Plan Review Details - Permit 14061324
Plan Review Stops For Permit 14061324
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 10:30 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 09:38 Sent To  
Notes
2015-08-14 09:47:03BUILDING REVIEW APPROVED WITH PROVISO:
 1- DRAWING A-5: PROVIDE COMPLETE AND CORRECT GARAGE
 DOOR OPENING FRAMING DETAILS AND SPECIFICATIONS.
 SPECIFY ALL FRAMING MEMBERS AND FASTENERS. SEC. R301
 AND R601.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-07-01 Cont ID  
Sent By jgomez Date 2015-07-01 Time 09:21 Rev Time 0.00
Received By jgomez Date 2015-07-01 Time 09:21 Sent To  
Notes
2015-07-01 09:25:30RESIDENTIAL (R3) ALTERATION/ ADDITION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES:
  
 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT
 THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED. PROVIDE
 BREAKDOWN FOR THE SCOPE OF WORK ON MAIN HOUSE AND SCOPE
 OF WORK ON REAR STRUCTURE).
  
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH
 LADDER. (REPEAT COMMENT. NOT ADDRESSED. ROOF FRAMING
 DETAILS NOT PROVIDED. )
  
 3- PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT).
  
 4- PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES
 NEW PORCH. PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE LOADS
 OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. SPECIFY ALL
 FRAMING MEMBERS AND FASTENERS. (REPEAT COMMENT. THE
 FRONT ELEVATION IS NOW MISSING THE GUARDRAILS. THERE IS
 NOTHING TO COMPARE TO PROPOSED GUARDRAIL. HANDRAIL
 DETAIL SUBMITTED SEEMS TO BE FOR INTERIOR HANDRAIL. AND
 CLARIFY HOW ARE THE #12X3" WD. SCREWS TOP & BTM. @16"
 O/C INSTALLED AS SHOWN ON THE HANDRAIL DETAIL?. FLOOR
 PLAN ON SHEET A-1 CALLS FOR ALUMINUM RAILING. THIS
 DETAIL IS FOR WOOD RAILING. SEC. 107.2.1 CITY
 AMENDMENTS).
  
 5- WALL SECTION A/A-2: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW PROVIDING "CROSS
 VENTILATION" SEC. R806 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT. SPECIFY SPACING OF THE 4"X7" SPECIFIED VENTS
 TO VERIFY CROSS VENTILATION.).
  
 6- REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND
 REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
 (REPEAT COMMENT. NOT ADDRESSED. 2X4 BUCK DOESN'T
 PROVIDE FULL SUPPORT TO THE DOOR FRAME).
  
 7- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL
 ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED
 GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS.
  
 8- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF
 SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL
 FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF
 THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO
 IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL
 SUBMITTED).
  
 B) SINGLE HUNG WINDOW. INFORMATION SUBMITTED DOESN'T
 HAVE A FLORIDA PRODUCT APPROVAL NUMBER. PROVIDE THE
 CORRESPONDING FLORIDA PRODUCT APPROVAL FOR THE
 SUBMITTED PACKAGE OR MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL (COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR BUILDING OFFICIAL APPROVAL).
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS AND USP STRUCTURAL
 CONNECTORS SPECIFIED ON FRAMING PLANS AND ALL DETAILS.
 OR SPECIFY THE FLORIDA PRODUCT APPROVAL NEXT TO THE
 SPECIFIED CONNECTOR. (REPEAT COMMENT).
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- SHEET A-1:
 A) LETTERING ON THE SITE PLAN IS NOT LEGIBLE. SEC
 107.2.1.4 CITY AMENDMENTS.
  
 B) MAIN SCOPE ON MAIN NOTES SPECIFY "FIRE DAMAGE
 REPAIRS". PLANS DON'T SHOW ANY INFORMATION REGARDING
 THIS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING AREAS DAMAGED BY FIRE AND PROPOSED REPAIRS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF NEW PORCH STEPS SHOWING COMPLIANCE WITH
 SEC. R311.7.4 OF 2010 FBC-RESIDENTIAL.
  
 B) LETTERING ON SIMPSON STRAPS AND POST/CAPS SCHEDULES
 IS NOT LEGIBLE. IT'S TOO SMALL. SEC.107.2.1.4 CITY
 AMENDMENTS.
  
 C) CLEARLY COORDINATE INFORMATION SHOWN ON THE SIMPSON
 STRAPS AND POST/CAPS SCHEDULES, ROOF FRAMING PLAN,
 PORCH SECTION AND DETAILS B/A2, C/A2 AND D/A2. THIS IS
 LIKE CUTTING AND PASTING INFORMATION BUT IT DOESN'T
 MATCH ACTUAL CONDITIONS. CHECK SIZES OF FRAMING
 MEMBERS, ACTUAL CONNECTIONS, CONNECTORS SIZES VS
 STRUCTURAL MEMBERS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) PORCH SECTION: (1) CLARIFY FINISH GRADE LEVEL. 16"
 OR 24'. SEE FRONT ELEVATION. CLARIFY NEW CONCRETE PORCH
 SLAB CONSTRUCTION. PORCH SECTION SHOWS CRAWL SPACE
 BELOW THE SLAB. NEED TO PROVIDE COMPLETE INFORMATION
 FOR UNDER FLOOR SPACE AS REQUIRED BY SEC. R408 OF 2010
 FBC-RESIDENTIAL. AND, NEED TO SHOW HOW IS THE SLAB
 ANCHORED TO THE EXITING WALL. SEC. 107.2.1 CITY
 AMENDMENTS. (2) SPECIFICATIONS CALL FOR (3)2X10 WD
 BEAM. ONLY 2 ARE SHOWN. (3) ROOF RAFTERS ARE 2X6. ROOF
 FRAMING CALLS FOR 2X8. (4)
  
 13- SHEET A-5:
 A) NEW FLOOR PLAN CALLS WINDOW ON THE LEFT HAND SIDE AS
 "EXISTING WINDOW". PLANS ARE MISLEADING BECAUSE
 ACCORDING TO THE DEMOLITION PLAN THIS WINDOW IS NOT
 PLACED IN THE SAME LOCATION. CLEARLY SPECIFY IF THE
 WINDOW WAS REMOVED. IF IT WAS REMOVED, THEN THE SAME
 WINDOW CAN'T BE USED UNLESS PRODUCT APPROVAL FOR THE
 SAME WINDOW IS PROVIDED. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- SHEET A4: THERE IS A NEW BILLIARD ROOM SHOWN ON THE
 FLOOR PLAN. THE ROOM SEEMS TO BE TOO SMALL FOR A
 BILLIARD ROOM. PROVIDE COMPLETE LAYOUT OF POOL TABLE
 SHOWING CLEARANCES TO PLAY POOL. NOTE: ORIGINALLY, THIS
 ROOM WAS DESIGNED AS A BEDROOM. PROVIDE CLARIFICATION
 WHY CHANGING THE BEDROOM FOR A BILLIARD ROOM THAT MAY
 NOT BE SUITABLE BECAUSE THERE IS NOT ENOUGH ROOM. THE
 PROPOSED USE OF THIS ROOM MAY NOT BE SUITABLE BASED ON
 THE SIZE OF ROOM. SEC. 102.2CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 12:39 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 12:34 Sent To  
Notes
2015-04-13 12:48:53RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED:
  
 1- SITE PLAN SHOWN ON SHEET A-1 DOESN'T MATCH SITE PLAN
 SHOWN ON SHEET A-5. AND IS MISSING THE CONNECTION
 (LAUNDRY ROOM) OF THE GARAGE WITH THE REAR BUILDING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- SCOPE OF WORK SPECIFIED ON SHEET A-1 DOESN'T MATCH
 SCOPE OF WORK SPECIFIED ON SHEET A-5. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- DESIGN DATA FOR WIND LOADS SHOWN ON SHEET A-1
 DOESN'T MATCH DESIGN DATA SPECIFIED ON SHEET A-5. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- INFORMATION SHOWN ON THE DESIGN DATA ON SHEET A-1
 AND SHEET A-5 IS CONFUSING. INFORMATION FOR INTERIOR
 AND END ZONE IS REPEATED TWICE BUT THE DESIGN PRESSURES
 ARE DIFFERENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT
 THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY
 AMENDMENTS.
  
 6- SHEET A-1:
 A) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH
 LADDER.
  
 B) ENGINEER OF RECORD TO SPECIFY THE ALTERATION LEVEL
 TYPE OR COMBINATION OF LEVELS OF ALTERATION AS REQUIRED
 BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 C) CLEARLY SPECIFY WHICH WINDOWS AND EXTERIOR DOORS ARE
 EXISTING AND WHICH ARE GOING TO BE REPLACED. IF
 REPLACING EXISTING BEDROOM WINDOWS, THEN SPECIFY
 EXISTING TYPE AND SIZE AND PROPOSED TYPE AND SIZE TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604 OF 2010 FBC-EXISTING BUILDING.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 8- COORDINATE LABELING NUMBERS OF BUILDINGS SHOWN ON
 THE SITE PLAN WITH LABELING OF BUILDINGS SHOWN ON
 SHEETS A-2 TO A-5. REVISE AS REQUIRED. CLEARLY MATCH
 BUILDING #1, BUILDING #2 AND BUILDING #3 WITH NUMBERS
 SHOWN ON THE SITE PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A-2:
 A) PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES
 NEW PORCH ON SHEET A-5. PROVIDE COMPLETE FRAMING
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 LIVE LOADS OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS AND FASTENERS.
  
 C) INFORMATION SHOWN ON THE WOOD FRAMING DETAIL
 SECTION, WALL SECTION AND DOOR FRAMING SECTION DOESN'T
 MATCH. REVISE AS REQUIRED TO MATCH AND CLARIFY WHERE
 ARE THESE SECTIONS TAKEN AT. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-3:
 A) WALL SECTION A/A-1: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW PROVIDING "CROSS VENTILATION
 IN BLOCKING" AS SPECIFIED ON THE WALL SECTION. SEC.
 R806 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND
 REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SIZE OF WINDOW SHOWN ON THE LEFT ELEVATION DOESN'T
 MATCH SIZE SPECIFIED ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) REVISE WINDOWS AND DOORS DESIGN PRESSURES TO MATCH
 CORRECT DESIGN PRESSURES AS SPECIFIED ON SHEET A-1 AND
 A-5. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) RIGHT ELEVATION DOESN'T MATCH FLOOR PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 11- SHEET A-4:
 A) CLEARLY SPECIFY EXISTING AND PROPOSED WINDOWS AND
 EXTERIOR DOORS. (COORDINATE WITH EXTERIOR ELEVATIONS ON
 SHEET A-3). SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NEW FLOOR PLAN SHOWS "NEW BILLIARD ROOM" AND "NEW
 PLAYROOM". PREVIOUS PLANS SHOWED THESE ROOMS AS
 BEDROOMS. IT'S NOT CLEAR WHY THE ROOMS WERE REDESIGNED
 AS PLAYROOMS, BUT IF THE ROOMS ARE NOT DESIGNED AS
 BEDROOMS, THEN ENGINEER OF RECORD TO SPECIFY ON PLANS
 THAT THESE ROOMS CAN NOT BE USED FOR SLEEPING PURPOSES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A-5:
 A) THIS IS NOT ALTERATION LEVEL 2. REVISE AS REQUIRED.
 SEE SEC.401.4 OF 2010 FBC-EXISTING BUILDING.
  
