Plan Review Details - Permit 14061326
Plan Review Stops For Permit 14061326
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 14:41 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 14:41 Sent To  
Notes
2015-08-14 14:54:11BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE "METAL HANDRAIL DETAIL ON SHEET A-2 TO MATCH
 FLOOR PLAN AND FRONT ELEVATION. IS THERE A HANDRAIL AND
 GUARDRAIL?. REVISE SIZE OF METAL FRAMING MEMBERS 1-1/2
 AND 2"?. SPECIFY CONNECTIONS TO CONCRETE STEP AND TO
 COLUMN.
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 CONSTRUCTION OF STEPS AND SPECIFY RISER AND TREAD TO
 SHOW COMPLIANCE WITH SEC. R311.7.4.
 3- REVISE WALL SECTION A/A-2: SCREEN VENTS AT 24" O.C.
 DON'T PROVIDE CROSS VENTILATION.
 4- SHEET A2:
 A) REVISE PORCH SECTION: (1) SPECIFICATIONS CALL FOR
 (3)2X10 WD BEAM. ONLY 2 ARE SHOWN.
 (2) ROOF RAFTERS ARE 2X6. ROOF FRAMING CALLS FOR 2X8.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-07-06 Cont ID  
Sent By jgomez Date 2015-07-06 Time 15:20 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 15:20 Sent To  
Notes
2015-07-06 15:21:53RESIDENTIAL (R3) ALTERATION/ ADDITION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES:
  
 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT
 THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED. PROVIDE
 BREAKDOWN FOR THE SCOPE OF WORK ON MAIN HOUSE AND SCOPE
 OF WORK ON REAR STRUCTURE).
  
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH
 LADDER. (REPEAT COMMENT. NOT ADDRESSED. ROOF FRAMING
 DETAILS NOT PROVIDED. )
  
 3- PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT).
  
 4- PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES
 NEW PORCH. PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE LOADS
 OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. SPECIFY ALL
 FRAMING MEMBERS AND FASTENERS. (REPEAT COMMENT. THE
 FRONT ELEVATION IS NOW MISSING THE GUARDRAILS. THERE IS
 NOTHING TO COMPARE TO PROPOSED GUARDRAIL. HANDRAIL
 DETAIL SUBMITTED SEEMS TO BE FOR INTERIOR HANDRAIL. AND
 CLARIFY HOW ARE THE #12X3" WD. SCREWS TOP & BTM. @16"
 O/C INSTALLED AS SHOWN ON THE HANDRAIL DETAIL?. FLOOR
 PLAN ON SHEET A-1 CALLS FOR ALUMINUM RAILING. THIS
 DETAIL IS FOR WOOD RAILING. SEC. 107.2.1 CITY
 AMENDMENTS).
  
 5- WALL SECTION A/A-2: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW PROVIDING "CROSS
 VENTILATION" SEC. R806 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT. SPECIFY SPACING OF THE 4"X7" SPECIFIED VENTS
 TO VERIFY CROSS VENTILATION.).
  
 6- REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND
 REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
 (REPEAT COMMENT. NOT ADDRESSED. 2X4 BUCK DOESN'T
 PROVIDE FULL SUPPORT TO THE DOOR FRAME).
  
 7- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL
 ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED
 GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS.
  
 8- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF
 SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL
 FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF
 THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO
 IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL
 SUBMITTED).
  
 B) SINGLE HUNG WINDOW. INFORMATION SUBMITTED DOESN'T
 HAVE A FLORIDA PRODUCT APPROVAL NUMBER. PROVIDE THE
 CORRESPONDING FLORIDA PRODUCT APPROVAL FOR THE
 SUBMITTED PACKAGE OR MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL (COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR BUILDING OFFICIAL APPROVAL).
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS AND USP STRUCTURAL
 CONNECTORS SPECIFIED ON FRAMING PLANS AND ALL DETAILS.
 OR SPECIFY THE FLORIDA PRODUCT APPROVAL NEXT TO THE
 SPECIFIED CONNECTOR. (REPEAT COMMENT).
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- SHEET A-1:
 A) LETTERING ON THE SITE PLAN IS NOT LEGIBLE. SEC
 107.2.1.4 CITY AMENDMENTS.
  
 B) MAIN SCOPE ON MAIN NOTES SPECIFY "FIRE DAMAGE
 REPAIRS". PLANS DON'T SHOW ANY INFORMATION REGARDING
 THIS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING AREAS DAMAGED BY FIRE AND PROPOSED REPAIRS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF NEW PORCH STEPS SHOWING COMPLIANCE WITH
 SEC. R311.7.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LETTERING ON SIMPSON STRAPS AND POST/CAPS SCHEDULES
 IS NOT LEGIBLE. IT'S TOO SMALL. SEC.107.2.1.4 CITY
 AMENDMENTS.
  
 C) CLEARLY COORDINATE INFORMATION SHOWN ON THE SIMPSON
 STRAPS AND POST/CAPS SCHEDULES, ROOF FRAMING PLAN,
 PORCH SECTION AND DETAILS B/A2, C/A2 AND D/A2. THIS IS
 LIKE CUTTING AND PASTING INFORMATION BUT IT DOESN'T
 MATCH ACTUAL CONDITIONS. CHECK SIZES OF FRAMING
 MEMBERS, ACTUAL CONNECTIONS, CONNECTORS SIZES VS
 STRUCTURAL MEMBERS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) PORCH SECTION: (1) CLARIFY FINISH GRADE LEVEL. 16"
 OR 24'. SEE FRONT ELEVATION. CLARIFY NEW CONCRETE PORCH
 SLAB CONSTRUCTION. PORCH SECTION SHOWS CRAWL SPACE
 BELOW THE SLAB. NEED TO PROVIDE COMPLETE INFORMATION
 FOR UNDER FLOOR SPACE AS REQUIRED BY SEC. R408 OF 2010
 FBC-RESIDENTIAL. AND, NEED TO SHOW HOW IS THE SLAB
 ANCHORED TO THE EXITING WALL. SEC. 107.2.1 CITY
 AMENDMENTS. (2) SPECIFICATIONS CALL FOR (3)2X10 WD
 BEAM. ONLY 2 ARE SHOWN. (3) ROOF RAFTERS ARE 2X6. ROOF
 FRAMING CALLS FOR 2X8. (4)
  
 13- SHEET A-5:
 A) NEW FLOOR PLAN CALLS WINDOW ON THE LEFT HAND SIDE AS
 "EXISTING WINDOW". PLANS ARE MISLEADING BECAUSE
 ACCORDING TO THE DEMOLITION PLAN THIS WINDOW IS NOT
 PLACED IN THE SAME LOCATION. CLEARLY SPECIFY IF THE
 WINDOW WAS REMOVED. IF IT WAS REMOVED, THEN THE SAME
 WINDOW CAN'T BE USED UNLESS PRODUCT APPROVAL FOR THE
 SAME WINDOW IS PROVIDED. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- SHEET A4: THERE IS A NEW BILLIARD ROOM SHOWN ON THE
 FLOOR PLAN. THE ROOM SEEMS TO BE TOO SMALL FOR A
 BILLIARD ROOM. PROVIDE COMPLETE LAYOUT OF POOL TABLE
 SHOWING CLEARANCES TO PLAY POOL. NOTE: ORIGINALLY, THIS
 ROOM WAS DESIGNED AS A BEDROOM. PROVIDE CLARIFICATION
 WHY CHANGING THE BEDROOM FOR A BILLIARD ROOM THAT MAY
 NOT BE SUITABLE BECAUSE THERE IS NOT ENOUGH ROOM. THE
 PROPOSED USE OF THIS ROOM MAY NOT BE SUITABLE BASED ON
 THE SIZE OF ROOM. SEC. 102.2CITY AMENDMENTS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 17:26 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 17:26 Sent To  
Notes
2015-04-13 17:26:48RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED:
  
 1- SITE PLAN SHOWN ON SHEET A-1 DOESN'T MATCH SITE PLAN
 SHOWN ON SHEET A-5. AND IS MISSING THE CONNECTION
 (LAUNDRY ROOM) OF THE GARAGE WITH THE REAR BUILDING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- SCOPE OF WORK SPECIFIED ON SHEET A-1 DOESN'T MATCH
 SCOPE OF WORK SPECIFIED ON SHEET A-5. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- DESIGN DATA FOR WIND LOADS SHOWN ON SHEET A-1
 DOESN'T MATCH DESIGN DATA SPECIFIED ON SHEET A-5. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- INFORMATION SHOWN ON THE DESIGN DATA ON SHEET A-1
 AND SHEET A-5 IS CONFUSING. INFORMATION FOR INTERIOR
 AND END ZONE IS REPEATED TWICE BUT THE DESIGN PRESSURES
 ARE DIFFERENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT
 THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY
 AMENDMENTS.
  
 6- SHEET A-1:
 A) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH
 LADDER.
  
 B) ENGINEER OF RECORD TO SPECIFY THE ALTERATION LEVEL
 TYPE OR COMBINATION OF LEVELS OF ALTERATION AS REQUIRED
 BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 C) CLEARLY SPECIFY WHICH WINDOWS AND EXTERIOR DOORS ARE
 EXISTING AND WHICH ARE GOING TO BE REPLACED. IF
 REPLACING EXISTING BEDROOM WINDOWS, THEN SPECIFY
 EXISTING TYPE AND SIZE AND PROPOSED TYPE AND SIZE TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604 OF 2010 FBC-EXISTING BUILDING.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 8- COORDINATE LABELING NUMBERS OF BUILDINGS SHOWN ON
 THE SITE PLAN WITH LABELING OF BUILDINGS SHOWN ON
 SHEETS A-2 TO A-5. REVISE AS REQUIRED. CLEARLY MATCH
 BUILDING #1, BUILDING #2 AND BUILDING #3 WITH NUMBERS
 SHOWN ON THE SITE PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A-2:
 A) PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES
 NEW PORCH ON SHEET A-5. PROVIDE COMPLETE FRAMING
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 LIVE LOADS OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS AND FASTENERS.
  
