Plan Review Stops For Permit 14061270 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-09-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-09-16 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-09-16 |
Time |
09:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-08-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-27 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-27 |
Time |
14:08 |
Sent To |
|
|
Notes |
2014-08-27 14:30:49 | BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- REVISE THE ENERGY CALCULATIONS: A) REVISE DOOR TYPE | | ON SHEET 3 OF 6 TO MATCH TYPE SHOWN ON PLANS AND | | PRODUCT APPROVALS SUBMITTED. B) REVISE WINDOWS OVERHANG | | DEPTH AND SEPARATION TO MATCH PLANS. | | | | 2- PROVIDE MANUFACTURER'S SPECS SHOWING THE WINDOWS AND | | DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY | | CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: EXTERIOR DOOR NOA 09-0415.08 | | SUBMITTED NOW ARE FOR NON-IMPACT GLAZED DOORS. PROVIDE | | PRODUCT APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS. | | SEC. 606.4 OF 2010 FBC-EXISTING BUILDING. | | | | 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT | | APPROVAL. SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | 5- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE | | INSTALLATION OF THE HURRICANE SHUTTERS. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-08-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-06 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-06 |
Time |
14:37 |
Sent To |
|
|
Notes |
2014-08-06 15:02:36 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 AND SEC. | | 103 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. | | NOT ADDRESSED). | | (NOTE: THIS IS NOT A CONTRIBUTING HISTORIC HOUSE). | | | | 2- ENGINEER TO REVISE THE ROOF SHEATHING INFORMATION | | GIVEN ON SHEET A-1: | | A) NEED TO SPECIFY MIN. 8D RING SHANK NAILS WHICH ARE 2 | | 1/2" LONG NOT 1 1/4". SEE SEC. R803.2.3.1 OF 2010 | | FBC-RESIDENTIAL. | | | | B) ENGINEER TO CLARIFY WHY THE NAILING ZONES ARE PER | | RAS 117?. WHERE IS THIS INFORMATION TAKEN FROM? ROOF | | SHEATHING AND RAS 117 ARE TWO DIFFERENT THINGS. REVISE | | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 3- ENGINEER TO REVISE EXTERIOR DOOR STRUCTURAL BUCK | | DETAIL ON SHEET A-2. NEED TO COMPLY WITH SEC. | | R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: THE BUCKS | | NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAMING. 2" X | | 4" BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME. | | SEE DOOR PRODUCT APPROVAL FOR DOOR FRAME SIZE AND | | REVISE AS REQUIRED. | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS | | SPECIFIED ON DETAILS ON SHEET A-1. ***NOTE: PROVIDE | | ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING | | THE SPECIFIED CONNECTOR. (REPEAT COMMENT NOT | | ADDRESSED). | | | | B) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS. | | DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE INCOMPLETE | | AND CUT. NEED COMPLETE DRAWINGS. (REPEAT COMMENT. NOT | | ADDRESSED). | | | | C) NEW COMMENT: SINGLE HUNG NOA 11-0404.09 AND EXTERIOR | | DOOR NOA 09-0608.16 SUBMITTED NOW ARE FOR NON-IMPACT | | WINDOWS AND DOORS. THEREFORE, NEED TO PROVIDE PRODUCT | | APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS AS REQUIRED | | BY SEC. 606.4 OF 2010 FBC-EXISTING BUILDING. | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 | | OF CITY AMENDMENTS TO FBC. | | | | 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE | | INSTALLATION OF THE HURRICANE SHUTTERS. THERE IS A CITY | | HURRICANE SHUTTERS INSTALLATION CHART THAT YOU CAN USE | | OR YOU CAN PROVIDE A DIFFERENT FORMAT THAT PROVIDES ALL | | THE INFORMATION REQUESTED IN THE CITY SAMPLE. SEC. | | 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | ***NOTES: | | *PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT | | TO EXPEDITE THE REVIEW PROCESS. | | *PLEASE REPLACE ANY REVISE SHEET. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-07-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-07-21 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-07-21 |
Time |
11:31 |
Sent To |
|
|
Notes |
2014-07-21 11:32:22 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 | | FBC-ENERGY CONSERVATION. | | (NOTE: NOT A CONTRIBUTING HISTORIC HOUSE). | | | | 2- ENGINEER TO PROVIDE COMPLETE DETAIL AND | | SPECIFICATIONS FOR GABLE END WALL SHOWING COMPLIANCE | | WITH SEC. R609.4 OF 2010 FBC-RESIDENTIAL. | | | | 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE NEW ROOF | | SHEATHING. SPECIFY MATERIAL AND FASTENER TYPE AND | | SPACING. SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL | | AND SPACING TO BE USED, INCLUDING ROOF ZONE #3. | | | | 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF | | VENTILATION AS REQUIRED BY SEC. R806. | | | | 5- A) REVISE ALL WINDOW STRUCTURAL BUCK DETAILS ON | | SHEET A-2. PROVIDE COMPLETE SPECIFICATIONS FOR SIZE AND | | FASTENING OF WINDOW BUCKS. REVISE DETAILS TO COMPLY | | WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: | | THE BUCKS NEED TO PROVIDE FULL SUPPORT TO THE WINDOW | | FRAMING. REVISE DETAILS AS REQUIRED. | | | | B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR DOORS. | | SEC. R612.10.2.1. COORDINATE WITH COMMENT 5(A) ABOVE. | | | | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) SINGLE HUNG WINDOWS TO BE INSTALLED. | | | | B) WINDOW MULLIONS. AND CLEARLY IDENTIFY MULLION SIZE | | AND FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES. | | | | C) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS | | SPECIFIED ON DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT | | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED | | CONNECTOR | | | | D) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS. | | DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE CUT. NEED | | COMPLETE DRAWINGS. | | | | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | 8- BEDROOM WINDOWS TO BE REPLACED: SPECIFY EXISTING | | TYPE AND SIZE OF EXITING WINDOWS TO BE REPLACED TO | | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. | | 604.1 OF 2010 FBC-EXISTING BUILDING. | | | | 9- REVISE WINDOW SCHEDULE. THERE ARE NO ALUMINUM CLAD | | WOOD WINDOWS. SEE PRODUCT APPROVALS SUBMITTED AND | | REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS... | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-20 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-20 |
Time |
11:40 |
Sent To |
|
|
Notes |
2014-08-20 11:41:17 | APPROVED WITH EXCEPTIONS. MAKE CORRECTIONS AS RED-LINED | | ON PLANS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2014-08-20 09:58:45 | NEW SHEETS SUBMITTED. JG. | 2014-08-06 16:45:16 | NEW SHEETS SUBMITTED. JG. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-07-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-22 |
Time |
17:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-22 |
Time |
17:27 |
Sent To |
|
|
Notes |
2014-07-22 17:43:21 | APPROVED WITH EXCEPTION. MAKE CORRECTIONS AS NOTED ON | | PLANS. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2014-08-19 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2014-08-19 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2014-08-19 |
Time |
16:04 |
Sent To |
|
|
Notes |
2014-08-06 16:46:02 | NEW DRAWINGS AND PRODUCT APPROVALS SUBMITTED. JG. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2014-07-09 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2014-07-09 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2014-07-09 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-09-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-09-16 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-09-10 |
Time |
11:37 |
Sent To |
|
|
Notes |
2014-09-11 11:37:48 | TO JG DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-08-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-27 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-20 |
Time |
09:57 |
Sent To |
|
|
Notes |
2014-08-20 09:58:11 | RE-SUBMITTAL SENT TO JULIO'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-08-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-19 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-01 |
Time |
14:19 |
Sent To |
|
|
Notes |
2014-08-20 09:57:23 | LAST REVIEW DONE BY HISTORIC. 8/19/14. . JG. | 2014-08-05 14:20:56 | 8/6/14 RE-SUBMITTAL SENT TO ZONING SHELF FOR HISTORIC | | REVIEW. NEW PRODUCT APPROVALS AND DRAWINGS WERE | | SUBMITTED. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2014-07-22 |
Time |
|
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-06-27 |
Time |
07:24 |
Sent To |
|
|
Notes |
2014-07-10 07:24:32 | SENT TO R13 SHELF FOR REVIEW. JG. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2014-09-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-09-16 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-09-16 |
Time |
13:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2014-08-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-27 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-27 |
Time |
15:20 |
Sent To |
|
|
Notes |
2014-08-27 15:20:34 | MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 | | OF 2010 FBC-ENERGY CONSERVATION. | | A) FRONT DOOR DOESN'T FACE EAST. | | B) GLAZING U-VALUE AND SHGC VALUE DOESN'T MATCH THE ONE | | SPECIFIED IN THE ENERGY CALCULATIONS. | | | | 2- REVISE TRANSFER DUCT SIZE SPECIFIED FOR DEN AREA. | | SIZE TO BE MIN. 13" AS REQUIRED BY SEC. M1602.4 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF PERSON | | RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 OF CITY | | AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2014-08-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-06 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-06 |
Time |
16:55 |
Sent To |
|
|
Notes |
2014-08-06 16:49:03 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW | | CHECKLIST. | | CODE: 2010 FBC. | | | | ****NOTE: THERE WAS NOT INFORMATION SUBMITTED TO | | ADDRESS THE COMMENTS ON FIRST REVIEW. PLEASE ADDRESS | | THE FOLLOWING COMMENTS FROM THE FIRST CHECKLIST: | | | | | | | | 1- PROVIDE COMPLETE INFORMATION FOR REVIEW: | | A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT | | MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF | | 2010 FBC-ENERGY CONSERVATION. | | | | B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT | | INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING | | CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO | | FBC | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT. | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-07-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-07-22 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-07-22 |
Time |
14:40 |
Sent To |
|
|
Notes |
2014-07-22 14:40:59 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE COMPLETE INFORMATION FOR REVIEW: | | A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT | | MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF | | 2010 FBC-ENERGY CONSERVATION. | | | | B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT | | INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING | | CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO | | FBC | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT. | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2014-08-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-27 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-27 |
Time |
15:04 |
Sent To |
|
|
Notes |
2014-08-20 09:59:51 | NEW SHEETS SUBMITTED. JG. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-08-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-08-06 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-08-06 |
Time |
16:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-07-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2014-07-22 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2014-07-22 |
Time |
14:56 |
Sent To |
|
|
Notes |
2014-07-22 15:14:06 | RESIDENTIAL (R3) ALTERATION, PLUMBING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- KITCHEN PLUMBING RISER DIAGRAM: THE CLOTHES WASHING | | MACHINE VENTING AND WASTE IS INCORRECT. SEE SEC. P2718 | | OF 2010 FBC-RESIDENTIAL AND SEC. P3005.1.1. APPLIANCES | | WITH PUMPING ACTION DISCHARGE CAN NOT BE CONNECTED TO | | THE KITCHEN BRANCH AS SHOWN ON PLUMBING RISER DIAGRAM. | | REVISE AS REQUIRED. | | | | ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE | | LICENSED CONTRACTOR DOING THE WORK. IF DOING SO, | | CONTRACTOR TO PROVIDE NAME AND SIGNATURE ON PLUMBING | | RISER DIAGRAM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2014-08-19 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2014-08-19 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2014-08-19 |
Time |
16:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-07-09 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2014-07-09 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2014-07-09 |
Time |
14:12 |
Sent To |
B |
|
Notes |
|
|