 B) ROOF FRAMING PLAN IS MISSING INFORMATION: (1)
 PROVIDE WALL SECTION SHOWING WHERE IS THE NEW 2X8 WOOD
 LEDGER GOING TO BE ATTACHED TO THE EXISTING BUILDING.
 (2) SPECIFY LEDGER ANCHOR BOLT SIZE AND SPACING. (3)
 SPECIFY CEILING CLEARANCES. (4) SPECIFY BEAM SIZE. (5)
 SPECIFY ROOF PITCH. (6) SPECIFY ROOF SHEATHING SIZE AND
 FASTENER TYPE AND SPACING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) ROOF SHINGLES. NOA 11-0913.10 SUBMITTED WAS THE
 APPROVAL FOR ANOTHER PROJECT AND WAS REVIEWED AND
 APPROVED BY ANOTHER ENGINEER NOT THE ONE RESPONSIBLE
 FOR THIS PROJECT. AND NEED 2 COPIES. ONLY 1 WAS
 SUBMITTED.
  
 C) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR SIZE
 OF GARAGE DOOR SPECIFIED ON PLANS. ALSO, NOA 12-0125.20
 SUBMITTED IS FOR ANOTHER PERMIT AND WAS APPROVED BY
 ANOTHER ENGINEER NOT THE ONE RESPONSIBLE FO THIS
 PROJECT.
  
 D) SINGLE HUNG WINDOW. NOA 11-1013.14 SUBMITTED IS NOT
 LEGIBLE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND ALL DETAILS. OR SPECIFY THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
 FLORIDA PRODUCT APPROVAL WAS SUBMITTED FOR SOME
 CONNECTORS, BUT NOT ALL OF THEM.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ENGINEER TO CLARIFY WHY THE SIGNATURE ON THE
 APPROVED PRODUCT APPROVALS IS DIFFERENT THAT THE
 SIGNATURE ON THE PLANS. PROVIDE SIGNED AND SEALED
 LETTER WITH EXPLANATION. CHAPTER 471 F.S.
  
 15- ENGINEER IS USING OLD SEAL. NEED TO USE CURRENT
 SEAL WITH THE WORDING "LICENSE" NOT "CERTIFICATE". SEC.
 61G15-23.001. F.A.C.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
2015-04-09 11:46:231) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CAN COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 16:06 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 16:06 Sent To  
Notes
2014-11-06 16:16:21RESIDENTIAL (R3) ALTERATION/ ADDITION THIRD BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE: THIS COMMENTS APPLY TO THE REAR BUILDING ONLY.
 FRONT BUILDING IS REVIEWED UNDER PERMIT #14061326.
  
 1- SCOPE OF WORK IS NOT CLEAR. PLANS SUBMITTED NOW ARE
 COMPLETELY DIFFERENT FROM WHAT WAS REVIEWED THE FIRST
 TIME. PLANS SUBMITTED FOR THE FIRST REVIEW SHOWED A
 DWELLING UNIT WITH 2 NEW BEDROOMS, A LAUNDRY AREA
 CONNECTING TO THE "EXISTING BUILDING". NOW, PLANS ONLY
 SHOW A DETACHED OFFICE TO BE CONVERTED TO GARAGE. WHAT
 HAPPENED TO THE REST OF THE BUILDING?. IS THERE ANY
 WORK ON THE REAR DWELLING UNIT?. THERE ARE SOME PENDING
 VIOLATIONS ON THE REAR BUILDING THAT WERE NEVER
 ADDRESSED. REVISE PLANS AS REQUIRED. THE INTENTION IS
 TO REVOKE EXPIRED PERMIT APPLICATION 10110533 THAT WAS
 SUBMITTED TO ADDRESS PREVIOUS VIOLATIONS. PROVIDE PLANS
 WITH CLEAR SCOPE OF WORK AND REVISE SCOPE OF WORK ON
 THE PERMIT APPLICATION ACCORDINGLY. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- REVISE VALUATION ON THE PERMIT APPLICATION TO MATCH
 SCOPE OF WORK AS REQUESTED ON ITEM #1 ABOVE. SEC. 109.3
 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE GARAGE DOOR. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 4- SHEET A-1:
 A) ENGINEER TO REVISE EXISTING BUILDING CODE EDITION
 SHOWN. THE CURRENT CODE IS THE 2010 NOT THE 2007. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 5- ENGINEER TO CLARIFY/REVISE THE "DESIGN DATA FOR WIND
 LOAD" INFORMATION. THE INFORMATION FOR THE WINDOWS AND
 DOORS DESIGN PRESSURES IS NOT CLEAR. WHY THE WINDOWS
 AND DOORS SAY INTERIOR ZONE PRESSURES WHILE THE GARAGE
 DOOR SAYS END ZONE PRESSURES? SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 6- CLEARLY IDENTIFY ON PLANS DOORS AND WINDOWS TO BE
 REPLACED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) OVERHEAD GARAGE DOOR SIZE AS SPECIFIED ON PLANS.
 B) ALL DOORS AND WINDOWS TO BE REPLACED.
  
