2014-07-03 13:28:40 | DATE: 7/3/2014 |
| PROJECT: RONICA HARWAY |
| PERMIT#: 14070037 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) INDICATE THE LOCATION OF THE MAIN SERVICE ON THE |
| FLOOR/SITE PLAN. INDICATE THE CIRCUITING ON THE FLOOR |
| PLAN IN RELATION TO THE PANEL SCHEDULE. FBC 107.2.1 |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. FBC 107.2.1 |
| |
| 2) INDICATE ON THE PLANS ALL REQUIRED OUTLETS PER |
| 210.52. |
| GUEST ROOMS OR GUEST SUITES IN HOTELS, MOTELS, SLEEPING |
| ROOMS IN DORMITORIES AND SIMILAR OCCUPANCIES SHALL HAVE |
| RECEPTACLES INSTALLED IN ACCORDANCE WITH 210.52(A) AND |
| 210.52(D). GUEST ROOMS OR GUEST SUITES PROVIDED WITH |
| PERMANENT PROVISIONS FOR COOKING SHALL HAVE RECEPTACLE |
| OUTLETS INSTALLED IN ACCORDANCE WITH ALL OF THE |
| APPLICABLE RULES IN 210.52. NEC 210.60(A) GENERAL |
| |
| 3) INDICATE ON THE PLAN THE NEW CEILING FANS WILL BE |
| SUPPORTED ACCORDINGLY. NEC 314.27(B) |
| OUTLET BOXES OR FITTINGS DESIGNED FOR THE SUPPORT OF |
| LUMINAIRES AND INSTALLED AS REQUIRED BY 314.233 SHALL |
| BE PERMITTED TO SUPPORT A LUMINAIRE WEIGHING 50LBS OR |
| LESS. A LUMINAIRE THAT WEIGHS MORE THAN 50LBS SHALL BE |
| SUPPORTED INDEPENDENTLY OF THE OUTLET BOX UNLESS THE |
| OUTLET BOX IS LISTED AND MARKED FOR THE MAXIMUM WEIGHT |
| TO BE SUPPORTED. NEC 314.27(B). |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |