Plan Review Details - Permit 14070012
Plan Review Stops For Permit 14070012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-07 Cont ID  
Sent By jgomez Date 2014-08-07 Time 16:01 Rev Time 0.00
Received By jgomez Date 2014-08-07 Time 16:01 Sent To  
Notes
2014-08-07 16:22:17BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVER. GENERAL NOTES ON COVER SHEET INDICATES
 NEW ROOF AS PART OF THE SCOPE OF WORK.
 B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS, DETAILS AND SPECIFICATIONS.
 C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 D) ROUND CASEMENT WINDOW AS SHOWN ON PLANS.
 E) NEW ALUMINUM CASEMENT NOA 12-0216.04 WAS SUBMITTED.
 NEED TO PROVIDE TWO COPIES.
 F) NEW FRENCH DOORS FLORIDA PRODUCT APPROVAL FL14504
 WAS SUBMITTED. NEED TO PROVIDE TWO COPIES.
 2- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS.
 3- SHEET A-2: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR INTERIOR HANDRAIL TO BE REPLACED.
 TABLE R301.5 AND SEC. R311.7.7.
 4- SHEET A-4: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY. TABLE
 R301.5 AND SEC. R312.
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON
 FIRST FLOOR. SEC. R301.
 6- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK
 DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR
 FRAME. SEC. R612.10.2.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By jgomez Date 2014-07-24 Time 08:38 Rev Time 0.00
Received By jgomez Date 2014-07-24 Time 08:38 Sent To  
Notes
2014-07-24 09:15:22RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ARCHITECT TO REVISE DESIGN CRITERIA ON SHEET A-10:
 A) CLARIFY WHY THE WIND NET UPLIFT IS ONLY FOR ZONES 1
 AND 2?. NEED WIND LOADS FOR ALL ZONES. SEC. R301 OF
 2010 FBC-RESIDENTIAL.
 B) REVISE THE BASIC WIND VELOCITY. SPECIFY THE ULTIMATE
 WIND LOAD AND THE NOMINAL WIND LOAD AS REQUIRED BY SEC.
 R301.2.1.3 OF 2010 FBC-RESIDENTIAL. (NOTE: ULTIMATE
 WIND SPEED FOR CITY OF WEST PALM BEACH IS 170MPH).
 C) REVISE OCCUPANCY. THIS IS NOT 1. THIS IS A SINGLE
 FAMILY RESIDENCE (R3).
  
 2- ARCHITECT TO REVISE ALL THE WINDOWS AND DOORS DESIGN
 PRESSURES SHOWN ON THE EXTERIOR ELEVATIONS. THEY DO NOT
 CORRESPOND TO EXPOSURE "C" ACCORDING TO HEIGHT AND
 OPENING LOCATION (INTERIOR OR END LOCATION). OR PROVIDE
 COMPLETE CALCULATIONS SHOWING HOW THE DESIGN PRESSURES
 SHOWN WERE CALCULATED. SEC. R301.2.1 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVER. NONE SUBMITTED. GENERAL NOTES ON COVER
 SHEET INDICATES NEW ROOF AS PART OF THE SCOPE OF WORK.
 ***NOTE: A ROOFING SUB-PERMIT IS REQUIRED ALSO.
 B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS, DETAILS AND SPECIFICATIONS.
 C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 DOWNLOAD CURRENT NOA AND RE-SUBMIT. PROVIDE 2 COPIES
 ONLY ONE SUBMITTED.
 D) FRENCH DOORS NOA 11-1013.24. ONLY ONE COPY
 SUBMITTED. PROVIDE ANOTHER COPY.
 E) CASEMENT WINDOWS NOA 11-1006.05. ONLY ONE COPY
 SUBMITTED. PROVIDE ANOTHER COPY.
 F) FIXED WINDOWS NOA 11-1021.17. ONLY ONE COPY
 SUBMITTED. PROVIDE ANOTHER COPY.