 *** NOTE: THERE ARE SOME PRODUCT APRPOVALS SUBMITTED
 THAT ARE FOR ANOTHER PERMIT APPLICATION (#14060946).
 ALL PRODUCT APPROVALS WERE SENT TO R12 SHELF TO RIDE
 ALONG WITH THAT PERMIT APPLICATION.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 ** NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 16:36 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 16:36 Sent To  
Notes
2014-10-15 16:36:34RESIDENTIAL (R3) ALTERATION/ ADDITION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
 ***NOTE: THIS INCLUDES THE OFFICE ADDITION. SEE ITEM #2
 AND #3 BELOW.
  
 2- PLANS SUBMITTED ON 2010 UNDER PERMIT #10110533
 SHOWED ONE OFFICE WITH COMPLETE BATHROOM AND CLOSET.
 THIS INFORMATION IS NOT SHOWN ON PLANS SUBMITTED THIS
 TIME. THERE ARE NOT PERMITS IN CITY RECORDS FOR THIS
 ADDITION. PROVIDE COMPLETE INFORMATION FOR THIS
 ADDITION. SEC. 107.2.1 AND 107.3.5.3 OF CITY AMENDMENTS
 TO FBC.
  
 3- IT LOOKS LIKE THIS PERMIT APPLICATION WAS DONE WITH
 THE INTENTION TO REVOKE OLD PERMIT APPLICATION
 #10110533. PERMIT APPLICATION #10110533 WAS SUBMITTED
 TO RESOLVE CODE VIOLATIONS. THIS PERMIT WAS NEVER
 ISSUED BECAUSE THE COMMENTS WERE NEVER ADDRESSED. THE
 SCOPE OF WORK IN THIS PERMIT APPLICATION AND PLANS
 SUBMITTED DON'T MATCH THE SCOPE OF WORK FOR WHICH
 PERMIT #10110533 WAS APPLIED FOR IN 2010. REVISE
 INFORMATION IN THE PERMIT APPLICATION AND PLANS TO
 MATCH THE DESCRIPTION STATED IN OLD PERMIT #10110533.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 ****** FOR YOUR INFORMATION THE FOLLOWING ISTHE
 DESCRIPTION STATED IN PERMIT #10110533: "RENOVATION
 REAR BLDG ( 1 & 2 ON PLAN) - ADD LAUNDRY ROOM,
 ELECTRICAL, PLUMBING, FOR SINK & LAUNDRY, BATH IN
 OFFICE AREA, SHEETROCK (2)FRONT & LAUNDRY, DOORS (3),
 TILE BATH, KITCHEN CABINETS, COUNTER, HVAC AIR HANDLER
 & COMPRESSOR".
 ***NOTE: WE HAVE COPIES OF THE PLANS SUBMITTED FOR
 PERMIT #10110533. THOSE PLANS WILL BE USED AS A
 REFERENCE TO COMPARE TO PLANS SUBMITTED NOW.
  
 4- UPDATE VALUATION DECLARED IN THE PERMIT APPLICATION
 TO INCLUDE ALL THE LABOR AND MATERIALS FOR ALL THE
 SCOPE OF WORK LISTED IN ITEM #3 ABOVE. AND, INCLUDE
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC.
  
 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS.
  
 B) CASEMENT WINDOWS.
  
 C) ALL EXTERIOR DOORS.
  
 D) ROOF SHINGLES AND FLAT ROOF WITH CORRESPONDING RAS
 117 CALCULATIONS, IF REQUIRED TO MEET THE DESIGN
 PRESSURES. (NOTE: ROOFING PERMIT WILL BE REQUIRED).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. COORDINATE WITH ITEM #2 ABOVE.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) AL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO 2010
 FBC.
  
 7- SHEET A-1:
 A) ENGINEER TO REVISE AREA CALCULATIONS. COORDINATE
 WITH ITEM #2 AND #3 ABOVE. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 B) ENGINEER TO SPECIFY LEVELS OF ALTERATIONS AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
 COORDINATE WITH ITEM #2 AND #3 ABOVE.
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT IN ORDER TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ANY REVISED SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-28 Cont ID  
Sent By jgomez Date 2014-07-28 Time 14:07 Rev Time 0.00
Received By jgomez Date 2014-07-28 Time 14:07 Sent To  
Notes
2014-07-28 14:08:30RESIDENTIAL (R3) ALTERATION/ ADDITION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
 ***NOTE: THIS INCLUDES THE OFFICE ADDITION. SEE ITEM #2
 AND #3 BELOW.
  
 2- PLANS SUBMITTED ON 2010 UNDER PERMIT #10110533
 SHOWED ONE OFFICE WITH COMPLETE BATHROOM AND CLOSET.
 THIS INFORMATION IS NOT SHOWN ON PLANS SUBMITTED THIS
 TIME. THERE ARE NOT PERMITS IN CITY RECORDS FOR THIS
 ADDITION. PROVIDE COMPLETE INFORMATION FOR THIS
 ADDITION. SEC. 107.2.1 AND 107.3.5.3 OF CITY AMENDMENTS
 TO FBC.
  