 C) INFORMATION SHOWN ON THE WOOD FRAMING DETAIL
 SECTION, WALL SECTION AND DOOR FRAMING SECTION DOESN'T
 MATCH. REVISE AS REQUIRED TO MATCH AND CLARIFY WHERE
 ARE THESE SECTIONS TAKEN AT. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-3:
 A) WALL SECTION A/A-1: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW PROVIDING "CROSS VENTILATION
 IN BLOCKING" AS SPECIFIED ON THE WALL SECTION. SEC.
 R806 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND
 REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SIZE OF WINDOW SHOWN ON THE LEFT ELEVATION DOESN'T
 MATCH SIZE SPECIFIED ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) REVISE WINDOWS AND DOORS DESIGN PRESSURES TO MATCH
 CORRECT DESIGN PRESSURES AS SPECIFIED ON SHEET A-1 AND
 A-5. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) RIGHT ELEVATION DOESN'T MATCH FLOOR PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 11- SHEET A-4:
 A) CLEARLY SPECIFY EXISTING AND PROPOSED WINDOWS AND
 EXTERIOR DOORS. (COORDINATE WITH EXTERIOR ELEVATIONS ON
 SHEET A-3). SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NEW FLOOR PLAN SHOWS "NEW BILLIARD ROOM" AND "NEW
 PLAYROOM". PREVIOUS PLANS SHOWED THESE ROOMS AS
 BEDROOMS. IT'S NOT CLEAR WHY THE ROOMS WERE REDESIGNED
 AS PLAYROOMS, BUT IF THE ROOMS ARE NOT DESIGNED AS
 BEDROOMS, THEN ENGINEER OF RECORD TO SPECIFY ON PLANS
 THAT THESE ROOMS CAN NOT BE USED FOR SLEEPING PURPOSES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A-5:
 A) THIS IS NOT ALTERATION LEVEL 2. REVISE AS REQUIRED.
 SEE SEC.401.4 OF 2010 FBC-EXISTING BUILDING.
  
 B) ROOF FRAMING PLAN IS MISSING INFORMATION: (1)
 PROVIDE WALL SECTION SHOWING WHERE IS THE NEW 2X8 WOOD
 LEDGER GOING TO BE ATTACHED TO THE EXISTING BUILDING.
 (2) SPECIFY LEDGER ANCHOR BOLT SIZE AND SPACING. (3)
 SPECIFY CEILING CLEARANCES. (4) SPECIFY BEAM SIZE. (5)
 SPECIFY ROOF PITCH. (6) SPECIFY ROOF SHEATHING SIZE AND
 FASTENER TYPE AND SPACING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) ROOF SHINGLES. NOA 11-0913.10 SUBMITTED WAS THE
 APPROVAL FOR ANOTHER PROJECT AND WAS REVIEWED AND
 APPROVED BY ANOTHER ENGINEER NOT THE ONE RESPONSIBLE
 FOR THIS PROJECT. AND NEED 2 COPIES. ONLY 1 WAS
 SUBMITTED.
  
 C) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR SIZE
 OF GARAGE DOOR SPECIFIED ON PLANS. ALSO, NOA 12-0125.20
 SUBMITTED IS FOR ANOTHER PERMIT AND WAS APPROVED BY
 ANOTHER ENGINEER NOT THE ONE RESPONSIBLE FO THIS
 PROJECT.
  
 D) SINGLE HUNG WINDOW. NOA 11-1013.14 SUBMITTED IS NOT
 LEGIBLE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND ALL DETAILS. OR SPECIFY THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
 FLORIDA PRODUCT APPROVAL WAS SUBMITTED FOR SOME
 CONNECTORS, BUT NOT ALL OF THEM.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ENGINEER TO CLARIFY WHY THE SIGNATURE ON THE
 APPROVED PRODUCT APPROVALS IS DIFFERENT THAT THE
 SIGNATURE ON THE PLANS. PROVIDE SIGNED AND SEALED
 LETTER WITH EXPLANATION. CHAPTER 471 F.S.
  
 15- ENGINEER IS USING OLD SEAL. NEED TO USE CURRENT
 SEAL WITH THE WORDING "LICENSE" NOT "CERTIFICATE". SEC.
 61G15-23.001. F.A.C.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-07 Cont ID  
Sent By jgomez Date 2014-11-07 Time 07:29 Rev Time 0.00
Received By jgomez Date 2014-11-07 Time 07:29 Sent To  
Notes
2014-11-07 07:30:20RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE: THESE COMMENTS APPLY TO FRONT BUILDING ONLY.
 REAR BUILDING COMMENTS ARE UNDER PERMIT #14061324.
  
 1- SCOPE OF WORK IS NOT CLEAR. SCOPE OF WORK SPECIFIED
 ON SHEET A-1 DOESN'T REFLECT WHAT THE FLOOR PLANS SHOW
 AND WHAT THE PERMIT APPLICATION SPECIFIES. REVISE ALL L
 THE INFORMATION AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- REVISE VALUATION ON THE PERMIT APPLICATION TO MATCH
 ALL THE SCOPE OF WORK SPECIFIED IN THE REVISED
 INFORMATION REQUESTED ON ITEM #1 ABOVE. SEC. 109.3 CITY
 AMENDMENTS TO FBC.
  
 3- ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE NEW
 STAIRS AT THE BOTTOM RIGHT SIDE SHOWN ON THE ELECTRICAL
 PLAN. PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR NEW DOOR, INCLUDING SIZE. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE NEW STAIRS
 SHOWING COMPLIANCE WITH SEC. R311.3 OF 2010 FBC-
 RESIDENTIAL. INCLUDE THE REQUIRED LANDING AND RISER AND
 TREADS DIMENSIONS.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ANY NEW DOORS OR EXTERIOR DOORS TO BE REPLACED.
 B) ANY NEW WINDOWS OR WINDOWS TO BE REPLACED.
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE FRAMING
 DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
 D) WINDOW MULLIONS, IF USED.
 E) ROOF SHINGLES IF THIS SCOPE OF WORK IS GOING TO BE
 INCLUDED.
  
 ***NOTE: THERE WERE SOME PRODUCT APPROVALS THAT WERE
 INLCUDED IN THIS PACKAGE. THEY HAD A DIFFERENT PERMIT
 NUMBER STAMPED ON THE FRONT COVER. THEY WERE ROUTED TO
 R12 SHELF TO RIDE ALONG WITH THAT PERMIT APPLICATION.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 6- IF REPLACING BEDROOM WINDOWS, THEN SPECIFY EXISTING
 WINDOW TYPE AND SIZE AND PROPOSED WINDOW TYPE AND SIZE
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENT OF
 SEC. 604 OF 2010 FBC-EXISTING BUILDING.
  
 7- IF REPLACING DOOR AND WINDOWS, THEN CLEARLY IDENTIFY
 ON PLANS WHICH DOORS AND WINDOWS ARE GOING TO BE
 REPLACED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:55 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 17:55 Sent To  
Notes
2014-10-15 17:55:39RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
  
  
 1- NO PLANS WERE SUBMITTED SHOWING SCOPE OF WORK.
 PROVIDE COMPLETE INFORMATION FOR REVIEW. SEC. 107.2.1
 CITY AMENDMENTS TO FBC. ***NOTE: COORDINATE WITH ITEM
 #2 BELOW.
  
 2- IT LOOKS LIKE THIS PERMIT WAS APPLIED FOR TO REVOKE
 EXPIRED PERMIT APPLICATION #10110532. PERMIT
 APPLICATION #10110532 WAS NEVER APPROVED BECAUSE
 COMMENTS WERE NEVER ADDRESSED. PLEASE REVISE SCOPE OF
 WORK TO MATCH SCOPE OF WORK SUBMITTED ON PERMIT
 APPLICATION #10110532. THE FOLLOWING IS THE SCOPE OF
 WORK FOR PERMIT APPLICATION #10110532: "MAIN HOUSE -
 RENOVATION / REPAIRS. ELECTRIC, SHEETROCK, STUCCO,
 CLOSE 2 WINDOWS & 1 DOOR WITH LATHE/STUCCO. INSTALL NEW
 DOOR ON NORTH SIDE & REAR DOOR. ROOF SHINGLES, HVAC AIR
 HANDLER & COMPRESSOR". SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 3- REVISE VALUATION TO REFLECT ALL THE SCOPE OF WORK.
 VALUATION TO INCLUDE ALL LABOR AND MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR: ALL WINDOW TYPES TO BE REPLACED,
 WINDOW MULLIONS TO BE REPLACED, ALL EXTERIOR DOORS,
 ROOF SHINGLES,
  
 5- PROVIDE SOME SORT OF KEY PLAN IDENTIFYING ALL
 WINDOWS AND DOORS TO BE REPLACED. CLEARLY SPECIFY TYPE
 AND SIZE OF ALL EXISTING BEDROOM WINDOWS TO BE REPLACED
 AND PROPOSED WINDOW TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF
 2010 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 09:49 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 09:49 Sent To  
Notes
2014-07-29 09:59:16RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- NO PLANS WERE SUBMITTED SHOWING SCOPE OF WORK.
 PROVIDE COMPLETE INFORMATION FOR REVIEW. SEC. 107.2.1
 CITY AMENDMENTS TO FBC. ***NOTE: COORDINATE WITH ITEM
 #2 BELOW.
  
 2- IT LOOKS LIKE THIS PERMIT WAS APPLIED FOR TO REVOKE
 EXPIRED PERMIT APPLICATION #10110532. PERMIT
 APPLICATION #10110532 WAS NEVER APPROVED BECAUSE
 COMMENTS WERE NEVER ADDRESSED. PLEASE REVISE SCOPE OF
 WORK TO MATCH SCOPE OF WORK SUBMITTED ON PERMIT
 APPLICATION #10110532. THE FOLLOWING IS THE SCOPE OF
 WORK FOR PERMIT APPLICATION #10110532: "MAIN HOUSE -
 RENOVATION / REPAIRS. ELECTRIC, SHEETROCK, STUCCO,
 CLOSE 2 WINDOWS & 1 DOOR WITH LATHE/STUCCO. INSTALL NEW
 DOOR ON NORTH SIDE & REAR DOOR. ROOF SHINGLES, HVAC AIR
 HANDLER & COMPRESSOR". SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 3- REVISE VALUATION TO REFLECT ALL THE SCOPE OF WORK.
 VALUATION TO INCLUDE ALL LABOR AND MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR: ALL WINDOW TYPES TO BE REPLACED,
 WINDOW MULLIONS TO BE REPLACED, ALL EXTERIOR DOORS,
 ROOF SHINGLES,
  
