Plan Review Details - Permit 14061270
Plan Review Stops For Permit 14061270
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 09:30 Rev Time 0.00
Received By jgomez Date 2014-09-16 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-08-27 Cont ID  
Sent By jgomez Date 2014-08-27 Time 14:08 Rev Time 0.00
Received By jgomez Date 2014-08-27 Time 14:08 Sent To  
Notes
2014-08-27 14:30:49BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE ENERGY CALCULATIONS: A) REVISE DOOR TYPE
 ON SHEET 3 OF 6 TO MATCH TYPE SHOWN ON PLANS AND
 PRODUCT APPROVALS SUBMITTED. B) REVISE WINDOWS OVERHANG
 DEPTH AND SEPARATION TO MATCH PLANS.
  
 2- PROVIDE MANUFACTURER'S SPECS SHOWING THE WINDOWS AND
 DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR: EXTERIOR DOOR NOA 09-0415.08
 SUBMITTED NOW ARE FOR NON-IMPACT GLAZED DOORS. PROVIDE
 PRODUCT APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS.
 SEC. 606.4 OF 2010 FBC-EXISTING BUILDING.
  
 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL. SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 5- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE HURRICANE SHUTTERS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-06 Cont ID  
Sent By jgomez Date 2014-08-06 Time 14:37 Rev Time 0.00
Received By jgomez Date 2014-08-06 Time 14:37 Sent To  
Notes
2014-08-06 15:02:36RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 AND SEC.
 103 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT.
 NOT ADDRESSED).
 (NOTE: THIS IS NOT A CONTRIBUTING HISTORIC HOUSE).
  
 2- ENGINEER TO REVISE THE ROOF SHEATHING INFORMATION
 GIVEN ON SHEET A-1:
 A) NEED TO SPECIFY MIN. 8D RING SHANK NAILS WHICH ARE 2
 1/2" LONG NOT 1 1/4". SEE SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) ENGINEER TO CLARIFY WHY THE NAILING ZONES ARE PER
 RAS 117?. WHERE IS THIS INFORMATION TAKEN FROM? ROOF
 SHEATHING AND RAS 117 ARE TWO DIFFERENT THINGS. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- ENGINEER TO REVISE EXTERIOR DOOR STRUCTURAL BUCK
 DETAIL ON SHEET A-2. NEED TO COMPLY WITH SEC.
 R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: THE BUCKS
 NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAMING. 2" X
 4" BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 SEE DOOR PRODUCT APPROVAL FOR DOOR FRAME SIZE AND
 REVISE AS REQUIRED.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS
 SPECIFIED ON DETAILS ON SHEET A-1. ***NOTE: PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR. (REPEAT COMMENT NOT
 ADDRESSED).
  
 B) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS.
 DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE INCOMPLETE
 AND CUT. NEED COMPLETE DRAWINGS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 C) NEW COMMENT: SINGLE HUNG NOA 11-0404.09 AND EXTERIOR
 DOOR NOA 09-0608.16 SUBMITTED NOW ARE FOR NON-IMPACT
 WINDOWS AND DOORS. THEREFORE, NEED TO PROVIDE PRODUCT
 APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS AS REQUIRED
 BY SEC. 606.4 OF 2010 FBC-EXISTING BUILDING.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 OF CITY AMENDMENTS TO FBC.
  
 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE HURRICANE SHUTTERS. THERE IS A CITY
 HURRICANE SHUTTERS INSTALLATION CHART THAT YOU CAN USE
 OR YOU CAN PROVIDE A DIFFERENT FORMAT THAT PROVIDES ALL
 THE INFORMATION REQUESTED IN THE CITY SAMPLE. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
  
 ***NOTES:
 *PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT
 TO EXPEDITE THE REVIEW PROCESS.
 *PLEASE REPLACE ANY REVISE SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-22 Cont ID  
Sent By jgomez Date 2014-07-21 Time 11:32 Rev Time 0.00
Received By jgomez Date 2014-07-21 Time 11:31 Sent To  
Notes
2014-07-21 11:32:22RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
 (NOTE: NOT A CONTRIBUTING HISTORIC HOUSE).
  