 3- IT LOOKS LIKE THIS PERMIT APPLICATION WAS DONE WITH
 THE INTENTION TO REVOKE OLD PERMIT APPLICATION
 #10110533. PERMIT APPLICATION #10110533 WAS SUBMITTED
 TO RESOLVE CODE VIOLATIONS. THIS PERMIT WAS NEVER
 ISSUED BECAUSE THE COMMENTS WERE NEVER ADDRESSED. THE
 SCOPE OF WORK IN THIS PERMIT APPLICATION AND PLANS
 SUBMITTED DON'T MATCH THE SCOPE OF WORK FOR WHICH
 PERMIT #10110533 WAS APPLIED FOR IN 2010. REVISE
 INFORMATION IN THE PERMIT APPLICATION AND PLANS TO
 MATCH THE DESCRIPTION STATED IN OLD PERMIT #10110533.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 ****** FOR YOUR INFORMATION THE FOLLOWING ISTHE
 DESCRIPTION STATED IN PERMIT #10110533: "RENOVATION
 REAR BLDG ( 1 & 2 ON PLAN) - ADD LAUNDRY ROOM,
 ELECTRICAL, PLUMBING, FOR SINK & LAUNDRY, BATH IN
 OFFICE AREA, SHEETROCK (2)FRONT & LAUNDRY, DOORS (3),
 TILE BATH, KITCHEN CABINETS, COUNTER, HVAC AIR HANDLER
 & COMPRESSOR".
 ***NOTE: WE HAVE COPIES OF THE PLANS SUBMITTED FOR
 PERMIT #10110533. THOSE PLANS WILL BE USED AS A
 REFERENCE TO COMPARE TO PLANS SUBMITTED NOW.
  
 4- UPDATE VALUATION DECLARED IN THE PERMIT APPLICATION
 TO INCLUDE ALL THE LABOR AND MATERIALS FOR ALL THE
 SCOPE OF WORK LISTED IN ITEM #3 ABOVE. AND, INCLUDE
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC.
  
 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS.
  
 B) CASEMENT WINDOWS.
  
 C) ALL EXTERIOR DOORS.
  
 D) ROOF SHINGLES AND FLAT ROOF WITH CORRESPONDING RAS
 117 CALCULATIONS, IF REQUIRED TO MEET THE DESIGN
 PRESSURES. (NOTE: ROOFING PERMIT WILL BE REQUIRED).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. COORDINATE WITH ITEM #2 ABOVE.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) AL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO 2010
 FBC.
  
 7- SHEET A-1:
 A) ENGINEER TO REVISE AREA CALCULATIONS. COORDINATE
 WITH ITEM #2 AND #3 ABOVE. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 B) ENGINEER TO SPECIFY LEVELS OF ALTERATIONS AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
 COORDINATE WITH ITEM #2 AND #3 ABOVE.
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT IN ORDER TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ANY REVISED SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2015-08-29 Cont ID  
Sent By skennedy Date 2015-08-29 Time 13:03 Rev Time 0.00
Received By skennedy Date 2015-08-29 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 16:04 Rev Time 0.00
Received By dhayes Date 2015-07-09 Time 16:04 Sent To  
Notes
2015-07-09 16:04:347/9/2015
 PROJECT: REAR STRUCTURE
 PERMIT#: 14061324
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 5TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) MAKE CORRECTIONS TO THE ELECTRICAL RISER DIAGRAM ON
 PG A-4. INDICATE THE SIZE AND TYPE AND LOCATION OF THE
 UTILITY SERVICE ENTRANCE. IS IT O/H OR U/G?
  
 2) THERE IS AN INDICATION OF TWO PANEL?C? ON THE FLOOR
 PLAN. ONE IN THE KITCHEN OF THE REAR STRUCTURE AND THE
 OTHER IN THE CONNECTED GARAGE? CLARIFY THE ACTUAL PANEL
 NAMES AND LOACTIONS. REVISE THE RISER DIAGRAM TO MATCH.
  
 3) PG A-5 INDICATES THE DEMOLITION AND REMOVAL OF A
 PANEL FROM A BATHROOM WALL THAT IS BEING DEMOLISHED.
 THE NEW FLOOR PLAN LAYOUT DOES NOT INCLUDE AN
 ELECTRICAL PANEL. HOWEVER THE RISER DIAGRAM INDICATES A
 FEEDER TO A SUB PANEL IN THAT LOCATION. PLEASE CLARIFY
 AND INDICATE THE LOCATION OF THE RELOCATED PANEL.
  
 4) THERE ARE 3 100AMP BREAKERS INDICATED IN THE 300AMP
 MAIN PANEL. ONE SUB FEED INDICATES A ?? PVC CONDUIT
 WITH 3 #3 WIRES. THERE ARE SEVERAL ISSUES WITH THIS. 1.
 IT?S NOT POSSIBLE TO BE A ?? CONDUIT. 2. IF IT?S A PVC
 CONDUIT IT REQUIRES A GROUND WIRE FROM NEC 250.122. AND
 3. IT CALLS OUT A THHN CONDUCTORS. THHN IS NOT APPROVED
 FOR WET LOCATION. AN OUTDOOR CONDUIT IS CONSIDERED A
 WET LOCATION.
  
 5) PROVIDE PANEL SCHEDULE FOR EACH OF THESE PANELS. NEC
 408.4
  
 6) THERE ARE SIMILAR ISSUES WITH THE NEXT CONDUIT TO
 THE NEW 100AMP SUB PANEL ?C?. THE RISER DIAGRAM SHOWS A
 1? CONDUIT 3,#6 AND 1#10CU GRD. A #6 CU CONDUCTOR IS
 NOT APPROVED FOR A 100AMP OCPD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 11:54 Rev Time 0.00
Received By dhayes Date 2015-07-09 Time 11:54 Sent To  
Notes
2015-07-09 12:36:287/9/2015
 PROJECT: REAR STRUCTURE
 PERMIT#: 14061324
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 16:03 Rev Time 0.00
Received By dhayes Date 2015-04-28 Time 16:03 Sent To  
Notes
2015-04-28 16:04:36DATE:4/28/2015
 PROJECT: 3721 EASTVIEW REAR STRUCTURE
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 4TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEE BUILDING COMMENTS AS WELL.
  
