS WERE SIZED. |
| 2010 FBC-P 1003.2 APPROVAL. THE SIZE, TYPE AND LOCATION |
| OF EACH INTERCEPTOR AND OF EACH SEPARATOR SHALL BE |
| APPROVED BY THE PLUMBING OFFICIAL. THE INTERCEPTOR OR |
| SEPARATOR SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| WITH THE MANUFACTURER?S INSTRUCTIONS AND THE |
| REQUIREMENTS OF THIS SECTION. WASTES THAT DO NOT |
| REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED |
| INTO ANY INTERCEPTOR OR SEPARATOR. |
| |
| 2) SHOW COMPLIANCE WITH 003.3.1 GREASE INTERCEPTORS AND |
| AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. |
| A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL |
| KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY |
| CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL |
| INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR |
| SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS |
| INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT |
| ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. |
| |
| 3) SHOW HOW THE GREASE INTERCEPTOR WAS SIZED AND IN |
| COMPLIANCE WITH: |
| 2010 FBC-P 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| GREASE REMOVAL DEVICES. |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| |
| ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| FAHRENHEIT (65.56 DEGREES CELSIUS). |
| |
| IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| REQUIRED MAINTENANCE & CLEANOUT SCHEDULE WILL BE |
| INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| MUNICIPAL CODE OF ORDINANCES. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| 7/18/2014 JULIAN BLAZER CALLED (THE WEITZ CO |
| REPRESENTATIVE) IN REFERANCE TO THIS PERMIT. IN |
| REVIEWING THE APPROVED PLANS SHEET PL003 THE GREASE |
| TRAP IS SIZED USING THE 2010 FBC-P TABLE 1003.5.1 WHICH |
| IS FOR CONCRETE VAULT TYPE INTERCEPTORS. THE SUBMITTED |
| PRODUCT IS SCHIER (2) GB-250 TYPE HYDROMECHANICAL |
| GREASE INTERCEPRTORS, NOT THE TYPE OF INTERCEPTOR THE |
| DESIGNER OF RECORD REQUIRES ,NOR HAS APPROVED WITH |
| THEIR SHOP DRAWING STAMP OF APPROVAL. |
| |
| PLEASE NOTE A REVISION WILL BE NEEDED TO THE PLAN SINCE |
| THE FORMULA AND SIZING ON PL003 IS FOR A CONCRETE VAULT |
| TYPE INTERCEPTOR. 2ND THE SCHIER GREASE INTERCEPTOR |
| WILL NEED TO BE SIZED USING THIER OWN FORMULA FOR |
| GREASE REMOVAL & RETENTION, REVIEWED BY THE DESIGNER OF |
| RECORD, AND SHOP DRAWING STAMP OF APPROVAL ON THE |
| DOCUMENTS. |
| |