 G) ROUND CASEMENT WINDOW AS SHOWN ON ELEVATIOINS.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO REVISE WINDOW AND DOOR SCHEDULES TO
 MATCH PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE FRENCH
 DOORS PRODUCT APPROVAL SUBMITTED IS FOR ALUMINUM DOORS
 NOT WOOD. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 6- SHEET A-2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR HANDRAIL TO BE REPLACED TO VERIFY COMPLIANCE
 WITH TABLE R301.5 AND SEC. R311.7.7 OF 2010
 FBC-RESIDENTIAL.
 B) POWDER ROOM #105. EXISTING WINDOW IS GOING TO BE
 BLOCKED. PROVIDE SPECIFICATIONS FOR VENTILATION. SEC.
 R303.3 OF 2010 FBC-RESIDENTIAL.
  
 7- A) WINDOW SCHEDULE ON SHEET A-5 IS MISSING WINDOW
 "N". PROVIDE INFORMATION FOR WINDOW "N" TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 604.1
 OF 2010 FBC-EXISTING BUILDING.
 B) CLARIFY WINDOW "B". IS IT A CASEMENT OR FIXED
 WINDOW?. IS IT ROUND OR SQUARE TOP?. EXTERIOR ELEVATION
 SHOWS ROUND TOP. CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 8- SHEET A-4: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY TO
 VERIFY COMPLIANCE WITH TABLE R301.5 AND SEC. R312 OF
 2010 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON
 FIRST FLOOR. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 10- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK
 DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR
 FRAME AS REQUIRED BY SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-11 Cont ID  
Sent By dhayes Date 2014-08-11 Time 16:09 Rev Time 0.00
Received By dhayes Date 2014-08-11 Time 16:09 Sent To  
Notes
2014-08-11 17:09:29DATE: 8/6/2014
 PROJECT: HARCOURT RESIDENCE
 PERMIT#: 14070012
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) MAINTAIN REQUIRED CLEARANCES PER THE NEC 110.26
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3 AND 314.3.1
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
 4)NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-25 Cont ID  
Sent By dhayes Date 2014-07-25 Time 08:50 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 08:46 Sent To  
Notes
2014-07-25 09:15:02DATE: 7/25/2014
 PROJECT: 224 LAKEWOOD RD.
 PERMIT#: 14070012
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THERE IS AN ELECTRICAL PERMIT APPLICATION INCLUDED
 WITH THIS SUBMITTAL PACKAGE HOWEVER THERE ARE NO
 ELECTRICAL PLANS OR SPECIFICATIONS INCLUDED AS REQUIRED
 FOR REVIEW. PROVIDE COMPLETE PLANS AND SPECIFICATIONS
 TO INCLUDE THE FOLLOWING: FBC WPB AMENDMENTS, SECTION
 107.2.1
 1. A DETAILED SCOPE OF ELECTRICAL WORK TO BE PERFORMED.
 2. A FLOOR PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL PANEL AND ALL THE ITEMS AS IDENTIFIED ON THE
 SCOPE OF WORK.
 3. A ONE LINE RISER DIAGRAM OF THE ELECTRICAL SERVICE
 IF ONE IS TO BE INCLUDED.
 4. A COMPLETE LOAD SUMMARY CALCULATION INDICATING THE
 EXISTING AND NEW LOADS.
 5. A PANEL SCHEDULE WITH A COMPLETE DIRECTORY OF
 CIRCUITRY AS IDENTIFIED ON THE FLOOR PLAN. A
 6. A FIXTURE SCHEDULE INDICATING THE LIGHTING FIXTURES
 PROPOSED INDICATING LOCATIONS LAMP TYPE, LOAD AND
 VOLTAGE.