 1) PROVIDE A LOAD SUMMARY. NEC 220.16
  
 2) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE,
 TYPE AND LOCATION OF THE SERVICE ENTRANCE,
 DISCONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM,
 MAIN(S), AND PANEL(S).
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 4) VERIFY RECEPTACLE SPACING. NEC 210.52
  
 5) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL
 SCHEDULE.
  
 6) PROVIDE A CIRCUIT DIRECTORY FOR EACH PANEL AND
 SUB-PANEL. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL
 BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 09:42 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 09:42 Sent To  
Notes
2014-11-13 10:10:40DATE:11/13/14
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL
 CURRENT FBC AND NEC BUT THE EDITIONS OF THE CODES NOTED
 ARE NOT ACCURATE. THE PLANS WILL BE REVIEWED UNDER THE
 2010 FBC AND THE 2008 NEC. THE SCOPE OF WORK ON THE
 APLICATION AND THE SCOPE OF WORK THAT APPEARS TO BE
 PROPOSED ON THE PLANS SUBMITTED ARE CONFLICTING. THE
 APPLICATION STATES THAT ONLY INTERIOIR FINISH ARE TO BE
 PERFORMED INVOLVING A/C, ELECTRIC, DRYWALL, TILE, AND
 PAINT. THE PLANS FOR THE REAR BUILDING INDICATE DEMO
 ONLY WITH A NEW GARAGE DOOR AND A GFI OUTLET. PLEASE
 ADDRESS ALL COMMENTS REGARDING THE PALNS SUBMITTED.
  
 2) THE DEMOLITION PLAN INDICATES AN ELECTRICAL PANEL.
 THE NEW FLOOR PLAN HAS NO ELECTRICAL PANEL. PROVIDE
 INFORMATION TO CLARIFY WHERE AND HOW THE DEMOLISHED
 FEEDER IS TERMINATED AND WHERE AND HOW THE NEW BRANCH
 CIRCUIT COMES FROM TO FEED THE NEW GFI OUTLET.
  
 3) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER.
 INDICATE THE REQUIRED LIGHTING OUTLET. NEC 210.70(2))A)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM, SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6717 OR [email protected]
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-10-01 Cont ID  
Sent By dhayes Date 2014-10-01 Time 09:38 Rev Time 0.00
Received By dhayes Date 2014-10-01 Time 09:14 Sent To B
Notes
2014-10-01 10:04:56ROUTE TO J G'S DESK.
2014-10-01 09:54:1110/1/2014
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE ADDRESS ON THE PLANS SUBMITTED DO NOT MATCH THE
 ADDRESS ON THE APPLICATION OR THE ADDRESS ON THE
 ORIGINAL PLANS SUBMITTED. THIS IS NOT THE SAME PROJECT
 THAT WAS SUBMITTED AND REVIEWED PREVIOUSLY. RESUBMIT
 WITH CORRECT PROJECT ADDRESSING THE DENIED COMMENTS
 FROM THE PREVIOUS REVIEW.
  
 YOU CAN SEE ALL CPREVIOUS COMMENTS AT THE FOLLOWING
 WEBSITE:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By dhayes Date 2014-07-30 Time 12:09 Rev Time 0.00
Received By dhayes Date 2014-07-30 Time 12:08 Sent To  
Notes
2014-07-30 12:12:08DATE: 7/30/2014
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL
 CURRENT FBC AND NEC BUT THE FLOORPLAN LAYOUT DO NOT
 CONFORM TO CODE. FBC 107.2.1.
  
 2) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. NEC 210.52(C)(1)
  
 3) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONLY ONE SERVICE . NEC 230.2. THE
 ELECTRICAL SERVICE IS INDICATED AS TWO SEPARTATE
 SERVICES ON ONE BUILDING. THE GROUNDING ELECTRODE
 SYSTEM IS INDICATED AS A SERVICE LATTERAL??
  
 4) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING
 INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 6) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD
 CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL
 LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220.
 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR
 CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS.
 PART I PROVIDES FOR GENERAL REQUIREMENTS FOR
 CALCULATION METHODS. PART II PROVIDES CALCULATION
 METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV
 PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES.
 FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED
 ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD.
  
 7) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC 314(D) BOXES AT CEILING-SUSPENDED
 (PADDLE) FAN OUTLETS. NOTED ON PLANS.
  
 THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT
 OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION
 DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL
 CURRENT CODES AND ORDINANCES PLEASE READ AND AND COMPLY
 WITH THE PROVISIONS OF THE 2008 EDITION OF THE NATIONAL
 ELECTRICAL CODE, AND THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE AS WELL AS THE WEST PALM BEACH AMENDMENTS
 TO CHAPTER ONE OF THE FLORIDA BUILDING CODE.
  
 ADDITIONALLY, SEE BLDG. REVIEW COMMENTS BY JULIO GOMEZ
 WITH REGARDS TO ORIGNAL SCOPE OF WORK AND VALUATION ON
 ORIGINAL REVOKED PERMIT APPLICATION #10110533.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 PLEASE INSERT CORRECTED PAGES INTO SUBMITTAL PACKAGE
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2015-08-26 Cont ID  
Sent By fmittner Date 2015-08-26 Time 14:06 Rev Time 0.00
Received By fmittner Date 2015-08-26 Time 14:06 Sent To  
Notes
2015-07-30 17:38:31NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2015-06-19 Cont ID  
Sent By fmittner Date 2015-06-19 Time 11:51 Rev Time 0.00
Received By fmittner Date 2015-06-19 Time 11:51 Sent To  
Notes
2015-06-04 17:26:16NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-04-08 Cont ID  
Sent By fmittner Date 2015-04-08 Time 11:12 Rev Time 0.00
Received By fmittner Date 2015-04-08 Time 11:12 Sent To  
Notes
2015-03-09 11:56:36NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By fmittner Date 2014-10-08 Time 10:19 Rev Time 0.00
Received By fmittner Date 2014-10-08 Time 10:19 Sent To B
Notes
2014-10-08 10:22:07DENIED BY HISTORIC. SCOPE HAS COMPLETELY CHANGED. PLANS
 UNDER THIS PERMIT NUMBER NOW INDICATE AN ADDITION TO
 THE FRONT OF THE HOUSE. ADDITIONS REQUIRE A CERTIFICATE
 OF APPROPRIATENESS APPLICATION TO BE SUBMITTED FOR
 THOROUGH HISTORIC PRESERVATION REVIEW. QUESTIONS
 CONTACT FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION
 PLANNER AT (561) 822-1457.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-07-24 Cont ID  
Sent By fmittner Date 2014-07-24 Time 15:35 Rev Time 0.00
Received By fmittner Date 2014-07-24 Time 15:34 Sent To  
Notes
2014-07-09 17:09:387/9/14

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-08-29 Time 09:25 Rev Time 0.00
Received By jgomez Date 2015-07-21 Time 17:35 Sent To  
Notes
2015-09-01 09:27:08LAST REVIEW (ELECTRICAL) DONE ON 8/29/15,
2015-07-30 17:36:24RE-SUBMITTAL SENT TO R12 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 12:36 Rev Time 0.00
Received By dhayes Date 2015-06-04 Time 17:24 Sent To  
Notes
2015-06-04 17:24:57RE-SUBMITTAL SENT TO R9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 16:16 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 11:55 Sent To  
Notes
2015-04-25 12:29:11SENT TO D HAYES
2015-03-09 11:55:57RE-SUBMITTAL SENT TO R11 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 10:10 Rev Time 0.00
Received By dhayes Date 2014-10-23 Time 13:46 Sent To  
Notes
2014-10-23 13:49:24R19
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:44 Rev Time 0.00
Received By jgomez Date 2014-09-30 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-30 Cont ID  
Sent By dhayes Date 2014-07-30 Time 12:59 Rev Time 0.00
Received By dhayes Date 2014-06-30 Time 09:07 Sent To  
Notes
2014-07-07 09:07:46R12
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-07-06 Cont ID  
Sent By jgomez Date 2015-07-06 Time 14:49 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 14:49 Sent To  
Notes
2015-07-06 14:49:51NO FEES. MU-2015-13044.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 13:34 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 13:34 Sent To  
Notes
2015-04-13 13:35:081- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:44 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 17:44 Sent To  
Notes
2014-10-15 17:44:39RESIDENTIAL (R3) ALTERATION/ ADDITION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-28 Cont ID  
Sent By jgomez Date 2014-07-28 Time 14:04 Rev Time 0.00
Received By jgomez Date 2014-07-28 Time 14:03 Sent To  
Notes
2014-07-28 14:06:401- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2015-07-13 Cont ID  
Sent By jgomez Date 2015-07-10 Time 13:55 Rev Time 0.00
Received By jgomez Date 2015-07-10 Time 13:55 Sent To  
Notes
2015-07-13 13:57:347/10/15 MET WITH CONTRACTOR DAVID BOWDEN. ALL A/C
 INFORMATION TO BE SUBMITTED UNDER A SEPARATE PERMIT.
 JG.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-07-07 Cont ID  
Sent By jgomez Date 2015-07-06 Time 14:53 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 14:53 Sent To  
Notes
2015-07-06 14:54:59RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE AND CORRECT INFORMATION FOR
 MECHANICAL REVIEW. PROVIDE A/C PLANS AND EQUIPMENT
 SIZING CALCULATIONS SHOWING THE MANUFACTURER'S MODEL
 AND NUMBER AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION. ALSO, SHOW THE EQUIPMENT INFORMATION ON
 THE A/C PLAN.
  
 ****NOTE: THERE ARE NOT MECHANICAL PERMITS FOR THIS
 HOUSE. ANY MECHANICAL WORK WAS DONE WITHOUT PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 17:18 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 17:18 Sent To  
Notes
2015-04-13 17:19:48RESIDENTIAL (R3) ALTERATION/ ADDITION THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:43 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 17:43 Sent To  
Notes
2014-10-15 17:43:56RESIDENTIAL (R3) ALTERATION/ ADDITION SECOND MECHANICAL
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 09:33 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 09:33 Sent To  
Notes
2014-07-29 09:33:34RESIDENTIAL (R3) ALTERATION/ADDITION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR MECHANICAL REVIEW.
 PROVIDE A/C PLANS AND EQUIPMENT SIZING CALCULATIONS
 SHOWING THE MANUFACTURER'S MODEL AND NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. ALSO,
 SHOW THE EQUIPMENT INFORMATION ON THE A/C PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2015-09-02 Cont ID  
Sent By gjohnson Date 2015-09-02 Time 17:00 Rev Time 0.00
Received By gjohnson Date 2015-09-02 Time 17:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2015-08-06 Cont ID  
Sent By gjohnson Date 2015-08-06 Time 16:08 Rev Time 0.00
Received By gjohnson Date 2015-08-06 Time 16:08 Sent To  
Notes
2015-08-06 16:16:505TH REVIEW FBCP 2010
  
