Plan Review Details - Permit 14061268
Plan Review Stops For Permit 14061268 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2014-07-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-07-09 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-07-09 |
Time |
16:04 |
Sent To |
|
|
Notes |
2014-07-09 16:12:01 | BUILDING PROVISO: | | NO ROOFING PRODUCT APPROVALS SUBMITTED. | | TO BE REVIEWED UNDER A SEPARATE ROOFING PERMIT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-07-30 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-30 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-07-30 |
Time |
17:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2014-09-02 |
|
|
Cont ID |
|
Sent By |
cranford |
Date |
2014-09-02 |
Time |
09:45 |
Rev Time |
1.50 |
Received By |
cranford |
Date |
2014-09-02 |
Time |
09:45 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-07-18 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-07-18 |
Time |
14:33 |
Sent To |
|
|
Notes |
2014-07-18 15:14:48 | 4847 FRED GLADSTONE DRIVE | | PERMIT #14061268 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET C2: THE "DARK GRAY" PAVED AREA INDICATED AS | | "SAWCUT MATCH EXISTING PAVEMENT" ADJACENT TO THE NEW | | PORTECOCHERE SHOULD BE MARKED AS A FIRE LANE. PER | | SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE MARKED | | WITH FREESTANDING SIGNS READING, "FIRE LANE - NO | | PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL | | BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS | | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE | | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE | | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. | | | | SHEET C2 AND SHEET LP1: FIRE HYDRANTS SHALL REMAIN | | CLEAR OF ALL OBSTRUCTIONS INCLUDING WATER FEATURES, | | BUILDINGS, VEHICLES, TREES, SHRUBS, ETC. FIRE HYDRANTS | | SHALL BE PROVIDED WITH A CLEAR SPACE OF 7'-6" TO THE | | FRONT/SIDES AND 4'-0" TO THE REAR BEHIND THE STEAMER | | CAP. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-09-02 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-09-02 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-07-01 |
Time |
09:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2014-09-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-09-19 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-09-19 |
Time |
08:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2014-09-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-09-18 |
Time |
17:21 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2014-09-18 |
Time |
17:21 |
Sent To |
|
|
Notes |
2014-09-18 17:23:43 | PASSED W/PROVISO | | | | 1) PRIOR TO THE FINAL INSPECTION THE MINOR AMENDMENT | | FOR THE SITE PLAN MODIFICATIONS SHALL HAVE BEEN | | APPROVED BY ZONING. | | | | 2) THE LANDSCAPE REQUIRES A SEPARATE PERMIT WITH PLANS. | | PLEASE NOTE THAT THE LANDSCAPE PLAN HAS NOT YET BEEN | | APPROVED AS PART OF THE MINOR AMENDMENT. | | | | 3) THE SITE LIGHTING REQUIRES A SEPARATE PERMIT WITH | | PLANS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-07-16 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-07-16 |
Time |
16:48 |
Rev Time |
0.75 |
Received By |
eschneid |
Date |
2014-07-16 |
Time |
16:48 |
Sent To |
|
|
Notes |
2014-07-16 17:35:15 | FAILED | | | | 1) THE MINOR AMENDMENT FOR THE SITE PLAN MODIFICATIONS | | HAS NOT BEEN APPROVED. ZONING STAFF IS AWAITING REVISED | | PLANS. | | | | 2) THE LANDSCAPE REQUIRES A SEPARATE PERMIT WITH PLANS. | | PLEASE NOTE THAT THE LANDSCAPE PLAN HAS NOT YET BEEN | | APPROVED AS PART OF THE MINOR AMENDMENT. | | | | 3) THE SITE LIGHTING REQUIRES A SEPARATE PERMIT WITH | | PLANS. | | | | 4) THE OVERALL LAYOUT OF THE IMPROVEMENTS MEET ZONING | | REQUIREMENTS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | 2014-07-01 16:33:42 | 7-1-14 |
|
|
|