 5- PROVIDE SOME SORT OF KEY PLAN IDENTIFYING ALL
 WINDOWS AND DOORS TO BE REPLACED. CLEARLY SPECIFY TYPE
 AND SIZE OF ALL EXISTING BEDROOM WINDOWS TO BE REPLACED
 AND PROPOSED WINDOW TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF
 2010 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2015-08-29 Cont ID  
Sent By skennedy Date 2015-08-29 Time 13:02 Rev Time 0.00
Received By skennedy Date 2015-08-29 Time 13:02 Sent To  
Notes
2015-07-09 13:40:50APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 NFPA 72.SECTION 29.8.3.4 SPECIFIC SMOKE DETECTOR
 LOCATION REQUIREMENTS:
 THE INSTALLATION OF SMOKE ALARMS AND SMOKE DETECTORS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 (1) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 LOCATED WHERE AMBIENT CONDITIONS, INCLUDING HUMIDITY
 AND TEMPERATURE, ARE OUTSIDE THE LIMITS SPECIFIED BY
 THE MANUFACTURER?S PUBLISHED INSTRUCTIONS.
 (2) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 LOCATED WITHIN UNFINISHED ATTICS OR GARAGES OR IN OTHER
 SPACES WHERE TEMPERATURES CAN FALL BELOW 40?F (4?C) OR
 EXCEED 100?F (38?C).
 (3)*WHERE THE MOUNTING SURFACE COULD BECOME
 CONSIDERABLY WARMER OR COOLER THAN THE ROOM, SUCH AS A
 POORLY INSULATED CEILING BELOW AN UNFINISHED ATTIC OR
 AN EXTERIOR WALL, SMOKE ALARMS AND SMOKE DETECTORS
 SHALL BE MOUNTED ON AN INSIDE WALL.
 (4)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A
 10 FT (3.0 M) RADIAL DISTANCE ALONG A HORIZONTAL FLOW
 PATH FROM A STATIONARY OR FIXED COOKING APPLIANCE,
 UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY TO
 COOKING APPLIANCES. SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT (6.1 M) ALONG
 A HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED
 COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION.
 EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE
 PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR
 INSTALLATION AT A RADIAL DISTANCE GREATER THAN 6 FT
 (1.8 M) FROM ANY STATIONARY OR FIXED COOKING APPLIANCE
 WHEN THE FOLLOWING CONDITIONS ARE MET:
 (A) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES
 HAVE NO CLEAR INTERIOR PARTITIONS OR HEADERS AND
 (B) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT
 THE PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
 (5)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 A DOOR TO A BATHROOM CONTAINING A SHOWER OR TUB.
 (6) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 THE SUPPLY REGISTERS OF A FORCED AIR HEATING OR COOLING
 SYSTEM AND SHALL BE INSTALLED OUTSIDE OF THE DIRECT
 AIRFLOW FROM THOSE REGISTERS.
 (7) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 THE TIP OF THE BLADE OF A CEILING-SUSPENDED (PADDLE)
 FAN.
 (8) WHERE STAIRS LEAD TO OTHER OCCUPIED LEVELS, A SMOKE
 ALARM OR SMOKE DETECTOR SHALL BE LOCATED SO THAT SMOKE
 RISING IN THE STAIRWAY CANNOT BE PREVENTED FROM
 REACHING THE SMOKE ALARM OR SMOKE DETECTOR BY AN
 INTERVENING DOOR OR OBSTRUCTION.
 (9) FOR STAIRWAYS LEADING UP FROM A BASEMENT, SMOKE
 ALARMS OR SMOKE DETECTORS SHALL BE LOCATED ON THE
 BASEMENT CEILING NEAR THE ENTRY TO THE STAIRS.
 (10)*FOR TRAY-SHAPED CEILINGS (COFFERED CEILINGS),
 SMOKE ALARMS AND SMOKE DETECTORS SHALL BE INSTALLED ON
 THE HIGHEST PORTION OF THE CEILING OR ON THE SLOPED
 PORTION OF THE CEILING WITHIN 12 IN. (300 MM)
 VERTICALLY DOWN FROM THE HIGHEST POINT.
 (11) SMOKE ALARMS AND DETECTORS INSTALLED IN ROOMS WITH
 JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF
 17.7.3.2.4.
 (12) HEAT ALARMS AND DETECTORS INSTALLED IN ROOMS WITH
 JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF
 17.6.3.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
2015-07-06 15:26:30NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 16:00 Rev Time 0.00
Received By dhayes Date   Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 16:01 Rev Time 0.00
Received By dhayes Date 2015-04-28 Time 15:25 Sent To  
Notes
2015-04-28 16:01:17DATE:4/28/2015
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061326
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 4TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEE BUILDING COMMENTS AS WELL.
  