  
 COMMENTS
  
 1. NEED SPECS FOR WATER HEATER.
 WPB AMENDMENTS TO FBC 2010 107.2.1
  
 2. PLEASE CLARIFY DOES THE NEW WATER HEATER ON BUILDING
 2 SERVE BUILDING 1.
 WPB AMENDMENTS TO FBC 2010 107.2.1
  
 3. PLUMBING RISER FOR WASHING MACHINE ON BUILDING 2
 REQUIERD.
 WPB AMENDMENTS TO FBC 2010 107.2.1
  
 4. VALUATION FOR SCOPE OF WORK APPEARS LOW SUBMIT
 SIGNED CONTRACT OR DETAILED
 ESTIMATE PER WPB AMEND TO FBC SEC 109.3
  
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 EX. 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-07-08 Cont ID  
Sent By TLARGE Date 2015-07-08 Time 05:24 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 05:01 Sent To  
Notes
2015-07-08 05:24:321) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CANNOT COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 2) THE PLANS SHOW BUILDING #2 AS A GARAGE YET THERE IS
 A PLUMBING RISER THAT SHOWS PLUMBING FIXTURES.
 CLARIFY.WPB AMEND. TO 201 FBC SEC.107.2.1.
 3) IDENTIFY ON EACH FLOOR PLAN WHICH BUILDING NUMBER IT
 IS.WPB AMEND. TO 201 FBC SEC.107.2.1.
 4) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAMS DO
 NOT CORRELATE WITH THE FLOOR PLAN.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 5) THEWASHING MACHINE IN THE LAUNDRY IS NOT SHOWN ON
 ANY OF THE PLUMBING RISERS.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO GO
 OVER THE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-04-09 Cont ID  
Sent By tklarge Date 2015-04-09 Time 11:42 Rev Time 0.00
Received By tklarge Date 2015-04-09 Time 10:52 Sent To  
Notes
2015-04-09 11:42:351) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CAN COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 17:43 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 17:43 Sent To  
Notes
2014-10-15 17:43:26RESIDENTIAL (R3) ALTERATION/ ADDITION SECOND PLUMBING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTE:
 FLOOR PLANS AND INFORMATION SUBMITTED IS FOR 635 37TH
 STREET. THIS IS THE INCORRECT ADDRESS FOR THIS PERMIT
 APPLICATION. NEED TO PROVIDE COMPLETE INFORMATION
 ADDRESSING THE ORIGINAL COMMENTS BELOW:
  
  
 1- PROVIDE COMPLETE PLUMBING RISER DIAGRAM FOR REVIEW.
 SEC. 107.3.5.3 CITY AMENDMENTS TO FBC.
 ***NOTE: COORDINATE WITH BUILDING REVIEW COMMENTS
 REGARDING ALL SCOPE OF WORK.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 09:41 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 09:41 Sent To  
Notes
2014-07-29 09:44:57RESIDENTIAL (R3) ALTERATION/ADDITION PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 1- PROVIDE COMPLETE PLUMBING RISER DIAGRAM FOR REVIEW.
 SEC. 107.3.5.3 CITY AMENDMENTS TO FBC.
 ***NOTE: COORDINATE WITH BUILDING REVIEW COMMENTS
 REGARDING ALL SCOPE OF WORK.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 14:30 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 14:30 Sent To  
Notes
2015-08-14 14:31:40NO ROOFING ON REAR STRUCTURE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By jgomez Date 2015-07-06 Time 14:50 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 14:50 Sent To  
Notes
2015-07-06 14:51:56NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES:
  
 1- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL
 ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED
 GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF
 SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL
 FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF
 THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO
 IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL
 SUBMITTED).
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2014-11-07 Cont ID  
Sent By jgomez Date 2014-11-07 Time 09:15 Rev Time 0.00
Received By jgomez Date 2014-11-07 Time 09:15 Sent To  
Notes
2014-11-07 09:16:10NO ROOF WORK ON THIS REVIEW. JG.

Review Stop Z ZONING
Rev No 6 Status P Date 2015-08-26 Cont ID  
Sent By fmittner Date 2015-08-26 Time 14:06 Rev Time 0.00
Received By fmittner Date 2015-08-26 Time 14:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2015-06-19 Cont ID  
Sent By fmittner Date 2015-06-19 Time 11:52 Rev Time 0.00
Received By fmittner Date 2015-06-19 Time 11:52 Sent To  
Notes
2015-06-04 17:25:25NEW PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 4 Status P Date 2015-04-08 Cont ID  
Sent By fmittner Date 2015-04-08 Time 11:12 Rev Time 0.00
Received By fmittner Date 2015-04-08 Time 11:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2014-10-30 Cont ID  
Sent By fmittner Date 2014-10-30 Time 13:20 Rev Time 0.00
Received By fmittner Date 2014-10-30 Time 13:20 Sent To  
Notes
2014-10-30 13:21:24NO SECOND UNIT PERMITTED ON SITE (PLANS SHOW KITCHEN).

Review Stop Z ZONING
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By fmittner Date 2014-10-08 Time 10:22 Rev Time 0.00
Received By fmittner Date 2014-10-08 Time 10:22 Sent To  
Notes
2014-10-08 10:22:46SCOPE OF WORK NOT CLEAR. IS THIS FOR FRONT HOUSE OR
 REAR HOUSE.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By fmittner Date 2014-07-15 Time 15:04 Rev Time 0.00
Received By fmittner Date 2014-07-15 Time 15:04 Sent To B
Notes
2014-07-24 15:36:56NO KITCHEN PERMITTED IN REAR UNIT. QUESTIONS CONTACT
 FRIEDERIKE MITTNER 822-1457.
2014-07-11 15:19:047/11/14