 2- ENGINEER TO PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR GABLE END WALL SHOWING COMPLIANCE
 WITH SEC. R609.4 OF 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE NEW ROOF
 SHEATHING. SPECIFY MATERIAL AND FASTENER TYPE AND
 SPACING. SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL
 AND SPACING TO BE USED, INCLUDING ROOF ZONE #3.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF
 VENTILATION AS REQUIRED BY SEC. R806.
  
 5- A) REVISE ALL WINDOW STRUCTURAL BUCK DETAILS ON
 SHEET A-2. PROVIDE COMPLETE SPECIFICATIONS FOR SIZE AND
 FASTENING OF WINDOW BUCKS. REVISE DETAILS TO COMPLY
 WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE:
 THE BUCKS NEED TO PROVIDE FULL SUPPORT TO THE WINDOW
 FRAMING. REVISE DETAILS AS REQUIRED.
  
 B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR DOORS.
 SEC. R612.10.2.1. COORDINATE WITH COMMENT 5(A) ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS TO BE INSTALLED.
  
 B) WINDOW MULLIONS. AND CLEARLY IDENTIFY MULLION SIZE
 AND FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
  
 C) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS
 SPECIFIED ON DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR
  
 D) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS.
 DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE CUT. NEED
 COMPLETE DRAWINGS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 8- BEDROOM WINDOWS TO BE REPLACED: SPECIFY EXISTING
 TYPE AND SIZE OF EXITING WINDOWS TO BE REPLACED TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604.1 OF 2010 FBC-EXISTING BUILDING.
  
 9- REVISE WINDOW SCHEDULE. THERE ARE NO ALUMINUM CLAD
 WOOD WINDOWS. SEE PRODUCT APPROVALS SUBMITTED AND
 REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS...
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By rmcdouga Date 2014-08-20 Time 11:40 Rev Time 0.00
Received By rmcdouga Date 2014-08-20 Time 11:40 Sent To  
Notes
2014-08-20 11:41:17APPROVED WITH EXCEPTIONS. MAKE CORRECTIONS AS RED-LINED
 ON PLANS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2014-08-20 09:58:45NEW SHEETS SUBMITTED. JG.
2014-08-06 16:45:16NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-22 Cont ID  
Sent By rmcdouga Date 2014-07-22 Time 17:27 Rev Time 0.00
Received By rmcdouga Date 2014-07-22 Time 17:27 Sent To  
Notes
2014-07-22 17:43:21APPROVED WITH EXCEPTION. MAKE CORRECTIONS AS NOTED ON
 PLANS.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-08-19 Cont ID  
Sent By fmittner Date 2014-08-19 Time 16:04 Rev Time 0.00
Received By fmittner Date 2014-08-19 Time 16:04 Sent To  
Notes
2014-08-06 16:46:02NEW DRAWINGS AND PRODUCT APPROVALS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-07-09 Cont ID  
Sent By fmittner Date 2014-07-09 Time 14:11 Rev Time 0.00
Received By fmittner Date 2014-07-09 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 13:52 Rev Time 0.00
Received By jgomez Date 2014-09-10 Time 11:37 Sent To  
Notes
2014-09-11 11:37:48TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-27 Cont ID  
Sent By jgomez Date 2014-08-27 Time 15:20 Rev Time 0.00
Received By jgomez Date 2014-08-20 Time 09:57 Sent To  
Notes
2014-08-20 09:58:11RE-SUBMITTAL SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-20 Cont ID  
Sent By jgomez Date 2014-08-19 Time 09:56 Rev Time 0.00
Received By jgomez Date 2014-08-01 Time 14:19 Sent To  
Notes
2014-08-20 09:57:23LAST REVIEW DONE BY HISTORIC. 8/19/14. . JG.
2014-08-05 14:20:568/6/14 RE-SUBMITTAL SENT TO ZONING SHELF FOR HISTORIC
 REVIEW. NEW PRODUCT APPROVALS AND DRAWINGS WERE
 SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-07-22 Time   Rev Time 0.00
Received By jgomez Date 2014-06-27 Time 07:24 Sent To  
Notes
2014-07-10 07:24:32SENT TO R13 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 13:27 Rev Time 0.00
Received By jgomez Date 2014-09-16 Time 13:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-08-27 Cont ID  
Sent By jgomez Date 2014-08-27 Time 15:20 Rev Time 0.00
Received By jgomez Date 2014-08-27 Time 15:20 Sent To  
Notes
2014-08-27 15:20:34MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
 A) FRONT DOOR DOESN'T FACE EAST.
 B) GLAZING U-VALUE AND SHGC VALUE DOESN'T MATCH THE ONE
 SPECIFIED IN THE ENERGY CALCULATIONS.
  