 7. A SITE PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL SERVICE.
 8. CUT SHEETS OF ANY SPECIALZED EQUIPMENT PROPOSED SUCH
 AS STEAM GENERATORS, TRANSFER SWITCHES GENERATORS, HOME
 AUTOMATION EQUIPMENT, STRUCTURED CABLING CABINETS
 ETC...
 9. REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NOTE: ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 THESE ARE JUST TO NAME A FEW. PLEASE FAMILILIARIZE
 YOURSELF WITH THE 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FBC AND THE WPB AMEMNDMENTS TO CHAPTER
 ONE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-11 Cont ID  
Sent By rmcdouga Date 2014-08-11 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2014-08-05 Time 13:04 Sent To  
Notes
2014-08-06 13:06:24RE-SUBMITTAL SENT TO R2 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-05 Cont ID  
Sent By skennedy Date 2014-08-05 Time 09:43 Rev Time 0.00
Received By skennedy Date 2014-07-01 Time 18:27 Sent To  
Notes
2014-07-01 18:30:42R16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-11 Cont ID  
Sent By rmcdouga Date 2014-08-11 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2014-08-11 Time 17:08 Sent To  
Notes
2014-08-11 17:08:53APPROVED WITH EXCEPTIONS.
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3.
 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND
 COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION
 402.1.2.4.
 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER
 GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4
 FOR BALANCED RETURN AIR.
 TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL
 AREA TO 100 CFMS OF SUPPLY AIR.
 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL
 FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND
 LOADS. FBCR M1307.2.1
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By jgomez Date 2014-07-24 Time 09:54 Rev Time 0.00
Received By jgomez Date 2014-07-24 Time 09:54 Sent To  
Notes
2014-07-24 09:58:05RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- THERE IS A MECHANICAL PERMIT APPLICATION SUBMITTED,
 BUT THERE IS NO INFORMATION SUBMITTED FOR THE
 MECHANICAL WORK TO BE PERFORMED. PROVIDE COMPLETE
 INFORMATION FOR MECHANICAL REVIEW. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-11 Cont ID  
Sent By rmcdouga Date 2014-08-11 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2014-08-11 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By jgomez Date 2014-07-24 Time 10:44 Rev Time 0.00
Received By jgomez Date 2014-07-24 Time 10:44 Sent To  
Notes
2014-07-24 10:49:18RESIDENTIAL (R3) ALTERATION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- THERE IS A PLUMBING PERMIT APPLICATION SUBMITTED,
 BUT THERE IS NO INFORMATION SUBMITTED FOR PLUMBING
 REVIEW. PROVIDE COMPLETE PLUMBING RISER DIAGRAM. NONE
 SUBMITTED AT THIS TIME. SEC. 107..3.5.3(11) OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-13 Cont ID  
Sent By shill Date 2021-02-13 Time 13:32 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2014-08-12 Cont ID  
Sent By rmcdouga Date 2014-08-12 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2014-08-12 Time 09:33 Sent To  
Notes
2014-08-12 09:38:09A SEPARATE PERMIT, APPLICATION AND REVIEW REQUIRED FOR
 ROOFING.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By jgomez Date 2014-08-07 Time 17:58 Rev Time 0.00
Received By jgomez Date 2014-08-07 Time 17:57 Sent To  
Notes
2014-08-07 17:58:561- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
  
 A) ROOF COVER. NONE SUBMITTED. GENERAL NOTES ON COVER
 SHEET INDICATES NEW ROOF AS PART OF THE SCOPE OF WORK.
 ***NOTE: A ROOFING SUB-PERMIT IS REQUIRED ALSO.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-07 Cont ID  
Sent By sgraham Date 2014-08-07 Time 15:10 Rev Time 0.00
Received By sgraham Date 2014-08-07 Time 15:10 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-28 Cont ID  
Sent By sgraham Date 2014-07-28 Time 11:15 Rev Time 0.00
Received By sgraham Date 2014-07-28 Time 11:15 Sent To  
Notes
2014-07-28 11:16:407/28/14 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY