2014-07-22 08:05:48 | DATE: 7/22/2014 |
| PROJECT: ROSEN RESIDENCE |
| PERMIT#: 14070043 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND |
| DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA |
| DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHEN APPROVED |
| BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| FBC-B 107.2.1 THE 8X11 RE-SUBMITTAL SHEET IS FAR TOO |
| SMALL TO BE LEGIBLE. PLEASE PROVIDE A FULL SIZE SHEETS |
| FOR REVIEW. |
| |
| 2) PROVIDE PRODUCT APPROVALS AND INSTALLATION DETAILS |
| FOR MOTORIZED SHADES, RIBBON LIGHTING, PENDENT |
| FIXTUURES AND RECESSED LIGHTING. LISTING AND LABELING |
| REQUIRED BY AN APPROVED TESTING LAB. IN JUDGING |
| EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING SHALL BE |
| EVALUATED: SUITABILITY FOR INSTALLATION AND USE IN |
| CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC |
| 110.3(A)(1 THRU 8). NOT ALL PRODUCT APPROVAL CUT SHEETS |
| SUBMITTED ARE "LISTED" BY AN APPROVED TESTING LAB. WHEN |
| RE-SUBMITTING PLEASE NOTE ON EACH PRODUCT APPROVAL |
| SHEET THE FIXTURE TYPE AND THE ROOM OR LOCATION ON THE |
| PLAN WHERE IT IS PROPOSED TO BE INSTALLED. THIS IS MOST |
| OFTEN ACCOMPLISHED BY THE USE OF A FIXTURE SCHEDULE AND |
| THEN GIVING EACH FIXTURE TYPE A LETTER OR NUMBER |
| DESIGNATION AND THEN MARKING THE PLAN WITH THE |
| CORESPONDING FIXTURE TYPE NEXT TO EACH FIXTURE. |
| |
| 3) NOT ALL PRODUCT APPROVALS HAVE BEEN SUBMITTED. I |
| STILL REQUIRE PRODUCT APPROVAL SHEETS FOR THE MOTORIZED |
| BLINDS FOR COMPLIANCE WITH APPLICABLE CODES AS STATED |
| ABOVE. NEC 110.3(A)(1 THRU 8). PROVIDE AND INDICATE ON |
| THE PLANS, ACCESS FOR MOTORS, CONTROLLERS AND OUTLETS |
| FOR THESE MOTORIZED BLINDS SHALL BE MAINTAINED AFTER |
| INSTALLATION. NEC 110.26 |
| |
| 4) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314.3.1 REVISE PLANS TO INDICATE COMPLIANCE. |
| |
| 5) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE PROVISIONS OF NEC 410.16(A) AND |
| (B). REVISE PLANS TO INDICATE COMPLIANCE. |
| |
| 6) THERE IS A NOTE ON THE PLAN INDICATING THE USE OF A |
| REMOTE TRANSFORMER. PLEASE SUBMIT CUT SHEET PRODUCT |
| APPROVAL FOR TRANSFORMER AND INDICATE ON THE PLANS THE |
| LOCATION OF THE TRANSFORMERS TO BE ACCESSIBLE AFTER |
| INSTALLATION. NEC110.26 |
| |
| 7) THERE IS A NOTE ON THE PLAN REGARDING AN ATTACHED AS |
| BUILT RECORD COPY FOR THE EXISTING PANEL SCHEDULE AND |
| LOAD CALCULATIONS. THIS INFORMATION IS REQUIRED AND IS |
| NOT A PART OF THE ORIGINAL SUBMITTAL. PLEASE PROVIDE A |
| PANEL SCHEDULE AND A LOAD CALCULATION INDICATING THE |
| SIZE OF THE ELECTRICAL SERVICE MAIN, AND PANEL |
| INCLUDING THE CAPACITY FOR THE ADDITIONAL CIRCUITRY AND |
| LOAD PROPOSED. FBC 107.2.1 |
| |
| 8) THERE IS A NOTE ON THE PLAN INDICATING WALL MOUNT TV |
| OUTLETS. WHEN RE-SUBMITTING PLEASE INCLUDE THE |
| INSTALLATION OF THE AUDIO/VIDEO INSTALLATION FROM THE |
| HEAD END ON OUT TO EACH OF THE TV LOCATIONS IN |
| COMPLIANCE WITH THE PROVISIONS OF THE NEC ARTICLE 820. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |