Plan Review Details - Permit 14061217
Plan Review Stops For Permit 14061217
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2016-03-22 Time 10:01 Sent To  
Notes
2016-03-24 09:32:52BUILDING PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. MARCH 22/ 2016
 ACTION: DENIED
  
 1) PROVISO: THE SURVEY INDICATES THE PROPOSED BUILDING
 WILL PROVIDE A REPLAT BEFORE PERMIT ISSUANCE.
  
 2) THRESHOLD BUILDINGS.
  
 2A) COMPLIED, 109.3.6.1 SUBMITTED A WRITTEN THRESHOLD
 PLAN.
  
 2B) COMPLIED.
  
 2C) 3RD REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD AGREEMENT FORMS MUST BE SIGNED BY ALL
 INTERESTED PARTIES AND RETURNED TO THE BUILDING
 DEPARTMENT BEFORE PERMIT ISSUANCE. . CONTACT KEN CONRAD
 MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 OR E-MAIL: [email protected] FOR FURTHER
 INFORMATION.
  
 2D) 3RD REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE REQUIRED.
  
 2E) 3RD REQUEST. THE CONTRACTOR OF RECORD WILL PRODUCE
 A JOB SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2F) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT.
 PLEASE CALL THE CITY OF WEST PALM BEACHES? AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2G) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT.
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 3-4) COMPLIED.
  
 5) 3RD REQUEST. ONLY ONE SIGNED & SEALED SOILS REPORT
 SUBMITTED THIS REVIEW, 2 ADDITIONAL SIGNED & SEALED
 ORIGINAL REPORTS ARE STILL REQUIRED. ARDAMAN &
 ASSOCIATES SUBSURFACE AND GEOTECHNICAL ENGINEERING
 EVALUATION REPORT DATED MAY 14/ 2014.
 5A) THE GEOTECHNICAL REPORT RECOMMENDS THE 14 INCH
 DIAMETER AUGER CAST PILE BE DRILLED TO A DEPTH OF 48
 FEET. THE 2010 FBC-B 1810. 3.5.2.2 UNCASED CAST IN
 PLACE DEEP FOUNDATIONS THE LENGTH SHALL NOT EXCEED 30
 TIMES THE AVERAGE DIAMETER OR APPROXIMATELY 35 FEET.
 THE EXCEPTION: THE LENGTH OF THE ELEMENT IS PERMITTED
 TO EXCEED 30 TIMES THE DIAMETER, PROVIDED THE DESIGN
 AND INSTALLATION OF THE DEEP FOUNDATIONS ARE UNDER THE
 DIRECT SUPERVISION OF A REGISTERED DESIGN PROFESSIONAL
 KNOWLEDGEABLE IN THE FIELD OF SOIL MECHANICS AND DEEP
 FOUNDATIONS. THE REGISTERED DESIGN PROFESSIONAL SHALL
 SUBMIT A REPORT TO THE BUILDING OFFICIAL STATING THAT
 THE ELEMENTS WERE INSTALLED IN COMPLIANCE WITH THE
 APPROVED CONSTRUCTION DOCUMENTS.
  
 5B) PLEASE PROVIDE WHAT GEOTECHNICAL ENGINEER WILL BE
 SUPERVISING AND MONITORING THE INSTALLATION OF THE
 AUGER CAST TEST PILE AS WELL AS THE PRODUCTION PILE.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 5C) WILL THERE BE A SPECIALTY PILE CONTRACTOR
 INSTALLING THE 14 INCH DIAMETER AUGER CAST PILE. THE
 PILE CONTRACTOR SHOULD BE RESPONSIBLE FOR DESIGNING,
 AND INSTALLING THE TEST ASSEMBLY AND PROVIDE A RECENTLY
 CALIBRATED HYDRAULIC JACK. THE CONTRACTOR?S DESIGN AND
 CALIBRATION OF THE TEST EQUIPMENT SHALL BE SUBMITTED TO
 THE GEOTECHNICAL ENGINEER FOR REVIEW AND APPROVAL.
  
  
  
  
  
 6) COMPLIED.
  
 7) SHEET A1.00 LIFE SAFETY SHEET:
 7A-F) COMPLIED.
  
 7G) PROVISO: APPROVED BY FIRE CHIEF PROVIDED THAT THE
 EQUIPMENT FITS DOES NOT MEET THE SIZE REQUIREMENTS OF
 911.1.3.THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE
 COMPLIANCE WITH [F] 403.4.5 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 7H-O) COMPLIED.
  
  
 7P)PROVISO, COMPLIED REPEAT 7G.
  
 7Q)3RD REQUEST. 2010FBC-B MISSING INFORMATION: 403.6
 ELEVATORS. ELEVATOR INSTALLATION AND OPERATION IN
 HIGH-RISE BUILDINGS SHALL COMPLY WITH CHAPTER 30 AND
 SECTIONS 403.6.1 AND 403.6.2.
  
 403.6.1 FIRE SERVICE ACCESS ELEVATOR. IN BUILDINGS WITH
 AN OCCUPIED FLOOR MORE THAN 120 FEET (36 576 MM) ABOVE
 THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS, A
 MINIMUM OF ONE FIRE SERVICE ACCESS ELEVATOR SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 3007.
  
 3007.4 FIRE SERVICE ACCESS ELEVATOR LOBBY. THE FIRE
 SERVICE ACCESS ELEVATOR SHALL OPEN INTO A FIRE SERVICE
 ACCESS ELEVATOR LOBBY IN ACCORDANCE WITH SECTIONS
 3007.4.1 THROUGH 3007.4.4.
  
 EXCEPTION: WHERE A FIRE SERVICE ACCESS ELEVATOR HAS TWO
 ENTRANCES ONTO A FLOOR, THE SECOND ENTRANCE SHALL BE
 PERMITTED TO OPEN INTO AN ELEVATOR LOBBY IN ACCORDANCE
 WITH SECTION 708.14.1.
  
 3RD REQUEST. 3007.4.1 ACCESS. THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL HAVE DIRECT ACCESS TO AN EXIT
 ENCLOSURE.
 THE RESPONSE INDICATES THAT A MEETING IS REQUESTED.
 I?VE SPOKEN TO THE BUILDING OFFICIAL ABOUT THIS CODE
 ISSUE AND THE RESPONSE THAT IT WAS APPROVED BY CHIEF
 PETER LEDUC. THE CODE ARTICLE GIVEN IS NOT A NFPA BUT
 2010 FLORIDA BUILDING CODE-BUILDING CODE SECTION. MR.
 BROWN REQUEST THAT THE ARCHITECT OF RECORD WRITE A
 LETTER ON THEIR LETTER HEAD THAT THEY RECEIVED APPROVAL
 FROM CHIEF PETER LEDUC, SIGN AND SEAL THE LETTER SO IT
 WILL BECOME PART OF THE PERMIT SET OF DOCUMENTS, (3)
 ORIGINALS TO GO WITH EACH SET OF PLANS.
  
 COMPLIED. 3007.4.2 LOBBY ENCLOSURE.
 THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 ENCLOSED WITH A SMOKE BARRIER HAVING A MINIMUM 1-HOUR
 FIRE-RESISTANCE RATING, EXCEPT THAT LOBBY DOORWAYS
 SHALL COMPLY WITH SECTION 3007.4.3.
  
 COMPLIED. 3007.4.3 LOBBY DOORWAYS. EACH FIRE SERVICE
 ACCESS ELEVATOR LOBBY SHALL BE PROVIDED WITH A DOORWAY
 THAT IS PROTECTED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 715.4. THE FIRE DOOR ASSEMBLY
 SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLY REQUIREMENTS OF SECTION 715.4.3.1 WITH THE UL
 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL.
  
 COMPLIED. PROVIDE THE SQUARE FOOTAGE OF THE FIRE
 SERVICE ELEVATOR LOBBY. 3007.4.4 LOBBY SIZE. EACH
 ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE A
 MINIMUM OF 150 SQUARE FEET (14 M2) IN AN AREA WITH A
 MINIMUM DIMENSION OF 8 FEET (2440 MM).
  
 7R) COMPLIED. SHEET A8.00 WALL TYPES K-P DO NOT PROVIDE
 FIRE RATING OF WALL.
  
 8-10) COMPLIED.
  
 11) SHEET A2.03:
 11A) THE PLANS SHOW A SHAFT BEGINNING ON THE 4TH FLOOR,
 THE SHEET A2.04-A2.10 SHOW THE SHAFT BUT THE WALL TAGS
 ARE MISSING FOR THE 2 HOUR FIRE RATING OF SHAFT. 2010
 FBC-B 708.2 SHAFT REQUIRED.
  
 12) SHEET A2.11: COMPLIED.
  
 13A-D) BUILDING PROVISO: THE PRODUCT APPROVALS HAVE
 BEEN REQUESTED TO BE DEFERRED SUBMITTALS. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE PROVIDE 3 SETS OF PRODUCT APPROVALS FOR EACH OF
 THE FOLLOWING COMPONENTS AND OR CLADDING IF SUBMITTING
 IN PAPER FORM.
  
 13A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES & WATERPROOFING FOR
 SLABS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 13B) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 13C) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER.
  
 13D) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
  
 14) BUILDING PROVISO: 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) COMPLIED WIND DESIGN CRITERIA..
  
 16-20) COMPLIED.
  
 20A) PROVISO: PLEASE ALSO NOTE THE 3 RD. FLOOR IS TO BE
 DESIGNED FOR A FUTURE RESTAURANT, BE AWARE OF 1013.2
 WHERE FIXED SEATING MAY BE A HEIGHT FACTOR IN THE GUARD
 RAIL PER 2010 FBC-B 1013.2..
  
 21) COMMENT # 5( A-C). SHEET S1 AND S11.1 BOTH INDICATE
 THE USE OF AUGER CAST PILE, PLEASE PROVIDE WHAT AGENCY/
 INSPECTION SERVICE WILL BE RESPONSIBLE FOR THE
 OBSERVING & RECORD KEEPING OF THE AUGER CAST PILE AS
 WELL AS LOAD TESTING TO SECTION 2010 FBC-B
 1810.3.3.1.2.
  
 22A) SHEET M602 BUILDING PRESSURIZATION- CONTROL
 SEQUENCE. UNDER THE HEADING 2.2.2.(A) (3) INDICATE THE
 INSTALLATION OF FIRE SMOKE DAMPERS WHEREAS THE FLOOR
 PLANS ONLY SHOW A FIRE DAMPER AT THE CORRIDOR.
 GUESTROOM WALL? 107.2.1.3. DISCREPANCY IN PLANS.
  
 22B) SHEET M602 BUILDING PRESSURIZATION- CONTROL
 SEQUENCE. UNDER THE HEADING 2.2.2.(C) THE PLANS
 INDICATE ONLY PRESSURIZING FLOORS 4 THROUGH 10. PLEASE
 EXPLAIN WHY THE 2ND AND 3RD FLOORS ARE NOT BEING
 PRESSURIZED? 909.6 PRESSURIZATION METHOD. THE PRIMARY
 MECHANICAL MEANS OF CONTROLLING SMOKE SHALL BE BY
 PRESSURE DIFFERENCES ACROSS SMOKE BARRIERS. MAINTENANCE
 OF A TENABLE ENVIRONMENT IS NOT REQUIRED IN THE SMOKE
 CONTROL ZONE OF FIRE ORIGIN.
  
 22C) PLEASE PROVIDE COMPLIANCE WITH: FBC-B 909.4
 ANALYSIS. A RATIONAL ANALYSIS SUPPORTING THE TYPES OF
 SMOKE CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6.
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 24) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2015-05-19 Time   Sent To  
Notes
2015-05-22 16:10:56BUILDING PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. MAY 22 2015
 ACTION: DENIED
  
 1) PROVISO: THE SURVEY INDICATES THE PROPOSED BUILDING
 WILL PROVIDE A REPLAT BEFORE PERMIT ISSUANCE.
  
 2) THRESHOLD BUILDINGS.
  
 2A) COMPLIED, 109.3.6.1 SUBMITTED A WRITTEN THRESHOLD
 PLAN.
  
 2B) COMPLIED.
  
 2C) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE.THE THRESHOLD
 AGREEMENT FORMS MUST BE SIGNED BY ALL INTERESTED
 PARTIES AND RETURNED TO THE BUILDING DEPARTMENT BEFORE
 PERMIT ISSUANCE. . CONTACT KEN CONRAD MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)805-6666 OR E-MAIL:
 [email protected] FOR FURTHER INFORMATION.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE REQUIED.
  
 2E) 2ND REQUEST. THE CONTRACTOR OF RECORD WILL PRODUCE
 A JOB SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2F) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT.
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2G) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT.
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 3-4) COMPLIED.
  
 5) 2ND REQUEST. NOTE, 3 ADDITIONAL WRITTENTHRESHOLD
 INSPECTION PLANS WERE SUBMITTED. SHEET S11.1 FOUNDATION
 NOTE # 1 ARDAMAN & ASSOCIATES HAS COMPLETED A SOILS
 REPORT DATED MAY 14/ 2014. PLEASE SUPPLY THE BUILDING
 DEPARTMENT WITH (3) ORIGINAL SIGNED & SEALED REPORTS.
 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION
 SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS
 OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR
 OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE
 LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS
 NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH,
 POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT
 OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY,
 COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS.
  
 6) COMPLIED.
  
 7) SHEET A1.00 LIFE SAFETY SHEET:
 7A-D) COMPLIED.
  
  
 7E) PLEASE PROVIDE COMPLIANCE A MEETING WITH OTHER
 DESIGNERS MAY BE REQUIRED.
 EMERGENCY POWER NOTES DON'T SHOW COMPLIANCE WITH 2010
 FBC-B [F] 403.4.8.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
 403.4.8.1:
 (3.) EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS;
  
 (4.) AUTOMATIC FIRE DETECTION SYSTEMS;
  
 (5.) FIRE ALARM SYSTEMS; AND
  
 (6.) ELECTRICALLY POWERED FIRE PUMPS.
  
 7F) (1) COMPLIED. (1) FIRE PUMP) THE LIFE SAFETY SHEET
 LEVEL 1 DOES NOT INDICATE COMPLIANCE WITH 403.3.2 WATER
 SUPPLY TO REQUIRED FIRE PUMPS.
  
 7F)(2) @ND REQUEST. CIVIL SHEET 09 DOES NOT SHOW WATER
 FROM 2 DIFFERENT MAINS. 2010 FBC-B 403.3.2 2 REQUIRED
 MAINS. REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY
 CONNECTIONS TO A MINIMUM OF TWO WATER MAINS LOCATED IN
 DIFFERENT STREETS. SEPARATE SUPPLY PIPING SHALL BE
 PROVIDED BETWEEN EACH CONNECTION TO THE WATER MAIN AND
 THE PUMPS. EACH CONNECTION AND THE SUPPLY PIPING
 BETWEEN THE CONNECTION AND THE PUMPS SHALL BE SIZED TO
 SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE. THE EXCEPTION WOULD STILL REQUIRE THE MAINS TO
 BE VALVED TO ALLOW FOR 2 TAPS TO BE INDEPENDENT BUT THE
 2 SUPLY LINES MERGE BACK INTO ONE LINE BEFORE GOING TO
 THE INPUT CHAMBER OF THE FIRE PUMP. THE FIRE DEPATMENT
 REQUIRES IF THIS METHOD OF COMPLIANCE IS CHOSEN THAT
 THE 2 TAPS CONTINUE UNTIL THEY MANIFOLD BACK TOGETHER
 AS A MANAFOLD JUST BEFORE THE INTAKE OF THE FIRE PUMP.
  
 7G) PROVISO: APPROVED BY FIRE CHIEF PROVIDED THAT THE
 EQUIPMENT FITS DOES NOT MEET THE SIZE REQUIREMENTS OF
 911.1.3.THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE
 COMPLIANCE WITH [F] 403.4.5 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 7H-J) COMPLIED.
  
 7K) MISSING INFORMATION: [F] 403.4.1 SMOKE DETECTION.
 SMOKE DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 907.2.13.1.
  
 7L) MISSING INFORMATION: [F] 403.4.2 FIRE ALARM SYSTEM.
 A FIRE ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 907.2.13.
  
 7M) [F] 403.4.3 EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 7N) [F] 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. [F]
 915.1 GENERAL. EMERGENCY RESPONDER RADIO COVERAGE SHALL
 BE PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE
 FLORIDA FIRE PREVENTION CODE.
  
  
 7O) COMPLIED. 403.4.6 SMOKE REMOVAL. SMOKE CONTROL
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 909.
  
 7P) REPEAT OF 7G.
  
 7Q) MISSING INFORMATION: 403.6 ELEVATORS.
 ELEVATOR INSTALLATION AND OPERATION IN HIGH-RISE
 BUILDINGS SHALL COMPLY WITH CHAPTER 30 AND SECTIONS
 403.6.1 AND 403.6.2.
  
 7Q) 403.6.1 FIRE SERVICE ACCESS ELEVATOR.
 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 FEET
 (36 576 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS, A MINIMUM OF ONE FIRE SERVICE ACCESS
 ELEVATOR SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007.
 3007.4 FIRE SERVICE ACCESS ELEVATOR LOBBY.
 THE FIRE SERVICE ACCESS ELEVATOR SHALL OPEN INTO A FIRE
 SERVICE ACCESS ELEVATOR LOBBY IN ACCORDANCE WITH
 SECTIONS 3007.4.1 THROUGH 3007.4.4.
  
 EXCEPTION: WHERE A FIRE SERVICE ACCESS ELEVATOR HAS TWO
 ENTRANCES ONTO A FLOOR, THE SECOND ENTRANCE SHALL BE
 PERMITTED TO OPEN INTO AN ELEVATOR LOBBY IN ACCORDANCE
 WITH SECTION 708.14.1.
  
 2ND REQUEST. 3007.4.1 ACCESS. THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL HAVE DIRECT ACCESS TO AN EXIT
 ENCLOSURE.
  
 COMPLIED. 3007.4.2 LOBBY ENCLOSURE.
 THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 ENCLOSED WITH A SMOKE BARRIER HAVING A MINIMUM 1-HOUR
 FIRE-RESISTANCE RATING, EXCEPT THAT LOBBY DOORWAYS
 SHALL COMPLY WITH SECTION 3007.4.3.
  
 EXCEPTION: ENCLOSED FIRE SERVICE ACCESS ELEVATOR
 LOBBIES ARE NOT REQUIRED AT THE STREET FLOOR.
  
 2ND REQUEST. 3007.4.3 LOBBY DOORWAYS. EACH FIRE SERVICE
 ACCESS ELEVATOR LOBBY SHALL BE PROVIDED WITH A DOORWAY
 THAT IS PROTECTED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 715.4. THE FIRE DOOR ASSEMBLY
 SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLY REQUIREMENTS OF SECTION 715.4.3.1 WITH THE UL
 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL.
  
 2ND REQUEST, PROVIDE THE SQUARE FOOTAGE OF THE FIRE
 SERVICE ELEVATOR LOBBY. 3007.4.4 LOBBY SIZE. EACH
 ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE A
 MINIMUM OF 150 SQUARE FEET (14 M2) IN AN AREA WITH A
 MINIMUM DIMENSION OF 8 FEET (2440 MM).
  
 7R) SHEET A8.00 WALL TYPES K-P DO NOT PROVIDE FIRE
 RATING OF WALL.
  
 8-10) COMPLIED.
  
 11) SHEET A2.03:
 11A) THE PLANS DO NOT DEPICT ANY SHAFTS IN THE KITCHEN
 AREA FOR THE FUTURE KITCHEN EXHAUST & HOOD SYSTEM.
 708.2 SHAFT REQUIED. SHEET A2.04 DOES SHOW NOT A 2 HOUR
 SHAFT BUT WHAT APPEARS TO BE 2 HOUR FIRE RATED DUCT
 WRAP. THIS DETAIL IS CONSISTENT UP THROUGH THE 10TH
 FLOOR. SEE M107 THE DUCT TURNS LEFT THEN UP AGAIN.
 ONTHE POOL DECK LEVEL IT IS SHOWN ON M107 IN THE R06
 SEERVICE ROOM. ON THE POOL ROOF DECK PLAN A2.11 THE
 DUCT DOES NOT SHOW UP. DISCREPANCY IN PLANS.
  
 IF THERE IS TO BE NO 2 HR SHAFT, THEN A 2 HOUR DUCT
 WRAP WILL BE REQUIRED, PROVIDE THE MANUFACTURERES
 DETAILS, THE OTHER ISSUE IS NOT HAVING FIRE STOPPING
 DETAILS OF THE ASSEMBLY THROUGH THE RATED FLOOR PER
 2010 FBC-B 713.3.1.2. THROUGH-PENETRATION FIRESTOP
 SYSTEMS.
  
 11B-C) COMPLIED.
  
 12) SHEET A2.11:
  
 12A-B) COMPLIED.
  
 12C) DEALS WITH THE STAIRS TO TTHE ELEVATOR EQUIPMENT,
 2010 FBC-B 1009.14. THE RESPONSE INDICATES THE USE OF
 OTIS GEN 2 ELEVATIONS WHICH ARE MACHINELESS EQUIPMENT.
 PLEASE PROVIDE WHERE THE CONTROL PANEL FOR THE ELEVATOR
 IS TO BE LOCATED? IF IN RATED WALLS HOW WILL THE RATING
 BE MAINTAINED? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 12D) COMPLIED.
  
 13) THE PRODUCT APPROVALS HAVE BEEN REQUESTED TO BE
 DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE PROVIDE 3 SETS OF PRODUCT APPROVALS FOR EACH OF
 THE FOLLOWING COMPONENTS AND OR CLADDING.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES & WATERPROOFING FOR
 SLABS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 14)PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15) COMPLIED WIND DESIGN CRITERIA..
  
 16-20) COMPLIED.
  
 20A) PROVISO: PLEASE ALSO NOTE THE 3 RD FLOOR IS TO BE
 DESIGNED FOR A FUTURE RESTARAUNT, BE AWARE OF 1013.2
 WHERE FIXED SEATING MAY BE A HEIGHT FACTOR IN THE GUARD
 RAIL.
  
 21) 2ND REQUEST. SHEET S1 AND S11.1 BOTH INDICATE THE
 USE OF AUGER CAST PILE, PLEASE PROVIDE WHAT AGENCY/
 INSPECTION SERVICE WILL BE RESPONSIBLE FOR THEOBSERVING
 & RECORD KEEPING OF THE AUGER CAST PILE ASWELL AS LOAD
 TESTING TO SECTION 2010 FBC-B 1810.3.3.1.2.
  
 22) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By jwitmer Date 2014-07-24 Time 11:51 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 09:41 Sent To  
Notes
2014-07-16 15:33:32BUILDING PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. JULY 17/ 2014
 ACTION: DENIED
  
 1) THE SURVEY INDICATES THE PROPOSED BUILDING WILL NEED
 EITHER A UNITY OF TITLE OR A REPLAT. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) COMPLIED, 109.3.6.1 SUBMITTED A WRITTEN THRESHOLD
 PLAN.
  
 2B) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2C) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.THE THRESHOLD AGREEMENT FORMS
 MUST BE SIGNED BY ALL INTERESTED PARTIES AND RETURNED
 TO THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE. .
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 OR E-MAIL: [email protected] FOR
 FURTHER INFORMATION.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE REQUIED.
  
 2E) THE CONTRACTOR OF RECORD WILL PRODUCE A JOB SUMMARY
 OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2G) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B SECTION
 3304 SITE WORK:
 3A) 3306.2 WALKWAYS. A WALKWAY SHALL BE PROVIDED FOR
 PEDESTRIAN TRAVEL IN FRONT OF EVERY CONSTRUCTION AND
 DEMOLITION SITE UNLESS THE APPLICABLE GOVERNING
 AUTHORITY AUTHORIZES THE SIDEWALK TO BE FENCED OR
 CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH TO
 ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF) (7.2
 KN/M2).
  
 3B) 3306.5 BARRIERS. BARRIERS SHALL BE A MINIMUM OF 8
 FEET (2438 MM) IN HEIGHT AND SHALL BE PLACED ON THE
 SIDE OF THE WALKWAY NEAREST THE CONSTRUCTION. BARRIERS
 SHALL EXTEND THE ENTIRE LENGTH OF THE CONSTRUCTION
 SITE. OPENINGS IN SUCH BARRIERS SHALL BE PROTECTED BY
 DOORS WHICH ARE NORMALLY KEPT CLOSED.
  
 3C) 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC AND
 PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE DURING
 CONSTRUCTION, REMODELING AND DEMOLITION WORK.
 PROTECTION MUST BE PROVIDED FOR FOOTINGS, FOUNDATIONS,
 PARTY WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. PROVISIONS
 SHALL BE MADE TO CONTROL WATER RUNOFF AND EROSION
 DURING CONSTRUCTION OR DEMOLITION ACTIVITIES. THE
 PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL
 PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
  
 3D) 3305.1 FACILITIES REQUIRED. SANITARY FACILITIES
 SHALL BE PROVIDED DURING CONSTRUCTION, REMODELING OR
 DEMOLITION ACTIVITIES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 3E) F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS.
  
 3F) 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE
 AND THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY
 OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS.
  
 3G) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO
 HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE
 STANDPIPE SHALL BE PROVIDED FOR USE DURING
 CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN
 THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET
 (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 3H) [F] 3312.1 COMPLETION BEFORE OCCUPANCY.
 IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY
 ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE
 AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED
 AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3.
  
 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 5) SHEET S11.1 FOUNDATION NOTE # 1 ARDAMAN & ASSOCIATES
 HAS COMPLETED A SOILS REPORT DATED MAY 14/ 2014. PLEASE
 SUPPLY THE BUILDING DEPARTMENT WITH (3) ORIGINAL SIGNED
 & SEALED REPORTS. 1803.3 BASIS OF INVESTIGATION. SOIL
 CLASSIFICATION SHALL BE BASED ON OBSERVATION AND ANY
 NECESSARY TESTS OF THE MATERIALS DISCLOSED BY BORINGS,
 TEST PITS OR OTHER SUBSURFACE EXPLORATION MADE IN
 APPROPRIATE LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE
 AS NECESSARY TO EVALUATE SLOPE STABILITY, SOIL
 STRENGTH, POSITION AND ADEQUACY OF LOAD-BEARING SOILS,
 THE EFFECT OF MOISTURE VARIATION ON SOIL-BEARING
 CAPACITY, COMPRESSIBILITY, LIQUEFACTION AND
 EXPANSIVENESS.
  
 6) SHEET A0.16:
 6A) MISC. NOTES INDICATE 5 SETS OF SHOP DRAWINGS ARE TO
 BE SUBMITTED. THE CITY WILL REQUIRE 3 SETS SINCE THIS
 IS A THRESHOLD BUILDING BUR WILL NOT STAMP THE OTHER
 SETS.
  
 6B) THE DESIGNER OF RECORD DECLARE ONLY MIAMI-DADE
 NOA'S ARE TO BE SUBMITTED ON THIS PROJECT. WITH THIS
 NOTE ON THE PLANS IF THE CONTRACTOR SUBMITS A FLORIDA
 APPROVAL THEY WIL BE DENIED. NOTE THE DESIGNER OF
 RECORD IS REQUIRED TO REVIEW ALL PRODUCT APPROVALS
 BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6C) CARPENTRY NOTE # 5 PLYWOOD SHEATHING NOTE DOES NOT
 INDICATE THAT SHEATHING BE FIRE RETARDANT TREATED
 PLYWOOD.
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 7) SHEET A1.00 LIFE SAFETY SHEET:
 7A) THE ZONING SHEET A0.01 INDICATES THIS TO BE A 10
 STORY WITH A MEZZANINE LEVEL. ON THIS SHEET THERE IS A
 DEFINITION OF MEZZANINE LEVEL FOR ZONING USE. SHEET
 A1.00 CONSTRUCTION TYPE LIST ALLOWED BUILDING HEIGHT AS
 12 STORIES AND THE ACTUAL HEIGHT BEING BUILT AS A 10
 STORY BUILDING.
 THIS WILL ACTUALLY BE CONSIDRED A 12 STORY BUILDING.
 THE DIFINITION OF MEZZANIE UNDER THE 2010 FBC-B 505.2
 EXCEPTION # 2, THE MEZZANINE IS LIMITED TO 1/2 OF THE
 ROOM SIZE NOT THE FLOOR PLATE, ADDING ONE STORY OF
 FLOOR AND THE ROOFTOP POOL DECK IS THE 12TH FLOOR OR
 LEVEL. SEE 2010 FBC-B 1509.2.3 USE LIMITATION.
 PENTHOUSES OR BULKHEADS USED FOR PURPOSES OTHER THAN
 PERMITTED BY THIS SECTION SHALL CONFORM TO THE
 REQUIREMENTS OF THIS CODE FOR AN ADDITIONAL STORY.
  
 7B) OCCUPANT LOAD TABLES ALL INDICATE FRACTIONS OF
 OCCUPANTS. THE OCCUPANTS FOR EACH ROOM ARE TO BE
 ROUNDED UP, THERE ARE NOT FRACTIONS OF PEOPLE IN THESE
 ROOMS. 2010 FBC-B TABLE 1004.1.1. ALSO SEE BOAF
 INFORMAL INTERPRETATION 5479 TUES. 12/18/2007. WITH
 THIS INCREASE IN OCCUPANTS THIS MAY AFFECT THE PLUMBING
 FIXTURE COUNT.
  
 7C) OCCUPANT LOAD TABLE DOES NOT INCLUDE ETHER THE POOL
 OR POOL DECK LOADS. SEE 2010 FBC-B TABLE 1004.1.1.
  
 7D) THE WALL LEGEND INDICATES THE USE OF A 2 HOUR RATED
 BLOCK PER UL-U905, SHEET A9.02 THIS DETAIL IS NOT
 INCLUDED IN THIS SHEET. 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 2010
 FBC-B 703.2 FIRE RESISTANCE RATINGS.
  
 7E) EMERGENCY POWER NOTES DON'T SHOW COMPLIANCE WITH
 2010 FBC-B [F] 403.4.8.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
 403.4.8.1:
 (3.) EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS;
  
 (4.) AUTOMATIC FIRE DETECTION SYSTEMS;
  
 (5.) FIRE ALARM SYSTEMS; AND
  
 (6.) ELECTRICALLY POWERED FIRE PUMPS.
  
 7F)(1) FIRE PUMP) THE LIFE SAFETY SHEET LEVEL 1 DOES
 NOT INDICATE COMPLIANCE WITH 403.3.2 WATER SUPPLY TO
 REQUIRED FIRE PUMPS.
 7F)(2) 2 REQUIRED MAINS. REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING
 SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER
 MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY
 PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE
 SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE
 PUMPS TO OPERATE.
  
 7G) THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE
 COMPLIANCE WITH [F] 403.4.5 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 7H) THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE
 COMPLIANCE WITH 403.5.5 LUMINOUS EGRESS PATH MARKINGS.
 LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1024. 1024.2 MARKINGS WITHIN
 EXIT ENCLOSURES.
 EGRESS PATH MARKINGS SHALL BE PROVIDED IN EXIT
 ENCLOSURES, INCLUDING VERTICAL EXIT ENCLOSURES AND EXIT
 PASSAGEWAYS, IN ACCORDANCE WITH SECTIONS 1024.2.1
 THROUGH 1024.2.6. 1024.2.1 STEPS. A SOLID AND
 CONTINUOUS STRIPE SHALL BE APPLIED TO THE HORIZONTAL
 LEADING EDGE OF EACH STEP AND SHALL EXTEND FOR THE FULL
 LENGTH OF THE STEP. OUTLINING STRIPES SHALL HAVE A
 MINIMUM HORIZONTAL WIDTH OF 1 INCH (25 MM) AND A
 MAXIMUM WIDTH OF 2 INCHES (51 MM). THE LEADING EDGE OF
 THE STRIPE SHALL BE PLACED AT A MAXIMUM OF 1/2 INCH
 (12.7 MM) FROM THE LEADING EDGE OF THE STEP AND THE
 STRIPE SHALL OVERLAP THE LEADING EDGE OF THE STEP BY
 NOT MORE THAN 1/2 INCH (12.7 MM) DOWN THE VERTICAL FACE
 OF THE STEP.
  
 7I) THE LIFE SAFETY PLANS DO NOT INDICATE THE USE OF
 ANY OF THE DEPICTED ROOMS, OCCUPANT LOADS, OR EXITS,
 FIRE COMMAND ROOM, FIRE PUMP ROOM, ELECTRIC ROOM AND OR
 VAULT, GENERATOR ROOM, ELEVATOR MACHINE ROOM, LAUNDRY &
 TRASH ROOMS, & DOMESTIC WATER PUMP ROOM. THIS IS A
 COMMON COMMENT FOR ALL LIFE SAFETY FLOOR PLANS>
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION :
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FIRE ACCESS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 LOCATION OF GREASE INTERCEPTORS
 OCCUPANCY GROUP
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT SIGNAGE & DIRECTIONALS
 EXIT DISCHARGE
  
 7J) THE EXIT STAIRWAY THAT HAS ITS EXIT DISCHARGE ONTO
 CLEMATIS, ALSO INCORPORATES A VESTIBULE AND A ELEVATOR
 WITHIN THE VESTIBULE. PLEASE SEE 2010 FBC-B
 1022.3ELEVATORS SHALL NOT OPEN INTO EXIT ENCLOSURES.
 THE ARGUEMENT CAN BE MADE THAT THIS AREA IS ONLY BEING
 USED AS A VESTIBULE, 1027.1 EXCEPTION # 2 .4 THE
 VESTIBULE IS ONLY FOR MEANS OF EGRESS AND EXITS
 DIRECTLY TO THE OUTSIDE.
  
 7K) MISSING INFORMATION: [F] 403.4.1 SMOKE DETECTION.
 SMOKE DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 907.2.13.1.
  
 7L) MISSING INFORMATION: [F] 403.4.2 FIRE ALARM SYSTEM.
 A FIRE ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 907.2.13.
  
 7M) [F] 403.4.3 EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 7N) [F] 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. [F]
 915.1 GENERAL. EMERGENCY RESPONDER RADIO COVERAGE SHALL
 BE PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE
 FLORIDA FIRE PREVENTION CODE.
  
  
 7O) 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 909.
  
 7P) MISSING INFORMATION: [F] 403.4.5 FIRE COMMAND. A
 FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 7Q) MISSING INFORMATION: 403.6 ELEVATORS.
 ELEVATOR INSTALLATION AND OPERATION IN HIGH-RISE
 BUILDINGS SHALL COMPLY WITH CHAPTER 30 AND SECTIONS
 403.6.1 AND 403.6.2.
  
 7Q) 403.6.1 FIRE SERVICE ACCESS ELEVATOR.
 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 FEET
 (36 576 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS, A MINIMUM OF ONE FIRE SERVICE ACCESS
 ELEVATOR SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007.
 3007.4 FIRE SERVICE ACCESS ELEVATOR LOBBY.
 THE FIRE SERVICE ACCESS ELEVATOR SHALL OPEN INTO A FIRE
 SERVICE ACCESS ELEVATOR LOBBY IN ACCORDANCE WITH
 SECTIONS 3007.4.1 THROUGH 3007.4.4.
  
 EXCEPTION: WHERE A FIRE SERVICE ACCESS ELEVATOR HAS TWO
 ENTRANCES ONTO A FLOOR, THE SECOND ENTRANCE SHALL BE
 PERMITTED TO OPEN INTO AN ELEVATOR LOBBY IN ACCORDANCE
 WITH SECTION 708.14.1.
  
 3007.4.1 ACCESS.
 THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL HAVE
 DIRECT ACCESS TO AN EXIT ENCLOSURE.
  
 3007.4.2 LOBBY ENCLOSURE.
 THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 ENCLOSED WITH A SMOKE BARRIER HAVING A MINIMUM 1-HOUR
 FIRE-RESISTANCE RATING, EXCEPT THAT LOBBY DOORWAYS
 SHALL COMPLY WITH SECTION 3007.4.3.
  
 EXCEPTION: ENCLOSED FIRE SERVICE ACCESS ELEVATOR
 LOBBIES ARE NOT REQUIRED AT THE STREET FLOOR.
  
 3007.4.3 LOBBY DOORWAYS.
 EACH FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 PROVIDED WITH A DOORWAY THAT IS PROTECTED WITH A
 3/4-HOUR FIRE DOOR ASSEMBLY COMPLYING WITH SECTION
 715.4. THE FIRE DOOR ASSEMBLY SHALL ALSO COMPLY WITH
 THE SMOKE AND DRAFT CONTROL DOOR ASSEMBLY REQUIREMENTS
 OF SECTION 715.4.3.1 WITH THE UL 1784 TEST CONDUCTED
 WITHOUT THE ARTIFICIAL BOTTOM SEAL.
  
 3007.4.4 LOBBY SIZE.
 EACH ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL
 BE A MINIMUM OF 150 SQUARE FEET (14 M2) IN AN AREA WITH
 A MINIMUM DIMENSION OF 8 FEET (2440 MM).
  
 7R) THERE WILL BE NO ADDITIONAL COMMENTS ON THE OTHER
 LIFE SAFETY SHEETS BECAUSE AS LISTED UNDER COMMENT 7I
 PLANS ARE LACKING REQUIRED ELEMENTS FOR MINIMUM
 CRITERIA FOR A COMMERCIAL PLAN REVIEW 107.3.5.1.
  
 8) SHEET A2.00:
 8A) FPL VAULT WILL REQUIRE 3 HR FIRE RATING WALL TAGS
 INDICATE 2 HR. PER 2008 NEC 110.31.A & 3 HR OPENING
 PROTECTIVES 2010 FBC-B 715.4.
  
 8B) FPL VAULT EXTERIOR DOORS HARDWARE SCHEDULE (A)
 ENTRY KEY LOCK & DEAD BOLT. 2010 FBC-B 1008.1.10 PANIC
 & FIRE EXIT HARDWARE REQUIREMENTS, ELECTRICAL ROOMS
 WITH EQUIPMENT RATED 1,200 AMPERES OR MORE AND OVER 6
 FEET (1829 MM) WIDE THAT CONTAIN OVERCURRENT DEVICES,
 SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT OR EXIT
 ACCESS DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE OR
 FIRE EXIT HARDWARE. THE DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL.
  
 8C) FPL VAULT BOLLARDS ON THE EXTERIOR NEEDS TO HAVE
 PROTECTION BOLLARDS TO ENSURE SAFE PASSAGE TO THE
 PUBLIC WAY. 1027.6. NO VEHICLES TO BE ABLE TO PARK OR
 UNLOAD IN FRONT OF THE DOORWAY OBSTRUCTING ACCESS TO
 THE PUBLIC WAY.
  
 8D) STAIRWELL # 2 THE NORTH & EAST WALLS NO WALL TAGS
 PROVIDING FIRE RATING, 2010 FBC-B 1022.1. 2HR FIRE
 RATING.
  
 8E) STAIRWELL # 2 THE EXTERIOR DOOR # 109 NEEDS TO HAVE
 PROTECTION BOLLARDS TO ENSURE SAFE PASSAGE TO THE
 PUBLIC WAY. 1027.6. NO VEHICLES WOULD BE ABLE TO PARK
 OR UNLOAD INFRONT OF THE DOORWAY OBSTRUCTING ACCESS TO
 THE PUBLIC WAY.
  
 8F) ROOM # 101 TRASH ROOM SOUTH WALL THERE IS NO WALL
 IDENTIFICATION TAG. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 8G) ROOM # 103 DIRTY LINENS AND LINEN SHUTE ROOM. LINEN
 CHUTE TERMINIATION DETAILS ARE NOT INCLUDED IN DETAIL
 #1 SHEET A5.12. 708.13.1 REFUSE AND LAUNDRY CHUTE
 ENCLOSURES. OPENINGS INTO THE SHAFT, INCLUDING THOSE
 FROM ACCESS ROOMS AND TERMINATION ROOMS, SHALL BE
 PROTECTED IN ACCORDANCE WITH THIS SECTION AND SECTION
 715.
  
 8H) LINEN CHUTE DETAIL # 1 SHEET A5.12 PLEASE PROVIDE
 COMPLIANCE WITH FIRE SPRINKLER REQUIREMENTS: F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 8I) DOOR 127 & 132 FRONT LOBBY DOORS WILL BE THE DOORS
 USED FROM THE 3RD FLOOR RESTARUART FOR EGRESS PURPOSES
 WILL REQUIRE PANIC HARDWARE,
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
  
 8J) ELEVATOR HOISTWAY WALL TAG "L" INDICATES THE USE OF
 1'-0" OF CONRETE WALLS NOTE WILL NEED CLAFIFICATION OF
 WET AREAS TO USE 3 5/8 INCH STUDS AND DENSEGLASS, IS
 THIS OVER AND ABOVE THE 12 INCH WALL OR INSTEAD OF?
 CLARIFICATION, ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 8K) ELEVATOR PUBLIC AND BACK OF HOUSE SERVICE ELEVATORS
 DETAIL # 2 SHEET A5.12 DOES NOT SHOW A SUMP PIT FOR THE
 ELEVATORS, S1 DOES SHOW SUMP PITS FOR BOTH ELEVATOR
 HOISTWAYS, DISCREPANCY IN PLANS.
  
 8L) STAIRWELL # 3 WEST WALL THERE IS NO WALL
 IDENTIFICATION TAGS 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. 1022.1 EXIT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE AND NOT LESS THAN 1
 HOUR WHERE CONNECTING LESS THAN FOUR STORIES. COMMON
 COMMENT FOR ALL FLOORS.
  
 8M) STAIRWELL # 3 COMMON WALL WITH ELEVATOR SHAFT NO
 WALL IDENTIFICATION TAG. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. 1022.1 EXIT ENCLOSURES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS
 WHERE CONNECTING FOUR STORIES OR MORE AND NOT LESS THAN
 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES.
  
 8N) NOTICE RETAIL SPACE 131 THE MEZZANINE AREA IS TO
 THE MAXIMUM, NO WALLS CAN BE PUT IN UNDER A TENANT
 BUILD OUT, BEWARE OF AREA LIMITATION, SEE SECTION 505.2
 AREA LIMITATION. THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF
 THE FLOOR AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE
 LOCATED. THE ENCLOSED PORTION OF A ROOM SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE FLOOR AREA OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING
 THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE FLOOR AREA OF THE ROOM.
  
 8O) 914.1 SHAFTWAY MARKINGS.
 VERTICAL SHAFTS SHALL BE IDENTIFIED AS REQUIRED BY
 SECTIONS 914.1.1 AND 914.1.2.
  
 8O)(1) [F] 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS.
 OUTSIDE OPENINGS ACCESSIBLE TO THE FIRE DEPARTMENT AND
 THAT OPEN DIRECTLY ON A HOISTWAY OR SHAFTWAY
 COMMUNICATING BETWEEN TWO OR MORE FLOORS IN A BUILDING
 SHALL BE PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED
 LETTERS AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE
 BACKGROUND. SUCH WARNING SIGNS SHALL BE PLACED SO AS TO
 BE READILY DISCERNIBLE FROM THE OUTSIDE OF THE
 BUILDING.
  
 8O)(2) [F] 914.1.2 INTERIOR ACCESS TO SHAFTWAYS.
 DOOR OR WINDOW OPENINGS TO A HOISTWAY OR SHAFTWAY FROM
 THE INTERIOR OF THE BUILDING SHALL BE PLAINLY MARKED
 WITH THE WORD ?SHAFTWAY? IN RED LETTERS AT LEAST 6
 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. SUCH
 WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE.
  
 EXCEPTION: MARKINGS SHALL NOT BE REQUIRED ON SHAFTWAY
 OPENINGS THAT ARE READILY DISCERNIBLE AS OPENINGS ONTO
 A SHAFTWAY BY THE CONSTRUCTION OR ARRANGEMENT.
  
 8O)(3) [F] 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
  
 8P) FIRE PUMP ROOM THE EXTERIOR DOORS 112 WILL ALSO
 NEED BALLARDS TO PROTECT THIS ROOM FOR ACCESS IN
 EMERGENCY SITUATIONS. 913.2 PROTECTION AGAINST
 INTERRUPTION OF SERVICE.
  
 9) SHEET A2.01 MEZZANINE LEVEL/ TRUE 2ND FLOOR:
 9A) MISSING WALL TAGS BETWEEN THE GENERATOR ROOM WALL
 M-10 &M-09. 403.4.7.1.
  
 9B) MISSING WALL TAGS BETWEEN M-01 & M-02. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 9C) MISSING WALL TAGS BETWEEN M-03 & M-04. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 9D) WALL TAGS MISSING BETWEEN M-11 & M15, M-12 & M-16
 AND M-14 & M-16.
  
 9E) WALL TAG MISSING BETWEEN THE ELEVATOR LOBBY &
 RETAIL MEZZANINE.
  
 10) SHEET A2.02 / 2ND FLOOR LEVEL:
 10A) THE GYM WINDOWS IDENTIFICATION TAG AA DOES NOT
 INDICATE A FIRE RATING, THIS BEING A 1 HOUR FIRE RATED
 WALL ASSEMBLY WILL REQUIRE A 3/4 HOUR OPENING
 PROTECTIVE. SEE 2010 FBC-B SECTION 715.5
 FIRE-PROTECTION-RATED GLAZING.
 GLAZING IN FIRE WINDOW ASSEMBLIES SHALL BE
 FIRE-PROTECTION RATED IN ACCORDANCE WITH THIS SECTION
 AND TABLE 715.5. GLAZING IN FIRE DOOR ASSEMBLIES SHALL
 COMPLY WITH SECTION 715.4.7. FIRE-PROTECTION-RATED
 GLAZING SHALL BE TESTED IN ACCORDANCE WITH AND SHALL
 MEET THE ACCEPTANCE CRITERIA OF NFPA 257 OR UL 9.
 FIRE-PROTECTION-RATED GLAZING SHALL ALSO COMPLY WITH
 NFPA 80. OPENINGS IN NONFIRE-RESISTANCE-RATED EXTERIOR
 WALL ASSEMBLIES THAT REQUIRE PROTECTION IN ACCORDANCE
 WITH SECTION 705.3, 705.8, 705.8.5 OR 705.8.6 SHALL
 HAVE A FIRE-PROTECTION RATING OF NOT LESS THAN 3/4
 HOUR.
  
 10B) DOOR 219 LINEN/ LAUNDRY CHUTE ACCESS ROOM DOOR IS
 MISSING SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 715.4.8.3. COMMON
 STATEMENT FOR ALL FLOORS.
  
 11) SHEET A2.03:
 11A) THE PLANS DO NOT DEPICT ANY SHAFTS IN TTHE KITCHEN
 AREA FOR THE FUTURE KITCHEN EXHAUST & HOOD SYSTEM.
 708.2 SHAFT REQUIED.
  
 11B) ELEVATOR LOBBY # 3, IT APPEARS THERE IS A GLASS
 PANEL, NOT IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED. SAFETY GLASS IS REQUIRED.
 2010 FBC-B 2406.4.
  
 11C) AREAS THAT ARE MISSING WALL IDENTIFICATION TAGS,
 RETROOM, COMMON AREAS WITH KITCHEN, FLEX ROOMS WITH
 RATED CORRIDOR, FLEX SPACE & RESTARUANT, WALLS AT DOOR
 313 & DOOR 317 AND STORAGE AREAS 300 & 301. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 12) SHEET A2.11:
 12A) NOTE # 23 INDICATES THE USE OF WOOD TRELLIS,
 PLEASE REVIEW 2010 FBC-B 603.1 ALLOWABLE USES OF
 COMBUSTIBLE MATERIALS.
  
 B) NOTES 21 & 22 DEAL WITH A PERMINATELY AFFIXED ROOF
 LADDER TO ROOF AND NOTE 22 A 24 X 24 INCH ROOF TOP
 SCUTLE HOLE. PLEASE REVIEW BOTH: 1009.13 & 1009.14.
 1009.13 STAIRWAY TO ROOF.
 IN BUILDINGS FOUR OR MORE STORIES ABOVE GRADE PLANE,
 ONE STAIRWAY SHALL EXTEND TO THE ROOF SURFACE, UNLESS
 THE ROOF HAS A SLOPE STEEPER THAN FOUR UNITS VERTICAL
 IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). IN BUILDINGS
 WITHOUT AN OCCUPIED ROOF, ACCESS TO THE ROOF FROM THE
 TOP STORY SHALL BE PERMITTED TO BE BY AN ALTERNATING
 TREAD DEVICE.
  
 1009.14 STAIRWAY TO ELEVATOR EQUIPMENT.
 ROOFS AND PENT-HOUSES CONTAINING ELEVATOR EQUIPMENT
 THAT MUST BE ACCESSED FOR MAINTENANCE ARE REQUIRED TO
 BE ACCESSED BY A STAIRWAY.
  
 1009.13.2 PROTECTION AT ROOF HATCH OPENINGS.
 WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED
 ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF
 EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED
 BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS
 OF SECTION 1013.
  
 13)PLEASE PROVIDE 3 SETS OF PRODUCT APPROVALS FOR EACH
 OF THE FOLLOWING COMPONENTS AND OR CLADDING.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES & WATERPROOFING FOR
 SLABS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 14) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15) SHEET S1 INDICATES THE WIND DESIGN CRITERIA WHICH
 IS CORRECT. SHEET S11.5 INDICATES THE POSITIVE AND
 NEGATIVE PRESSURES FOR THIS BUILDING WHICH ARE EXTREMLY
 LOW, THE 2010 FBC-B GIVE PRESSURES UP TO AND
 MULTIPLIERS TO 60 FT. EVEN AT 60 FT , "C" EXPOSURE THE
 PRESSURES ARE HIGHERE THAN WHAT IS PROPOSED ARE LOW FOR
 10 SQ FT OF ROOF AREA AND WALL AREA. IF A WIND TUNNEL
 TEST WAS COMPLETED PLEASE PROVIDE (3) SETS OF SIGNED &
 SEALED ORIGINALS.
  
 ONCE THE PRESSURES ARE DETERMINED TO BE CODE COMPLIANT,
 THE DESIGNER OF RECORD OR CONTRACTOR CAN REQUEST IN
 WRITING THAT THE PRODUCT APPROVALS BE A DEFERRED
 SUBMITTAL, GIVING THEM TIME TO BID THE PROJECT OUT AND
 ONLY HAVE TO SUBMIT THE ACTUAL PRODUCTS THAT WILL BE
 INSTALLED WITHIN THE BUILDING. 107.3.4.2. DEFERRED
 SUBMITTALS.
  
 16) SHEET A7.01 DETAIL # 2 ENLARGED HANDICAPPED
 BATHROOM WITH A STANDARD ACCESSIBLE SHOWER AND A
 TRANSFER SEAT ON THE BACK WALL. THE PLANS SHOW A 30 X48
 INCH SPACE FOR THE WHEEL CHAIR AS DEPICTED THE PERSON
 IN THE WHEELCHAIR WILL NOT BE ABLE TO MAKE THE
 TRANSFER. THE WHEEL CHAIR IS INFRONT OF THE SEAT.
 TRANSFER TYPE SHOWER COMPARTMENTS NEEDS 12 INCHES
 BEHIND THE SEAT SO THE OCCUPANT OF THE WHEEL CHAIR WILL
 BE ABLE TO TRANSFER ACROSS TO THE SHOWER SEAT. SEE 2010
 FBC-ACCESSIBILITY CODE 608.2.1 AND THE SAME FIGURE.
 SHOWN IN THE PICTURE IS A 3X3 FOOT SHOWER BUT THE
 TRANSFER FROM THE WHEEL CHAIR TO THE SEAT WILL BE THE
 SAME REQUIREMENT.
  
 17) SHEET A7.02:
 17A) THERE WAS A SLIGHT CHANGE IN THE 2010
 FBC-ACCESSIBILITY CODE IN HEIGHT OF GRAB BARS, DEPICTED
 IN THE PLANS IS A MAXIMUM OF 36 INCHES CENTERLINE, THE
 2010 FBC-ACCESSIBILITY CODE NOW MEASURES THE 33-36
 INCHES TO THE TOP OF THE BAR, TOP OF GRIPPING SURFACE.
 609.4.
  
 17B) THE BABY CHANGING TABLE PLEASE PROVIDE THE HEIGHT
 OF THE HANDLE AT TTHE TOP OF THE TABLE. IT APPEARS TO
 BE APPROX. 5'-6" IN HEIGHT?
 SHOW COMPLIANCE WITH REACH RANGES 2010
 FBC-ACCESSIBILITY CODE 308.308.2.1 & 308.3.1.
  
 18) SHEET A8.01 THE TYPICAL SHOWER CURB DETAIL
 INDICATES AN OPTION AS TO CODE COMPLIANCE FOR SHOWER
 PAN MATERIALS 417.5.2.1 - 417.5.2.5.
 2010 ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION...
  
 19A) SHEET A8.02 DETAIL # 1-2 BOTH INDICATE THE USE OF
 PLYWOOD SHEATHING ON LIGHT GAUGE METAL STUDS. PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING. L
  
 19B) SHEET A8.02 SAME DETAILS DOES NOT INDICATE THE
 THICKNESS OF THE PLYWOOD NOR DOES THE PLANS PROVIDE THE
 TYPE OF FASTENER AND SIZE OF FASTENER TO BE USED IN
 SECURINGTHE PLYWOOD TO THE METAL STUDS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 20) SHEET A8.03 DETAIL 1 & 2 TYPICAL BALCONY, SHOWS A
 BALISTER & HANDRAIL SYSTEM HEIGHT OF 42 INCHES FINISH
 NOTE THIS IS A MINIMUM HEIGHT, ONE DETAIL SHOWS THE
 FINISH FLOOR BENEATH THE BOTTOM RAIL AT 42 INCHES THE
 OTHER SHOWS THE BOTTOM RAIL SITTING ON THE ROUGH SLAB
 AT A HEIGHT OF 44". 2010 FBC-B 1013.2 HEIGHT. PLEASE
 PROVIDE WHICH TYPE OF INSTALATION WILL BE USED ON THIS
 PROJECT. DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL
 INFORMATIO IS REQUIED.
 PLEASE ALSO NOTE THE 3 RD FLOOR IS TO BE DESIGNED FOR A
 FUTURE RESTARAUNT, BE AWARE OF 1013.2 WHERE FIXED
 SEATING MAY BE A HEIGHT FACTOR IN THE GUARD RAIL.
  
 21) SHEET S1 AND S11.1 BOTH INDICATE THE USE OF AUGER
 CAST PILE, PLEASE PROVIDE WHAT AGENCY/ INSPECTION
 SERVICE WILL BE RESPONSIBLE FOR THEOBSERVING & RECORD
 KEEPING OF THE AUGER CAST PILE ASWELL AS LOAD TESTING
 TO SECTION 2010 FBC-B 1810.3.3.1.2.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 .

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-03-17 Cont ID  
Sent By albarran Date 2016-03-17 Time 15:42 Rev Time 0.00
Received By albarran Date 2016-03-17 Time 11:41 Sent To  
Notes
2016-03-17 15:45:123RD ELECTRICAL REVIEW NOTES FOR PERMIT 14061217
 REVIEWED FOR COMPLIANCE WITH: 2010 FBC & NEC 2008
  
 BELOW ARE THE COMMENTS RESPONSES TO THE SECOND REVIEW.
 TO SIMPLIFY MATTERS I HAVE USED THE SAME FORMAT OF THE
 PREVIOUS REVIEW AND DELETED ALL THE SATISFACTORILY
 ADDRESSED AND ONLY LEFT THE ONES REQUIRING FURTHER
 ATTENTION. FURTHERMORE, ALL SHOW WINDOW AND SIGN OUTLET
 REQUIREMENTS HAVE BEEN DEFFERED TO THE TENANT
 BUILD-OUT.
  
 PAGE 201
 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE
 REQUIRED IN THE ENTRY HALLWAYS.
 (A) PER FBC-E 505.2.1 EVERY AREA ENCLOSED BY WALLS OR
 FLOOR TO CEILING PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO CONTROL THE LIGHTING WITHIN THE
 SPACE. THIS MEANS SEPARATE LIGHT SWITCHES ARE REQUIRED
 IN THE TOILET AREA, MAIN BATH AREA AND CLOSET.
 FURTHERMORE, FBC-M SECTION 401.3 REQUIRES THAT
 VENTILATION BE PROVIDED WHENEVER THE SPACE IS OCCUPIED
 THEREFORE THE EXHAUST FANS SHALL BE TIED TO THE
 LIGHTING.
 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE
 DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL
 BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) &
 (D).
 (A) RECEPTACLES AS INDICATED ON PLANS DO NOT COMPLY
 WITH THE MINIMUM CODE REQUIREMENTS OF NEC 210.52(A)(1).
 4. THOUGH NEC REQUIRES TAMPER?RESISTANT RECEPTACLES FOR
 DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE
 INSTALLATION OF TAMPER?RESISTANT DEVICES IS A
 SUGGESTION.
 (A) RESPONSE COMPLIANT W/NEC 2008 THOUGH REQUIRED IN
 CURRENT CODE.
  
 PAGE 301
 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS
 ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE
 ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC
 CONTROLS AS PER FBC?E SHALL BE INSTALLED AS REQUIRED.
 (A) RESPONSE ACCEPTED HERE SEE NOTE ABOVE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-09 Cont ID  
Sent By albarran Date 2015-09-09 Time 16:32 Rev Time 0.00
Received By albarran Date 2015-09-09 Time 08:38 Sent To I
Notes
2015-09-09 16:37:15PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 PAGE E101
 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EACH
 ENTRANCE OF A COMMERCIAL BLDG. IN THIS CASE, THERE ARE
 THREE MARKED ON THE PLANS.
 2. NEC 210.62 STATES THAT AT LEAST 1 OUTLET BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EACH 12? OF WINDOW OR PORTION THEREOF.
 3. ADDITIONAL LIGHTING SHALL BE INSTALLED IN STAIR 3.
 SWITCHING TO CODE.
 PAGE 104
 1. SAME AS NUMBER 1 ABOVE. THE S.E. DOOR MAY NOT
 REQUIRE THIS IF IT IS AN INTERIOR DOOR.
 2. THE SAME APPLIES TO ?FLEX SPACE? 1, 2 & 3.
 PAGE 201
 1. PER FBC-ENERGY SECTION 505.2.1.3(3) HOTEL ROOMS
 SHALL HAVE A MASTER SWITCH AT THE ENTRY DOOR TO ALL
 LIGHTING AND SWITCHED OUTLETS IN THE ROOM.
 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE
 REQUIRED IN THE ENTRY HALLWAYS.
 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE
 DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL
 BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) &
 (D).
 4. THOUGH NEC REQUIRES TAMPER-RESISTANT RECEPTACLES FOR
 DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE
 INSTALLATION OF TAMPER-RESISTANT DEVICES IS A
 SUGGESTION.
 5. FBC-907.2.11.1 REQUIRES THAT SINGLE STATION SMOKE
 DETECTORS BE INSTALLED IN EVERY GUEST ROOM.
 PAGE 301
 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS
 ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE
 ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC
 CONTROLS AS PER FBC-E SHALL BE INSTALLED AS REQUIRED.
 2. ACCORDING TO THE RISER DIAGRAM, PANEL IL IS TO BE
 INSIDE THE MAIN ELECTRICAL ROOM, BUT IT IS NOT
 INDICATED ON DETAIL 4 OF THIS PAGE.
 3. THE RISER REFLECT PANEL IL AS A SINGLE UNIT, YET THE
 PANEL SCHEDULE SHEET SHOWS TWO SEPARATE PANELS.
 4. THE RISER DIAGRAM DOES NOT MATCH THE PANEL SCHEDULE
 AS SHOWN ON THE DRAWINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-06 Cont ID  
Sent By dhayes Date 2014-08-06 Time 14:08 Rev Time 0.00
Received By dhayes Date 2014-08-06 Time 13:27 Sent To  
Notes
2014-08-06 14:07:57DATE: 8/6/2014
 PROJECT: CLEMATIS HOTEL
 PERMIT#: 14061217
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PRIMARY PERMIT SUBMITTAL INCLUDES A FLORIDA
 ENERGY EFFICIENCY CODE SUBMITTAL THAT INDICATES
 COMPLIANCE WITH THE FBC FOR ENERGY. HOWEVER, THE PLANS
 DO NOT REFLECT FULL COMPLIANCE. INDICATE FULL
 COMPLIANCE ON THE ELECTRICAL PLANS AS FOLLOWS:
 2) PROVIDE A LIGHTING FIXTURE SCHEDULE, ACCOMPANIED BY
 MANUFACTURER EQUIPMENT SUBMITTALS AND SHOP DRAWINGS ON
 LIGHTING CONTROL AND/OR ENERGY MANAGEMENT SYSTEMS. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 3) SHEET E101
 SEE CODE REFERENCE: FBC-E 505.2 LIGHTING CONTROLS
 (MANDATORY). LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4
 A.) LOBBY AND SERVICE CORRIDORS. INDICATE COMPLIANCE
 WITH FBC-E 505.2.2 AUTOMATIC LIGHTING SHUTOFF.
 B.) ELECTRICAL RM #110, FIRE PUMP RM #112, SHOULD NOT
 HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES
 WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT
 SAFETY OR SECURITY.
 C.) THE PORTE COCHERE LIGHTING DOES NOT INDICATE ANY
 LIGHTING CONTROL FBC-E 505.2.4 EXTERIOR LIGHTING
 CONTROLS REQUIRED.
 D.) POLE LIGHTS AT FRONT ENTRY REQUIRE LIGHTING CONTROL
 AND WIND LOAD CALCULATIONS. FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 E.) AC-R1.1 DOES NOT INDICATE A CIRCUIT OR A
 DISCONNECT. DISCONNECTING MEANS SHALL BE LOCATED WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE
 DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED
 ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING
 EQUIPMENT. NEC 440.14
  
 4) SHEET E 102
 A.) GENERATOR RM #M10 AND THE BOILER RM #M01 SHOULD NOT
 HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES
 WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT
 SAFETY OR SECURITY. 505.2.4
  
 5) SHEET E103 AND SHEET E 201
 SLEEPING ROOMS IN HOTELS REQUIRE LIGHTING CONTROL.
 FBC-E 505.2.1.3 ADDITIONAL CONTROLS. (3)
  
 6) SHEET E 104
 A.) INDICATE COMPLIANCE WITH FBC-E 505.2.2 AUTOMATIC
 LIGHTING SHUTOFF.
 B) INDICATE CIRCUITS FOR EXIT AND EMERGENCY LIGHTING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 7) SHEET E 108
 A.) ADDITIONAL GFI SERVICE OUTLETS ON THE ROOF FOR
 MECHANICAL EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED
 ON THE SAME LEVEL AND WITHIN 25FT OF THE HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. SEE NEC
 210.63, 210.8(A)(3), AND 406.8(B)(1),
  
 8) SHEET E 401
 A.) NOTE 4 INDICATES TO REFER TO PANEL SCHEDULES FOR
 FEEDER SIZE. PANEL MDPAC CALLS FOR 4 RUNS OF 4, 500
 KCMIL AL BUT ALSO CALLS FOR A 400AMP SERVICE RATED MCB
 WITH A CONNECTED LOAD OF 136AMPS PER PHASE.
 CLARIFICATION IS REQUIRED. FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 B.) NOTE 6 INDICATES THE FIRE PUMP IS A 100HP 208V
 3PHASE MOTOR. A 100 HP FIRE PUMP MOTOR REQUIRES A
 MINIMUM 400AMP SERVICE RATED OCPD AND FEEDER. RATE FIRE
 PUMP CONTROLLER AND FEEDERS PER NEC 695. SUBMIT
 MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR AND
 CONTROLER/ATS
 C.) NOTE 13 INDICATES TO FEED THE 100HP FIRE PUMP FROM
 GENERATOR WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR
 REQUIRES A MUCH LARGER FEEDER. REVISE DESIGN FOR CODE
 COMPLIANCE. SEE NEC 310, 430, 695, AND 700
 D.) NOTE 17 INDICATES TO FEED THE 100HP FIRE PUMP FROM
 UTILITY WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR
 REQUIRES A MUCH LARGER FEEDER. THERE IS NO INDICATION
 OF A METER AHEAD OF THIS UTILITY FEEDER. REVISE DESIGN
 FOR CODE COMPLIANCE. SEE NEC 215, 225, 230.2, 310, 430
 AND 695.
 E) NOTE 20 INDICATES THE GENERATOR WILL COMPLY WITH
 NFPA 101 AMONG OTHERS ETC... PLEASE ADD 2008 EDITION OF
 NFPA 70, ARTICLE 700.
 F.) NOTE 22 CALL OUT A GENERATOR BUT DOES NOT IDENTIFY
 THE SIZE AND TYPE. IDENTIFY THE GENERATOR WITH VOLTAGE,
 KVA/KW SIZE ADEQUATELY TO SUPPORT ALL DESIGN LOADS AND
 PROVIDE MANUFACTURER EQUIPMENT SUBMITTALS ON THE
 GENERATOR AND ATS AS SUPPORTING DOCUMENTATION.
 G.) NOTE 39 INDICATES THIS SPACE TO BE THE FPL UTILITY
 VAULT. THE NAME DESIGNATION ABOVE THIS ROOM IS
 GENERATOR ROOM. CLARIFICATION IS REQUIRED. FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
 H.) PANEL 1L INDICATES IT IS TO BE FED FROM PANEL
 MDPAC. THERE IS NO LOAD INDICATED IN PANEL MDPAC ON
 SHEET E 501. I BELIEVE THE INTENT WAS TO INDICATE THE
 FEED FROM PANEL MDPA HOWEVER THERE IS NO LOAD INDICATED
 IN PANEL MDPA EITHER. THEREFORE THERE HAS BEEN NO LOAD
 CALCULATED.
 I.) THE RISER DIAGRAM INDICATES TO REFERENCE THE PANEL
 SCHEDULE FOR FEEDER SIZES. WHEN I REFERENCE PANEL MDPA
 OR MDPAC FOR FEEDER SIZES FOR PANELS 2L, 3L, 4L ETC...
 OR PANEL 2AC, 3AC, 4AC, ETC... THE NOTE IS THE SAME. TO
 REFERENCE THE PANEL SCHEDULE FOR FEEDER. THERE ARE NO
 PANEL SCHEDULES ON ANY OF THE E SHEETS FOR ANY OF THE
 FLOOR PANELS 2L, 3L,4L ETC..., 2AC, 3AC, 4AC, ETC...,
 2R,3R, PROVIDE ALL PANEL SCHEDULES, LOADS AND FEEDERS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 J.) LOAD CALCULATIONS ARE REQUIRED FOR THE BUILDING
 ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE 220. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 K.) IDENTIFY ALL SERVICE METERS AND MAINS. NEC 225.37
 IDENTIFICATION.
 L.) INDICATE THE REQUIRED SIGNAGE INSIDE AND OUTSIDE
 THE BUILDING AS REQUIRED TO IDENTIFY THE GENERATOR AS
 AN ALTERNATE SOURCE OF POWER. NEC 700.8 NEC 225.37
 IDENTIFICATION.
 M.) PROVIDE MANUFACTURER EQUIPMENT PRODUCT SUBMITTALS
 FOR THE GENERATOR, ATS AND RELATED EQUIPMENT. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 N) PROVIDE AND INDICATE THE TESTING AND MAINTENANCE
 REQUIRED PER NEC 700
 O.) THERE IS A RUN IDENTIFIED AS 2, 4? EC (EMPTY
 CONDUITS) FROM AN UNIDENTIFIED SOURCE NEXT TO
 UNIDENTIFIED FPL UTILITY METER? THIS APPEARS TO
 REPRESENT A FUTURE METER FOR A FUTURE TENANT IN WHAT IS
 IDENTIFIED AS A FUTURE RETAIL SPACE. CLARIFICATION IS
 REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND MAXIMUM
 NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF
 DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS.
 P.) PANEL K IS INDICATED ON THE THIRD LEVEL. THERE IS
 NO MAIN INDICATED IN FRONT OF OR GROUPED WITH THE REST
 OF THE MAINS IN THE MAIN ELECTRICAL ROOM. CLARIFICATION
 IS REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND
 MAXIMUM NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF
 DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS.
  
 9) SHEET E 502
 A.) PANEL RAC IS IDENTIFIED AS A 1200AMP MLO PANEL WITH
 A 110AMP SUPPOSED LOAD FED WITH ONE SET OF 4, 250KCMIL
 AL W,1#4AL GRND FROM AN UNIDENTIFIED MAIN IN THE MAIN
 ELECTRICAL ROOM. IDENTIFY THE MAIN AS MAIN #? OF 6?
 IDENTIFY ALL SERVICE METERS AND MAINS.
  
 10) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION
 FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: GENERATOR,
 FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK,
 STRUCTURED CABLING, AUDIO/VIDEO, LIGHTNING PROTECTION
 AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT /WP-CONTENT/UPLOADS/SITES/33
 /2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2016-06-14 Cont ID  
Sent By Mgonzale Date 2016-06-14 Time   Rev Time 1.00
Received By mgonzale Date 2016-06-14 Time   Sent To Z
Notes
2016-06-14 15:41:50PLEASE SUBMIT APPLICATIONS FOR A DEVELOPMENT PERMIT
 AND RIGHT-OF-WAY PERMIT FROM THE ENGINEERING
 DEPARTMENT. APPLICATION FORMS CAN BE FOUND AT
 HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
 (SECTIONS 2-421 AND 78-432, CODE OF ORDINANCES)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-05-22 Cont ID  
Sent By cranford Date 2015-05-22 Time 14:55 Rev Time 0.00
Received By cranford Date 2015-05-22 Time 11:08 Sent To  
Notes
2015-05-22 14:54:541. PLEASE ADDRESS OUT PREVIOUS COMMENTS FROM THE 2014
 REVIEW.
  
 2. GREASE TRAPS ARE PROPOSED WITHIN THE BUILDING, IN
 THE SAME SPACE INTENDED FOR THE TRASH DUMPSTERS /
 COMPACTORS. PLEASE VERIFY THAT THE PROPOSED SIZE AND
 QUANTITY OF TRASH BINS IS APPROPRIATE FOR THE WASTE
 YARDAGE ANTICIPATED TO BE GENERATED BY THE COMPLEX.
 DEMONSTRATE THAT THE NEEDED DUMPSTER(S) WILL FIT WITHIN
 THE PROPOSED BUILDING. CONSIDER USING A COMPACTOR TO
 REDUCE THE YARDAGE OF WASTE THAT WILL NEED TO BE
 COLLECTED. (SHEET P101)
  
 3. PLEASE DEMONSTRATE THAT THE PROPOSAL TO ROLL THE
 TRASH BINS INTO THE ALLEY WILL NOT IMPEDE TRAFFIC FLOW
 WHILE THE BINS ARE IN THE ALLEY OR COMPLETELY BLOCK
 TRAFFIC WHEN THE SOLID WASTE TRUCKS ARE COLLECTING THE
 GARBAGE.
  
 4. PLEASE CONNECT THE FIRE RISER DRAIN TO THE SANITARY
 SYSTEM RATHER THAN THE STORMWATER SYSTEM. PER NFPA
 STANDARDS: THE DRAIN SHOULD BE PIPED TO A SUMP, WHICH
 IN TURN SHOULD DISCHARGE BY GRAVITY OR BE PUMPED TO A
 WASTE WATER DRAIN OR SEWER. (SHEET FS 201)
  
 5. PLEASE DISCUSS THE PROPOSED SANITARY CONNECTION
 LOCATION WITH PUBLIC WORKS STAFF. THE CITY IS IN THE
 PROCESS OF ABANDONING UTILITIES WITHIN ALLEYS DUE TO
 THEIR AGE AND DIFFICULTY PERFORMING MAINTENANCE AND
 REPAIR ACTIVITIES. THE SANITARY CONNECTION MAY NEED TO
 BE RELOCATED TO THE MAIN LINE ALONG DIXIE.
  
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By cranford Date 2014-07-30 Time 13:03 Rev Time 5.00
Received By cranford Date 2014-07-30 Time 13:00 Sent To M
Notes
2014-07-30 13:03:28ENGINEERING/PUBLIC WORKS DEPT COMMENTS
  
 1. PLEASE SUBMIT APPLICATIONS FOR A DEVELOPMENT PERMIT
 AND RIGHT-OF-WAY PERMIT FROM THE ENGINEERING
 DEPARTMENT. APPLICATION FORMS CAN BE FOUND AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
 (SECTIONS 2-421 AND 78-432, CODE OF ORDINANCES)
  
 2. PLEASE SHOW THE SIGHT TRIANGLES ON THE GROUND FLOOR
 LANDSCAPING PLAN FOR THE INTERSECTIONS AND VEHICULAR
 EXITS. (SECTION 94-305E, CODE OF ORDINANCES)
  
 3. DIXIE IS A ONE-WAY ROAD (SOUTH BOUND ONLY) IN FRONT
 OF THE PROPOSED ENTRANCE. PLEASE SHOW THE SIGNAGE
 PROPOSED TO CONVEY THE TRAFFIC PATTERN TO HOTEL GUESTS
 USING THE ENTRANCE DRIVE. PLEASE SUBMIT AN UPDATED
 TRAFFIC CIRCULATION PLAN WITH TRAFFIC MOVING IN THE
 CORRECT DIRECTION AND USING APPROPRIATE TURNING
 TEMPLATES.
  
 4. PLEASE SHOW THE LOADING SPACE (TO REPLACE THE
 LOADING DOCK INCLUDED IN THE APPROVED SITE PLAN FOR
 PROJECT Z11120014) AND THE LOCATION OF EMERGENCY
 VEHICLE PARKING/STAGING AREA(S).
  
 5. PLEASE SHOW THE LOCATIONS OF THE ROOF DRAINS.
 CALCULATIONS WILL NEED TO BE PROVIDED AS PART OF THE
 ENGINEERING DEPARTMENT DEVELOPMENT PERMIT APPLICATION.
 IS THE ALLEY PROPOSED TO BE REPAVED WITH ASPHALT OR
 WITH PAVERS? PLAN SHEET C-05 SHOWS THE ALLEY AS
 PROPOSED ASPHALT WHILE DETAIL C-C INDICATES SIDEWALK
 PAVERS.
  
 6. PLEASE CLARIFY WHICH VERTICAL DATUM HAS BEEN USED
 FOR THE PLANS. THE SUBMITTED SURVEY AND ARCHITECTURAL
 PLANS REFERENCE NGVD 29 IN NOTE 6 WHILE THE CIVIL PLANS
 REFERENCE NAVD 1988.
  
 7. CONDITIONS OF FORMAL SITE PLAN APPROVA ( Z11120014)L
 MUST BE MET PRIOR TO BUILDING PLAN APPROVAL INCLUDING
 OBTAINING A UNITY OF TITLE. THE APPLICATION FORM FOR
 THE UNITY OF TITLE CAN BE FOUND AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 KELLY E CRANFORD, PE
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC SERVICES
 CITY OF WEST PALM BEACH
 (561)494-1098
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-11 Time 16:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-04 Cont ID  
Sent By pleduc Date 2015-09-04 Time   Rev Time 0.00
Received By pleduc Date 2015-09-03 Time 12:41 Sent To  
Notes
2015-09-03 14:16:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) COMMAND ROOM
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 5. A WORK TABLE.
 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 13. FIRE PUMP STATUS INDICATORS
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 16. CONTROLS REQUIRED FOR SMOKE CONTROL
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 2) RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM
 FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE
 RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-05-11 Cont ID  
Sent By pleduc Date 2015-05-11 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 16:39 Sent To  
Notes
2015-05-11 12:15:51THIS 2ND PLAN REVIEW WAS FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A1.00 ADD AND EXIT SIGN AT DOOR # 108 FROM THE
 LOBBY AREA. A REMOTE EXIT FROM THE FRONT LOBBY DOORS IS
 REQUIRED. CHANGE EXIT SIGNS TO THE OPPISITE SIDE OF
 DOORS # 107.1 SHOWN ON E 101.
  
 2) SHEET A 2.03 DOOR # 325 THE DOOR SWING IS REQUIRED
 TO SWING IN THE DIRECTION OF EXIT TRAVEL. SHOW DOORS
 SWINING IN OPPOSITE DIRECTION.
  
 3) SHEET E 104 EXIT SIGNS UNDER THE CENTER TERRACE AREA
 NEED TO BE TURNED IN THE OPPISTE DIRECTION LEADING
 PEOPLE TO THE STAIR, NOT AWAY FROM IT.
  
 4) SHEET E 107, REQUIRED TO ADD AN EXIT SIGN, MOUNTED
 ON THE CORNER WALL, SENDING PEOPLE FROM THE BATHROOM
 AND SUNDECK AREA THRU THE SEATING AREA.
  
 5) SHEET A 1.11 EXIT STAIR 1 EXIT LOAD CALCULATION
 SHOWS 388 PERSON/3 STAIRS 130 PERSONS. THERE ARE ONLY 2
 STAIRS FROM THIS AREA. PLEASE CORRECT.
  
 6) SHEET E 104, DOORS # 311 - 311.1 SHOWS A DIFFERENT
 SWING THAN WHAT IS SHOWN ON A 1.03 AND A 2.03. PLEASE
 CORRECT
 SHEET A 1.03, REQUIRED TO HAVE A 2ND EXIT FROM
 RESTURANT AREA REMOTE FROM THE CENTER STAIR EXIT. THE
 EXIT DOOR NEEDS TO SWING IN THE DIRECTION OF TRAVEL.
 PLEASE CORRECT.
  
 7) SHEET FA 301 PROVIDE A NOTE INDICATING VOICE/ALARM
 COMMUNICATION SYSTEM PER NFPA 1 13.7.2.27.2.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By pleduc Date 2014-07-10 Time   Rev Time 0.00
Received By pleduc Date 2014-07-03 Time 11:15 Sent To  
Notes
2014-07-09 15:31:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2. PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 3. PROVIDE A DRAWING NOTES TO THE FUEL SUPPLY OF THE
 GENERATOR AND BOILER.
  
 4. PROVIDE A DRAWING NOTE FOR PROVIDING AN EXTERIOR KEY
 SAFE TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY
 INTO THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE
 CAN BE ORDERED FROM WWW.KNOXBOX.COM
  
 5. PROVIDE A DRAWING NOTE FOR TACTILE SIGNAGE AT ALL
 REQUIRED EXIT DOORS WITH EXIT SIGNS.
  
 6. PROVIDE A DRAWING NOTE FOR STAIRWAY IDENTIFICATION:
 NEW ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND
 EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES
 SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 7. SHEET A 1.01 & A 2.01 RETAIL MEZZANINE M22 SHALL NOT
 BE OCCUPIED UNTIL THE 2ND MEANS OF EGRESS IS PROVIDED
 FOR AND APPROVED.
  
 8. CLARIFICATION AND CONSISTENCY IS REQUIRED REGARDING
 ELEVATOR LOBBY DOOR RATINGS:
 SHEET A 2.01 DOOR M21 IS RATED AND APPROVED.
 SHEET A 2.03 DOOR 326 IS NOT RATED.
 SHEET A 2.11 DOORS PD 10 & 10.1 ARE NOT RATED.
 SOME DOORS ARE LABLED CORRIDOR DOORS ON THE DOOR
 SCHEDULE, SOME ARE LABELD ELEVATOR LOBBY DOORS. PLEASE
 PROVIDE JUSTIFICATION. IT IS IMPERATIVE THAT EACH DOOR
 ASSOCIATED WITH
 AN ELEVATOR LOBBY ARE RATED AND INSTALLED CONSISTENTLY
 TO ENSURE EQUAL LIFE SAFETY IN THE SAME SPACES.
  
 9. PROVIDE FOR CO MONITORING IN THE GENERATOR AND
 BOILER ROOMS.
  
 10. SHEETS A 2.00, A 2.01, M101 & M102, DO NOT SHOW A
 VENTILATION SYSTEM IN THE PORTE COCHERE, DROP OFF
 AREAS. IT IS IMPERATIVE THAT THESE AREAS HAVE
 VENTIALTION PROVIDED FOR TO REMOVE ANY BUILDUP OF
 VEHICULAR GASES, CO.
  
 11. SHEET FA 101 CO MONITORS ARE NEEDED FOR THE PORTE
 COCHERE, DROP OFF AREAS. SLEEPING ROOMS ARE DIRECTLY
 ABOVE THIS AREA AND IT IS IMPERATIVE THAT A PROTECTION
 SYSTEM IS PROVIDED TO REDUCE AND/OR ELIMINATE VEHICULAR
 GASES.
  
 12. SHEET E 103 - ADD EXIT SIGN IN MAIN CORRIDOR
 POINTING DOWN CORRIDOR 236 TO STAIR NO. 1, 235.
  
 13. SHEET E 104 - ADD EXIT SIGN IN HALLWAY OF EXTERIOR
 TERRACE 327, LEADING TO STAIR NO. 3, 312.
 - ADD EXIT SIGN OUTSIDE SOTH ELEVATOR LOBBY DOOR
 LEADING TO STAIR NO. 1, 371.
  
 14. SHEET E 106 - ADD EXIT SIGN AT SOUTH CORRIDOR
 DIVIDER HEADER LEADING TO STAIR NO. 1, 518. ( COPY THIS
 EXIT SIGN AS PROVIDED FOR SAME LOCATION ON SHEET E 105)
 - ADD EXIT SIGN AT NORTH CORRIDOR HEADER LEADING TO
 STAIR NO. 2, 513. ( COPY THIS EXIT SIGN AS PROVIDED FOR
 SAME LOCATION ON SHEET E 105)
  
 15. SHEET 107 - REMOVE EXIT SIGN IN ELEVATOR LOBBY
 PD10, SOUTH DOOR LOCATION (NO EXIT) AND ADD EXIT SIGN
 ON SUN DECK PD17, SIDE OF DOOR.
 - ADD EXIT SIGN INSIDE ELEVATOR LOBBY PD10, AT NORTH
 SIDE DOOR.
 - ADD EXIT SIGN AT NORTH SIDE OF SEATING PD12, LEADING
 TO POOL DECK AREA.
 - ADD EXIT SIGN AT NORTH SIDE OF SUN DECK PD17 AT THE
 SEATING AREA LEADING THROUGH SEATING AREA TO POOL DECK.
 - ADD EXIT SIGN AT NORTH SIDE OF POOL DECK PD02,
 LEADING TO NORTH EXIT STAIR PD01. EXIT SIGN SHALL BE
 VISABLE FROM SOUTH POOL DECK AREA.
 - ADD EXIT SIGN AT SOTH SIDE OF POOL DECK LEADING TO
 NORTH EXIT STAIR PD07. EXIT SIGN SHALL BE VISABLE FROM
 NORTH SIDE OF POOL DECK AREA.
  
 16. NO UPPER ROOF ACCESS/EGRESS IS NOTED OR READILY
 IDENTIFIABLE. PLEASE PROVIDE FOR ACCESS/EGRESS.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-04-10 Cont ID  
Sent By tklarge Date 2016-04-10 Time 09:28 Rev Time 0.00
Received By tklarge Date 2016-04-10 Time 09:25 Sent To  
Notes
2016-04-10 08:44:36GAS REVIEW
  
 1) SUBMIT THE SPECIFICATIONS/INSTALL MANUALS FOR POWER
 VENTS FOR THE GAS WATER HEATERS.FBC 107.1.
 2) SHT. P 402 - SUBMIT AN EXPLANATION AS TO HOW THE
 CALCULATIONS FOR THE COMBUSTION AIR FOR THE GA WATER
 HEATERS WAS DONE.THERE IS A REFERENCE TO SEC. 706 OF
 THE FBC-MECHANICAL CODE. THIS CODE SECTION SPECIFICALLY
 STATES THAT THE CODE SECTION DOES NOT APPLY TO DIRECT
 VENT APPLIANCES. SEC. 304.1 OF THE FBC- FUEL GAS STATES
 THAT DIRECT VENT APPLIANCES SHALL BE PROVIDED WITH
 COMBUSTION, VENTILATION AND DILUTION AIR IN ACCORDANCE
 WITH THE APPLIANCE MANUFACTURER'S INSTRUCTIONS. SUBMIT
 A COPY OF THE INSTALL DOCUMENT FOR REVIEW.
 3) IDENTIFY THE GAS VENTS ON THE ROOF PLAN ( IF THAT'S
 WHERE THEY WILL TERMINATE).
 4) SUBMIT A DETAIL SHOWING THE TERMINATION POINT OF THE
 GAS VENTS, HEIGHT ABOVE ROOF, ETC.FGC SECS. 502 THRU
 505.
 5) SHT. P 301 - THE LENGTH OF THE GAS LINE IS SHOWN AS
 150 FT.AND ON SHT. P 310 IT IS SHOWN AS 81 FT. CLARIFY.
 6) SHT.P 310 - SEDIMENT TRAPS ARE REQUIRED ON THE WATER
 HEATER GAS PIPING TO EACH GAS HEATER. 2010 FGC
 SEC.408.4.
 7) SHT. P 310 SHOWS THE BTU LOAD OF THE GAS SYSTEM AS
 1,200,000 BTU'S AND SHT. P 402 , GAS WATER HEATER
 SCHEDULE SHOWS THE LOAD AS 500,000 BTU'S EACH. CLARIFY.
 8) SHT.P 310 - PROVIDE A DETAIL AS TO HOW THE GAS
 PIPING IS ENTERING THE STRUCTURE. THE PLANS ARE VAGUE.
 GAS PIPING SHALL NOT PENETRATE THE BUILDING FOUNDATION
 WALLS AT ANY POINT BELOW GRADE. SCHEDULE 40 METALLIC
 PIPE IS NOT PERMITTED BELOW GROUND UNLESS PROTECTED IN
 ACORDANCE WITH SECS.404.9 THROUGH 404.9.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-06-13 Cont ID  
Sent By tklarge Date 2015-06-13 Time 08:28 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 08:28 Sent To  
Notes
2015-06-13 08:29:58SEE PLAN REVIEW COMMENTS FOR GAS UNDER THE PLUMBING
 PLAN REVIEW COMMENTS .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-07-27 Cont ID  
Sent By jwitmer Date 2014-07-27 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2014-07-27 Time 08:30 Sent To  
Notes
2014-07-27 08:51:15GAS PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JULY 27/ 2014
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTICE TO THE DESIGNER OF RECORD:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE TO THE DESIGNER FOR PLAN REVIEW, IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS
 SYSTEM. THE PLANS SHOW THE NATURAL GAS SYSTEM INTRERING
 THE BUILDING WITHIN THE FPL VAULT. PLEASE CHECK WITH
 FPL, I DO NOT BELIEVE THEY WANT ANY OTHER UTILITES
 SHARING THEIR VAULT SPACE EXSPECIALLY A 2LB NATURAL GAS
 SYSTEM.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, 101.3 THE PURPOSE OF THIS CODE IS TO
 ESTABLISH THE MINIMUM REQUIREMENTS TO SAFEGUARD THE
 PUBLIC HEALTH, SAFETY AND GENERAL WELFARE THROUGH
 STRUCTURAL STRENGTH, MEANS OF EGRESS FACILITIES,
 STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION,
 ENERGY CONSERVATION, AND SAFETY TO LIFE AND PROPERTY
 FROM FIRE AND OTHER HAZARDS ATTRIBUTED TO THE BUILT
 ENVIRONMENT AND TO PROVIDE SAFETY TO FIRE FIGHTERS,
 CODE OFFICIALS, AND EMERGENCY RESPONDERS DURING
 EMERGENCY OPERATIONS.
  
 2) A SEPERATE GAS PERMIT WILL NEED TO BE APPLIED FOR,
 THE FUEL GAS REVIEW CAN TAKE PLACE UNDER THE PRIME
 (MASTER) PERMIT OR THE GAS CAN BE TAKEN OUT TOTALLY AND
 REVIEWED INDEPENDENTLY AS A SEPERATE PERMIT.
  
 3) THERE ARE NO GAS PLANS, THE PLANS SUBMITTED DO NOT
 INDICATE WHAT TYPE OF FUEL THE FIRE PUMP AND GENERATOR
 ARE TO RUN ON PLEASE REVIEW THE MINIMUM PLAN REVIEW
 CRITERIA FOR A COMMERCIAL GAS PLAN REVIEW:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3.3. TYPE OF GAS, (LP OR NATURAL).
  
 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 3.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 3.10 2010 FBC-B 916.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES IN THE NEW BUILDING OR
 ADDITION, OR AT SUCH OTHER LOCATIONS AS REQUIRED BY
 THIS CODE.
  
 916.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION 916.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
  
 1. A HARD-WIRED CARBON MONOXIDE ALARM.
  
 2. A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 916.1.2 COMBINATION ALARMS.
 COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-23 Cont ID  
Sent By cpuell Date 2016-06-23 Time 08:40 Rev Time 0.00
Received By cpuell Date 2016-03-07 Time 10:16 Sent To  
Notes
2016-06-22 16:40:14TO C.PUELL
2016-03-08 10:16:25C27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-09 Cont ID  
Sent By cpuell Date 2015-09-09 Time 16:39 Rev Time 0.00
Received By albarran Date 2015-04-21 Time 13:48 Sent To  
Notes
2015-09-09 16:40:369/9/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "TBD". MA
2015-04-22 13:49:20RE-SUBMITTAL SENT TO C33 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By skennedy Date 2014-09-03 Time 07:28 Rev Time 0.00
Received By skennedy Date 2014-06-26 Time 10:30 Sent To  
Notes
2014-07-01 10:30:43SENT TO C33 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2016-03-22 Time 10:01 Sent To  
Notes
2016-03-24 09:33:42BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-05-19 Cont ID  
Sent By jwitmer Date 2015-05-19 Time 05:56 Rev Time 0.00
Received By jwitmer Date 2015-05-19 Time 05:56 Sent To  
Notes
2015-05-19 05:56:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-27 Cont ID  
Sent By jwitmer Date 2014-07-27 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2014-07-27 Time 07:09 Sent To  
Notes
2014-07-27 07:10:07BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-24 Cont ID  
Sent By ccole Date 2016-03-24 Time 17:29 Rev Time 0.00
Received By ccole Date 2016-03-23 Time 17:28 Sent To  
Notes
2016-03-24 17:30:223RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #14061217
 3/24/16
  
 1) THE REQUESTED RATIONAL ANALYSIS FOR THE SMOKE
 CONTROL SYSTEM WAS NOT SUBMITTED- REFER TO SECTION
 513.4 FBC-10 MECHANICAL. THE REVISED PLANS ARE NOT
 PROVIDING SUFFICIENT INFORMATION TO VERIFY THE SYSTEM
 IS COMPLIANT WITH THE CODES. THE DESIGN PROFESSIONAL
 SHALL SUBMIT A NARRATIVE THAT CLEARLY DEMONSTRATES THE
 SYSTEM DESIGN, AND ALL EQUIPMENT AND COMPONENTS
 SPECIFIED ARE IN COMPLIANCE WITH SECTIONS 513.4.1-
 513.4.6 FBC-10 MECHANICAL. PLEASE NOTE THAT ALL
 SUBMITTALS FOR EQUIPMENT AND COMPONENTS OF THE SMOKE
 CONTROL SYSTEM- FANS, DUCTWORK, FIRE ALARM DEVICES AND
 CONTROLS, FIRE/SMOKE DAMPERS, GENERATOR, MOTORIZED AND
 BAROMETRIC DAMPERS ETC. SHALL BEAR THE DESIGN
 PROFESSIONAL OF RECORD'S SIGNATURE OF APPROVAL.
  
 2) SHEET M602: BUILDING PRESSURIZATION- CONTROL
 SEQUENCE: TWO DIFFERENT EMERGENCY OPERATION PROCEDURES
 ARE SHOWN DEPENDING ON HOW THE FIRE ALARM IS ACTIVATED-
 BY FLOW SWITCH, OR BY SMOKE DETECTORS. IN THE FIRST
 SEQUENCE (FLOW SWITCH) THE FSD'S ARE TO REMAIN OPEN ON
 THE FIRE FLOOR PRESSURIZING BOTH THE CORRIDORS AND THE
 GUEST ROOMS, BUT IN THE SECOND SEQUENCE (SMOKE
 DETECTORS), THE CONTROL SEQUENCE INDICATES THAT ALL
 FSD'S ON FIRE FLOOR WILL CLOSE TO PREVENT SMOKE
 MIGRATION INTO THE GUESTROOMS. THERE APPEARS TO BE A
 CONFLICT HERE, AND THE STATEMENT IS CONFUSING BECAUSE
 FSD'S ARE SHOWN FOR BOTH RTU-1 (GUEST ROOMS) AND RTU-2
 (CORRIDORS) AT THE RATED SHAFTS ON EACH FLOOR
 (M103-M201). ARE WE TALKING ABOUT JUST CLOSING THE FSD
 FOR RTU-1 OR RTU-2 AS WELL WHICH WOULD BE MORE TYPICAL?
 ADDITIONALLY, PLEASE CLARIFY WHY FIRE DAMPERS (FD'S)
 ARE INDICATED AT THE O/A DUCT PENETRATIONS INTO THE
 GUESTROOMS. WOULD THESE NOT BE REDUNDANT IF THERE IS AN
 FSD AT THE SHAFT? PLEASE NOTE THAT IF THESE DAMPERS ARE
 TO BE PART OF THE SMOKE CONTROL SYSTEM THEN THEY SHALL
 BE CHANGED TO FSD'S IN ACCORDANCE WITH SECTIONS 715.4.3
 & 715.4.3.1 FBC-10 BUILDING. PLEASE CLARIFY HOW SMOKE
 WOULD BE REMOVED FROM THE FLOOR OF FIRE ORIGIN USING
 THIS DESIGN. WOULD THE SYSTEM FUNCTION MORE EFFECTIVELY
 IF SMOKE EVACUATION ON THE FLOOR OF ORIGIN WAS
 INCLUDED?
  
 3) IT APPEARS THAT THE REVISED PLANS AND CALCULATIONS
 ARE NOT CONSISTENT WITH THE NARRATIVE SUBMITTED BY CLAD
 WHICH INDICATES THAT ALL PREVIOUS COMMENTS HAVE BEEN
 ADDRESSED AND PLANS HAVE BEEN CORRECTED. THOSE COMMENTS
 FROM THE 2ND REVIEW ARE ITEMIZED BELOW ALONG WITH SOME
 ADDITIONAL COMPLIANCE NOTES.
  
 COMMENT #1: A) CALCULATIONS FOR ZONES #4 & 5A WERE NOT
 SUBMITTED. B) ZONE #7 CALCULATIONS APPEAR TO BE FOR THE
 FLEX SPACES ONLY AND DO NOT INCLUDE THE TOILET,
 JANITOR, AND STORAGE ROOMS SERVICED BY AC R1. C)
 CALCULATIONS FOR THE HOTEL ROOMS ON ALL FLOORS NOT
 SUBMITTED.
  
 COMMENT #2: THE ENERGY CALCULATIONS HAVE NOT BEEN
 CORRECTED OR REVISED AS INDICATED IN THE NARRATIVE: THE
 ORIGINAL FORM HAS BEEN RE-SUBMITTED. PLEASE CORRECT THE
 CALCULATIONS SO THE DATA FOR THE SYSTEMS MATCHES THE
 SYSTEMS SPECIFIED ON THE PLANS AND EQUIPMENT SCHEDULES.
  
 COMMENT #3: SHEETS M101, M102, & M103: CORRIDORS SHALL
 NOT SERVE AS RETURN AIR DUCTS.
  
 COMMENT #4: M101: FIRE DAMPERS ARE STILL NOT SHOWN AT
 DUCT PENETRATIONS OF THE SECURITY/HR & OFFICE/VALET
 COMMON WALLS.
  
 COMMENT #5, M101: REQUIRED TRASH ROOM EXHAUST SYSTEM
 NOT ADDED TO THE PLANS.
  