 1) PROVIDE A LOAD SUMMARY. NEC 220.16
  
 2) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE,
 TYPE AND LOCATION OF THE SERVICE ENTRANCE,
 DISCONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM,
 MAIN(S), AND PANEL(S).
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 4) VERIFY RECEPTACLE SPACING. NEC 210.52
  
 5) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL
 SCHEDULE.
  
 6) PROVIDE A CIRCUIT DIRECTORY FOR EACH PANEL AND
 SUB-PANEL. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL
 BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 10:41 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 10:41 Sent To  
Notes
2014-11-13 10:50:37DATE:11/13/14
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061326
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL
 CURRENT FBC AND NEC BUT THE EDITIONS OF THE CODES NOTED
 ARE NOT ACCURATE. THE PLANS WILL BE REVIEWED UNDER THE
 2010 FBC AND THE 2008 NEC. THE SCOPE OF WORK ON THE
 APLICATION AND THE SCOPE OF WORK THAT APPEARS TO BE
 PROPOSED ON THE PLANS SUBMITTED ARE CONFLICTING. THE
 APPLICATION STATES THAT ONLY REPAIRS ARE TO BE
 PERFORMED INVOLVING 3 SHEETS OF DRYWALL ALONG WITH SOME
 TILE AND PAINT. THE PLANS INDICATE A NEW ELECTRICAL
 PANEL, NEW A/C, SEVERAL NEW OUTLETS, CEILING FANS, AND
 LIGHTS. PLEASE ADDRESS ALL COMMENTS REGARDING THE PALNS
 SUBMITTED.
  
 2) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. NEC 210.52(C)(1)
  
 3) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE,
 TYPE AND LOCATION OF THE SERVICE ENTRANCE,
 DICONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM,
 MAIN(S), AND PANEL(S).
  
 4) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING
 INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 6) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD
 CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL
 LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220.
 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR
 CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS.
 PART I PROVIDES FOR GENERAL REQUIREMENTS FOR
 CALCULATION METHODS. PART II PROVIDES CALCULATION
 METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV
 PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES.
 FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED
 ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD.
 ADDITIONALLY INCLUDE A LOAD FOR THE REAR BUILDING.
  
 7) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL SWITCH?
 CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXIT SWITH GRADE LEVEL ACCESS. A VEHICLE
 DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR
 ENTRANCE OR EXIT.. NEC 210.70(A)(2) INDICATE ALL
 REQUIRED SWITCHES AND LIGHTS REQUIRED.
  
 8) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11(C)(2)
  
 9) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
  
 10) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 11) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 12) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL
 SCHEDULE.
  
 THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT
 OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION
 DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL
 CURRENT CODES AND ORDINANCES PLEASE REVISE PLANS TO
 COMPLY WITH THE PROVISIONS OF THE 2008 EDITION OF THE
 NATIONAL ELECTRICAL CODE, THE 2010 EDITION OF THE
 FLORIDA BUILDING CODE AS WELL AS THE WEST PALM BEACH
 AMENDMENTS TO CHAPTER ONE OF THE FLORIDA BUILDING CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM, SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6717 OR [email protected]
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-10-16 Cont ID  
Sent By dhayes Date 2014-10-16 Time 12:29 Rev Time 0.00
Received By dhayes Date 2014-10-16 Time 12:29 Sent To  
Notes
2014-10-16 12:34:5110/16/2014
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061326
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE ADDRESS ON THE PLANS SUBMITTED DO NOT MATCH THE
 ADDRESS ON THE APPLICATION OR THE ADDRESS ON THE
 ORIGINAL PLANS SUBMITTED. THIS IS NOT THE SAME PROJECT
 THAT WAS SUBMITTED AND REVIEWED PREVIOUSLY. RESUBMIT
 WITH CORRECT PROJECT ADDRESSING THE DENIED COMMENTS
 FROM THE PREVIOUS REVIEW.
  
 YOU CAN SEE ALL CPREVIOUS COMMENTS AT THE FOLLOWING
 WEBSITE:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By dhayes Date 2014-07-30 Time 11:48 Rev Time 0.00
Received By dhayes Date 2014-07-30 Time 11:25 Sent To  
Notes
2014-07-30 11:53:54DATE: 7/30/2014
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061326
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SEE BUILDING REVIEW COMMENTS. NO PLANS SUBMITTED.
 2) SCOPE OF WORK AND VALUATION ON APPLICATION DOES NOT
 MATCH REVOKED EXPIRED PERMIT APPLICATION AND PLANS FOR
 AFTER THE FACT PROJECT. REVISE PERMIT VALUATION. FBC
 WPB AMENDMENTS. 109.3
  
 BUILDING COMMENTS BY JULIO GOMEZ:
 "1- NO PLANS WERE SUBMITTED SHOWING SCOPE OF WORK.
 PROVIDE COMPLETE INFORMATION FOR REVIEW. SEC. 107.2.1
 CITY AMENDMENTS TO FBC. ***NOTE: COORDINATE WITH ITEM
 #2 BELOW.
 2- IT LOOKS LIKE THIS PERMIT WAS APPLIED FOR TO REVOKE
 EXPIRED PERMIT APPLICATION #10110532. PERMIT
 APPLICATION #10110532 WAS NEVER APPROVED BECAUSE
 COMMENTS WERE NEVER ADDRESSED. PLEASE REVISE SCOPE OF
 WORK TO MATCH SCOPE OF WORK SUBMITTED ON PERMIT
 APPLICATION #10110532. THE FOLLOWING IS THE SCOPE OF
 WORK FOR PERMIT APPLICATION #10110532: "MAIN HOUSE -
 RENOVATION / REPAIRS. ELECTRIC, SHEETROCK, STUCCO,
 CLOSE 2 WINDOWS & 1 DOOR WITH LATHE/STUCCO. INSTALL NEW
 DOOR ON NORTH SIDE & REAR DOOR. ROOF SHINGLES, HVAC AIR
 HANDLER & COMPRESSOR". SEC. 107.2.1 CITY AMENDMENTS TO
 FBC."
 3- REVISE VALUATION TO REFLECT ALL THE SCOPE OF WORK.
 VALUATION TO INCLUDE ALL LABOR AND MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC."
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2015-08-26 Cont ID  
Sent By fmittner Date 2015-08-26 Time 14:07 Rev Time 0.00
Received By fmittner Date 2015-08-26 Time 14:07 Sent To  
Notes
2015-08-26 14:08:41NO OBSCURE GLASS

Review Stop HIST HISTORICAL
Rev No 4 Status F Date 2015-06-19 Cont ID  
Sent By fmittner Date 2015-06-19 Time 11:49 Rev Time 0.00
Received By fmittner Date 2015-06-19 Time 11:49 Sent To  
Notes
2015-06-19 11:49:56COMMENTS FROM LAST REVIEW NOT ADDRESSED. QUESTIONS
 CONTACT FRIEDERIKE MITTNER AT 822-1457.
2015-06-04 17:30:49NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2015-04-08 Cont ID  
Sent By fmittner Date 2015-04-08 Time 11:10 Rev Time 0.00
Received By fmittner Date 2015-03-31 Time 15:31 Sent To  
Notes
2015-04-08 11:11:21NEW FRONT PROCH REQURIES APPROVAL BY THE HPB. OWNER
 NEEDS TO SUBMIT COA FOR APPROVAL. SAHLLNOT USE OBSCURE
 WINDOW ON FRONT FACADE. QUESTIONS CONTACT FRIEDERIEK
 MITTNER AT 822-1457.
2015-03-09 12:01:16NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-10-30 Cont ID  
Sent By fmittner Date 2014-10-30 Time 13:24 Rev Time 0.00
Received By fmittner Date 2014-10-30 Time 13:24 Sent To  
Notes
2014-10-15 17:54:42SEE BUILDING COMMENTS DATED 7/29/14. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2014-09-08 Cont ID  
Sent By fmittner Date 2014-07-30 Time 07:43 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-07-09 17:10:527/9/14

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2015-09-02 Cont ID  
Sent By gjohnson Date 2015-09-02 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2015-09-02 Time 16:55 Sent To  
Notes
2015-09-01 15:19:38RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-09-01 Time 09:35 Rev Time 0.00
Received By jgomez Date 2015-07-21 Time 17:43 Sent To  
Notes
2015-07-30 17:43:40RE-SUBMITTAL SENT TO R12 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-07-30 Cont ID  
Sent By jgomez Date 2015-07-21 Time 17:44 Rev Time 0.00
Received By jgomez Date 2015-06-04 Time 17:29 Sent To  
Notes
2015-07-30 17:45:38NEW PACKAGE WAS RE-SUBMITTED ON 7/21/15. JG.
2015-06-04 17:29:49RE-SUBMITTAL SENT TO R9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 16:16 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 11:59 Sent To  
Notes
2015-04-25 12:30:49SENT TO D HAYES
2015-03-09 11:59:56RE-SUBMITTAL SENT TO R11 BIN FOR REVIEW. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 10:50 Rev Time 0.00
Received By dhayes Date 2014-10-23 Time 13:50 Sent To  
Notes
2014-10-23 13:50:53R19
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:55 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By jgomez Date 2014-08-18 Time 08:57 Rev Time 0.00
Received By jgomez Date 2014-06-30 Time 09:06 Sent To  
Notes
2014-09-03 08:57:44LAST REVIEW DONE ON 8/18/14. JG.
2014-07-07 09:06:46R12
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-09-01 Time 09:35 Rev Time 0.00
Received By jgomez Date 2015-09-01 Time 09:34 Sent To  
Notes
2015-09-01 09:35:197/10/15 MET WITH CONTRACTOR DAVID BOWDEN. ALL A/C
 INFORMATION TO BE SUBMITTED UNDER A SEPARATE PERMIT.
 JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2015-07-07 Cont ID  
Sent By jgomez Date 2015-07-06 Time 15:23 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 15:22 Sent To  
Notes
2015-07-06 15:23:32RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE AND CORRECT INFORMATION FOR
 MECHANICAL REVIEW. PROVIDE A/C PLANS AND EQUIPMENT
 SIZING CALCULATIONS SHOWING THE MANUFACTURER'S MODEL
 AND NUMBER AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION. ALSO, SHOW THE EQUIPMENT INFORMATION ON
 THE A/C PLAN.
  
 ***NOTE: THERE ARE NOT MECHANICAL PERMITS FOR THIS
 HOUSE. ANY MECHANICAL WORK WAS DONE WITHOUT PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 17:27 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 17:27 Sent To  
Notes
2015-04-13 17:27:31RESIDENTIAL (R3) ALTERATION THIRD MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-11-07 Cont ID  
Sent By jgomez Date 2014-11-07 Time 11:21 Rev Time 0.00
Received By jgomez Date 2014-11-07 Time 11:21 Sent To  
Notes
2014-11-07 11:22:07RESIDENTIAL (R3) ALTERATION THIRD MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:56 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 17:55 Sent To  
Notes
2014-10-15 17:57:05RESIDENTIAL (R3) ALTERATION SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 11:45 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 11:45 Sent To  
Notes
2014-07-29 11:46:11RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-09-02 Cont ID  
Sent By gjohnson Date 2015-09-02 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2015-09-02 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-08-06 Cont ID  
Sent By gjohnson Date 2015-08-06 Time 15:18 Rev Time 0.00
Received By gjohnson Date 2015-08-06 Time 15:18 Sent To  
Notes
2015-08-06 15:57:051ST REVIEW FBCP
  
 COMMENT
  
 1.PAGE A-1 SCOPE OF WORK SHOWS NEW BATHROOM. A RISER
 DIAGRAM IS REQUIERD FOR SANITY AND WATER.
 WPB AMENDMENTS TO FBC 2010 SEC. 107.3.5.3[11]
  
 2. VALUATION FOR SCOPE OF WORK APPEARS LOW SUBMIT
 SIGNED CONTRACT OR DETAILED
 ESTIMATE PER WPB AMEND TO FBC SEC 109.3
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 EX. 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By TLARGE Date 2015-07-08 Time 05:47 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 05:41 Sent To  
Notes
2015-07-08 05:25:231) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CANNOT COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 2) THE PLANS SHOW BUILDING #2 AS A GARAGE YET THERE IS
 A PLUMBING RISER THAT SHOWS PLUMBING FIXTURES.
 CLARIFY.WPB AMEND. TO 201 FBC SEC.107.2.1.
 3) IDENTIFY ON EACH FLOOR PLAN WHICH BUILDING NUMBER IT
 IS.WPB AMEND. TO 201 FBC SEC.107.2.1.
 4) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAMS DO
 NOT CORRELATE WITH THE FLOOR PLAN.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 5) THEWASHING MACHINE IN THE LAUNDRY IS NOT SHOWN ON
 ANY OF THE PLUMBING RISERS.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 I SUGGEST CALLING ME TO SET UP AN APPOINTMENT TO GO
 OVER THE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-09 Cont ID  
Sent By tklarge Date 2015-04-09 Time 11:41 Rev Time 0.00
Received By tklarge Date 2015-04-09 Time 11:33 Sent To  
Notes
2015-04-09 11:40:441) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CAN COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 14:54 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 14:54 Sent To  
Notes
2015-08-14 14:55:21SHINGLES NOA 12-0309.01 SUBMITTED. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By jgomez Date 2015-07-06 Time 15:25 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 15:24 Sent To  
Notes
2015-07-06 15:25:41NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES:
  
 1- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL
 ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED
 GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF
 SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL
 FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF
 THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO
 IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL
 SUBMITTED).
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2014-11-07 Cont ID  
Sent By jgomez Date 2014-11-07 Time 09:14 Rev Time 0.00
Received By jgomez Date 2014-11-07 Time 09:14 Sent To  
Notes
2014-11-07 09:14:57NO ROOF WORK ON THIS REVIEW. JG.

Review Stop Z ZONING
Rev No 5 Status P Date 2015-08-26 Cont ID  
Sent By fmittner Date 2015-08-26 Time 14:07 Rev Time 0.00
Received By fmittner Date 2015-08-26 Time 14:07 Sent To  
Notes
2015-07-30 17:48:37NEW PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 4 Status P Date 2015-06-19 Cont ID  
Sent By fmittner Date 2015-06-19 Time 11:50 Rev Time 0.00
Received By fmittner Date 2015-06-19 Time 11:50 Sent To  
Notes
2015-06-04 17:31:07NEW PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-04-08 Cont ID  
Sent By fmittner Date 2015-04-08 Time 11:10 Rev Time 0.00
Received By fmittner Date 2015-04-08 Time 11:10 Sent To  
Notes
2015-03-09 12:00:58NEW PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-30 Cont ID  
Sent By fmittner Date 2014-10-30 Time 13:24 Rev Time 0.00
Received By fmittner Date 2014-10-30 Time 13:24 Sent To  
Notes
2014-10-15 17:53:04SEE BUILDING COMMENTS DATED 7/29/14. JG.

Review Stop Z ZONING
Rev No 1 Status N Date 2014-09-08 Cont ID  
Sent By skennedy Date 2014-07-30 Time 07:43 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2014-07-30 13:50:067/30/14 ZONING SENT TO FM. SG