 2- REVISE TRANSFER DUCT SIZE SPECIFIED FOR DEN AREA.
 SIZE TO BE MIN. 13" AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-08-06 Cont ID  
Sent By jgomez Date 2014-08-06 Time 16:55 Rev Time 0.00
Received By jgomez Date 2014-08-06 Time 16:55 Sent To  
Notes
2014-08-06 16:49:03RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ****NOTE: THERE WAS NOT INFORMATION SUBMITTED TO
 ADDRESS THE COMMENTS ON FIRST REVIEW. PLEASE ADDRESS
 THE FOLLOWING COMMENTS FROM THE FIRST CHECKLIST:
  
  
  
 1- PROVIDE COMPLETE INFORMATION FOR REVIEW:
 A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT
 MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF
 2010 FBC-ENERGY CONSERVATION.
  
 B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT
 INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO
 FBC
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT.
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-22 Cont ID  
Sent By jgomez Date 2014-07-22 Time 14:40 Rev Time 0.00
Received By jgomez Date 2014-07-22 Time 14:40 Sent To  
Notes
2014-07-22 14:40:59RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE INFORMATION FOR REVIEW:
 A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT
 MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF
 2010 FBC-ENERGY CONSERVATION.
  
 B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT
 INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO
 FBC
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT.
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By jgomez Date 2014-08-27 Time 15:04 Rev Time 0.00
Received By jgomez Date 2014-08-27 Time 15:04 Sent To  
Notes
2014-08-20 09:59:51NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-06 Cont ID  
Sent By jgomez Date 2014-08-06 Time 16:51 Rev Time 0.00
Received By jgomez Date 2014-08-06 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-22 Cont ID  
Sent By jgomez Date 2014-07-22 Time 15:02 Rev Time 0.00
Received By jgomez Date 2014-07-22 Time 14:56 Sent To  
Notes
2014-07-22 15:14:06RESIDENTIAL (R3) ALTERATION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- KITCHEN PLUMBING RISER DIAGRAM: THE CLOTHES WASHING
 MACHINE VENTING AND WASTE IS INCORRECT. SEE SEC. P2718
 OF 2010 FBC-RESIDENTIAL AND SEC. P3005.1.1. APPLIANCES
 WITH PUMPING ACTION DISCHARGE CAN NOT BE CONNECTED TO
 THE KITCHEN BRANCH AS SHOWN ON PLUMBING RISER DIAGRAM.
 REVISE AS REQUIRED.
  
 ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE
 LICENSED CONTRACTOR DOING THE WORK. IF DOING SO,
 CONTRACTOR TO PROVIDE NAME AND SIGNATURE ON PLUMBING
 RISER DIAGRAM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-19 Cont ID  
Sent By fmittner Date 2014-08-19 Time 16:05 Rev Time 0.00
Received By fmittner Date 2014-08-19 Time 16:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-09 Cont ID  
Sent By fmittner Date 2014-07-09 Time 14:12 Rev Time 0.00
Received By fmittner Date 2014-07-09 Time 14:12 Sent To B
Notes
***NONE***