 **ADVISORY** PLEASE REVIEW SECTION 501.2.1 FOR LOCATION
 OF, AND REQUIRED CLEARANCE DISTANCES FOR THE TRASH ROOM
 EXHAUST OUTLET, AND ALL OTHER EXHAUST OUTLETS ON THE
 EXTERIOR WALLS AND ROOFS OF THE BUILDING- PROVIDE
 DETAILS AND NOTES TO VERIFY COMPLIANCE. ADDITIONALLY,
 SEE SECTION 401.4 FOR ALL AIR INTAKE LOCATIONS AND
 CLEARANCE DISTANCES AT EXTERIOR WALLS AND ROOFS-
 PROVIDE DETAILS AND NOTES TO VERIFY COMPLIANCE.
  
 COMMENT #6, M102: SEE ADVISORY NOTE ABOVE IN REGARD TO
 THE EXHAUST OUTLETS AND AIR INTAKES ON THE EXTERIOR
 WALLS OF THE GENERATOR, FIRE PUMP, AND BOILER ROOMS. A)
 PROVIDE MAKE-UP AIR FOR THE BOILER AND FIRE PUMP ROOM
 EXHAUST SYSTEMS. B) PROVIDE VENT PIPING DETAILS FOR THE
 GENERATOR INCLUDING TYPE AND SIZE OF VENT PIPE AND
 TERMINATION LOCATION. C) CLARIFY IF A FUEL TANK WILL BE
 LOCATED IN THE GENERATOR ROOM AND PROVIDE
 SPECIFICATIONS IF APPLICABLE. D) PROVIDE AN EQUIPMENT
 SCHEDULE LISTING ALL THE MAKES AND MODELS AND SIZES OF
 AIR INTAKE AND EXHAUST LOUVERS. PLEASE NOTE THE
 MIAMI-DADE NOA'S OR FLORIDA PRODUCT APPROVALS MUST BE
 SUBMITTED FOR THE LOUVERS AS PART OF THE SUBMITTAL
 PACKAGE.
  
 COMMENT #8, M102: THE EXHAUST SYSTEMS AND FAN SIZING
 FOR THE GENERATOR AND FIRE PUMP ROOMS APPEAR TO HAVE
 BEEN CALCULATED USING THE METHOD USED FOR PARKING
 GARAGES. PLEASE SEE SECTION 4.1.2.1.3 NFPA 37-2010.
 ADDITIONALLY, THE EXHAUST DETAILS AND RISERS REFERENCED
 IN THE CALCULATIONS ARE NOT IN THE PLANS.
  
 COMMENT #9, M102- CALCULATIONS AND MAKE-UP AIR FOR THE
 BOILER ROOM EXHAUST HAVE NOT BEEN PROVIDED. PLEASE NOTE
 THAT AN EXHAUST SYSTEM IS REQUIRED FOR THE LOCKER ROOM
 SHOWN ON THE PLAN- SEE TABLE 403.3 AND REVISE THE PLAN
 ACCORDINGLY.
  
 COMMENT #10: OPERATIONAL SEQUENCE FOR MOTORIZED O/A AIR
 DAMPERS ON THE 1ST, 2ND, 3RD, AND 4TH FLOORS NOT
 PROVIDED AS REQUESTED. PLEASE SEE SECTION 503.2.5.4
 FBC-10 ENERGY CONSERVATION AND SHOW COMPLIANCE. PLEASE
 PROVIDE A PRODUCT SUBMITTAL REVIEWED BY THE EOR THAT
 MEETS COMPLIANCE WITH SECTION 503.2.5.4.1 WHICH
 REQUIRES THE DAMPER TO BE CLASS 1 LEAKAGE-RATED.
  
 COMMENT #11: SEE ADVISORY PRINTED ABOVE.
  
 COMMENT #12, M103: NUMEROUS FD'S OR FSD'S STILL MISSING
 AND ONE FLEX DUCT IS STILL SHOWN PENETRATING THE RATED
 CORRIDOR WALLS BY THE CORRIDOR 229/ICE MACHINE ALCOVE.
 A) DAMPERS MISSING AT: GRILL IN F&B DIRECTOR/SERVICE
 CORRIDOR WALL, EXHAUST DUCT PENETRATING MECH
 231/CORRIDOR 232 WALL, AND ALL TOILET EXHAUST DUCTS
 PENETRATING CORRIDOR WALLS. PLEASE NOTE A FIRESTOPPING
 DETAIL WILL BE REQUIRED FOR THE PRESSURIZATION DUCTS
 FROM RTU'S 1 & 2 PENETRATING THE RATED 2ND FLOOR
 FLOOR/CEILINGS.
  
 COMMENT #13, M1101-108, 201: REFRIGERANT PIPING CHASES
 AND RUNS NOT SHOWN.
  
 COMMENT #14: REFER TO 3RD REVIEW COMMENT #2 PRINTED
 ABOVE REGARDING FSD LOCATIONS AND SYMBOLS. ACCESS TO
 FIRE DAMPERS AND ACCESS PANEL DETAIL STILL EXISTS.
  
 COMMENT #15, M104: FIRE DAMPER MISSING FOR 24X8 DUCT
 PENETRATING THE ELEVATOR LOBBY/CORRIDOR WALL, AND
 EXHAUST DUCT PENETRATING THE CORRIDOR/STORAGE &
 CORRIDOR/WOMEN'S TOILET COMMON WALLS.
  
 **ADVISORY** M104: IN REGARD TO THE FUTURE GREASE DUCT
 RUNNING THOUGH THE FUTURE KITCHEN TO THE RATED CHASE,
 PLEASE REFER TO SECTION 506.3.7 FOR DUCT LENGTHS AND
 SLOPES, AND 506.3.8.2.
  
 COMMENT #16, M107: DAMPERS FOR DUCTS PENETRATING RATED
 FLOOR/CEILING ASSEMBLIES NOT SHOWN, AND FIRE DAMPER AND
 FIRESTOPPING DETAILS NOT PROVIDED. THE SUBMITTED
 RESPONSE NARRATIVE INDICATES FLAMEBAR DUCT IS TO BE
 USED BUT IT IS NOT NOTED ON THE PLAN.
  
 COMMENT #18, M107: THE CALCULATIONS FOR THE POOL
 EQUIPMENT WERE DONE USING A CALCULATION METHOD FOR
 PARKING GARAGES USING CO SENSORS. PLEASE PROVIDE
 CALCULATIONS AND A SYSTEM THAT WILL OPERATE BASED ON
 THE TYPE OF PROCESSES AND CHEMICALS TO BE USED AND
 STORED IN THE ROOM.
  
 **ADVISORY** M108: A) GUARDS MAY BE REQUIRED FOR
 SERVICEABLE EQUIPMENT ALONG THE ROOF EDGES OF STAIR
 TOWER #2 IF THE PARAPET DOES NOT EXTEND 42" ABOVE THE
 ROOF SERVICE. B) THE GREASE DUCT TERMINATION IS WITHIN
 10' OF THE ADJOINING PROPERTY LINE- REFER TO SECTION
 506.3.12.3 AND INDICATE COMPLIANCE ON THE PLAN.
  
 COMMENT #19, M302 & M303: PRODUCT CUT SHEETS AND NOA'S
 FOR MECHANICAL CURBS, STANDS, AND EQUIPMENT SHALL BE
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR.
  
 COMMENT #20, M502: CALCULATIONS FOR THE MEZZANINE
 LOUNGE, THE DIRTY LINENS ROOM, AND THE GUEST ROOMS NOT
 PROVIDED.
  
 COMMENT #21, M502: REQUESTED AIR BALANCE CALCULATIONS
 NOT PROVIDED.
  
 COMMENT #22, M602: REFER TO 3RD REVIEW COMMENTS #1 & 2
 PRINTED ABOVE.
  
 COMMENT #23: PROVIDE THE REQUESTED SUBMITTAL PACKAGE.
  
 4) SHEET M201: PROVIDE A SEQUENCE OF OPERATION FOR THE
 SMOKE DETECTORS IN THE GUEST ROOMS AND PROVIDE A
 SUBMITTAL FOR THE DEVICES APPROVED WITH SIGNATURE BY
 THE EOR.
  
 5) M201: LABEL THE ABOVE CEILING PLENUM SPACES AND
 PROVIDE NOTES AND DETAILS FOR CONSTRUCTION IN
 COMPLIANCE WITH SECTION 602.
  
 6) M301: DUCT HANGING, REINFORCEMENT AND CONNECTION
 DETAILS SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT
 CONSTRUCTION STANDARDS. PLEASE REVIEW THE DETAILS ON
 THE SHEET TO VERIFY COMPLIANCE AND LIST THE STANDARD IN
 THE PROJECT DESIGN CRITERIA.
  
 7) M501 & M503: REVISE THE ENERGY CALCULATIONS TO
 INCLUDE ALL THE COMPLIANCE DATA LISTED IN THE AC
 SCHEDULES.
  
 8) M503: INDICATE THE MANUFACTURER OF THE VRF SYSTEMS
 ON THE PLAN AND SUBMIT PRODUCT DATA SHEETS REVIEWED
 WITH SIGNATURE BY THE EOR. SHOW ON THE PLANS THE
 LOCATIONS OF THE CONTROL BOXES FOR THE SYSTEMS (LABELED
 AS BS IN SCHEDULES AND RISERS).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-20 Cont ID  
Sent By ccole Date 2015-05-20 Time 13:09 Rev Time 0.00
Received By ccole Date 2015-04-24 Time 13:09 Sent To  
Notes
2015-05-20 13:10:55CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
 PERMIT #14061217
 MECHANICAL REVIEW.
  
 1 ) COOLING & HEATING LOAD CALCULATIONS: THE SUBMITTAL
 DOES NOT INCLUDE THE CALCULATIONS FOR THE HOTEL ROOMS,
 AND MANY OF THE ROOMS AND SPACES SHOWN ON THE 1ST,
 MEZZANINE, AND 2ND FLOOR PLANS SUCH AS THE GYM, TRASH
 ROOM, SECURITY ROOM, LINEN ROOM, EMPLOYEE LOUNGE,
 HOUSEKEEPING; AND THE VARIOUS OFFICES, STORAGE ROOMS
 ETC. THROUGHOUT THE BUILDING, AND THE ROOMS AND SPACES
 ON THE POOL DECK FLOOR. IN ADDITION, THE SQUARE
 FOOTAGES LISTED ON THE DOCUMENTS DO NOT MATCH THE
 SQUARE FOOTAGES LISTED ON THE PLAN (SEE LIFE SAFETY
 SHEETS A1.00- A1.11.) FOR SQUARE FOOT TABLES. PLEASE
 NOTE THAT THE NUMBERED ZONES ON THE CALCS DO NOT
 CORRELATE TO THE PLANS WHICH DO NOT INDICATE ZONES.
 PLEASE REVIEW AND REVISE.
 2) ENERGY CALCULATION FORM 405-2010: THE FORM IS
 IDENTIFYING THE AC SYSTEMS AS "THROUGH THE WALL SINGLE
 PACKAGE" HOWEVER THE MAJORITY OF THE UNITS ARE
 MULTI-SPLIT SYSTEMS EXCEPT FOR THE TWO RTU?S.
 ADDITIONALLY, I DO NOT SEE HOW THE SYSTEMS LISTED- 1,
 2, & 15 CORRELATE TO THE ACTUAL SYSTEMS SHOWN ON THE
 HVAC PLAN SCHEDULES: PLEASE REVISE THE CALCULATIONS TO
 MATCH THE SYSTEMS ON THE PLANS, AND PLACE THE
 EFFICIENCY RATINGS OF THE SYSTEMS ON THE EQUIPMENT
 SCHEDULES.
 3) SHEETS M101, M102, & M103: THE PLANS INDICATE THE
 CORRIDORS BEING USED TO CONVEY RETURN AIR BACK TO THE
 UNITS WHICH IS NOT PERMITTED PER SECTION 601.2 FMC-10.
 PLEASE PROVIDE DUCTED RETURNS.
 4) M101: THERE ARE FIRE DAMPERS MISSING FOR DUCTS
 PENETRATING THE COMMON WALLS BETWEEN THE WOMEN'S
 RESTROOM/HR ROOMS, SECURITY/HR ROOM, AND THE
 OFFICE/VALET ROOMS; AND DAMPERS MISSING OVER THE RATED
 DOORS IN THE SERVICE CORRIDOR, AND OVER THE
 LINEN/CORRIDOR DOOR. PLEASE NOTE THAT A FLEX DUCT IS
 SHOWN PENETRATING THE OFFICE/VALET WALL- NOT PERMITTED
 PER SECTION 603.6.5 FMC-10.
 5) M101: EXHAUST IS REQUIRED FOR THE TRASH ROOM IN
 ACCORDANCE WITH TABLE 6-4 ASHRAE 62.1 04. REVISE THE
 PLANS TO SHOW THE FAN, EXHAUST DUCT IF NEEDED, AND
 TERMINATION LOCATION. INCLUDE THE REQUIRED FAN IN THE
 EQUIPMENT SCHEDULES.
 6) M102: FIRE DAMPERS MISSING FOR DUCTS PENETRATING
 COMMON WALLS BETWEEN THE MECH. RM/EMPLOYEE LOUNGE,
 MECH. RM/LOCKER RM, LOCKER RM/STORAGE RM, AND THE O/A
 DUCTS AT BOILER RM/SERVICE CORRIDOR AND SERVICE
 CORRIDOR/MECH. RM.
 7) M102: A RETURN AIR ARROW SYMBOL IS SHOWN DIRECTING
 AIR FROM THE SERVICE CORRIDOR THROUGH THE RATED DOUBLE
 DOORS AT THE MECH. RM: HOW IS AIR RETURNING THROUGH
 THESE RATED DOORS?
 8) M102: CLARIFY HOW THE EXHAUST SYSTEMS WERE SIZED FOR
 THE GENERATOR AND FIRE PUMP ROOMS: PROVIDE CALCULATIONS
 AND INDICATE THE SEQUENCE OF OPERATION FOR THE FANS.
 9) M102: CLARIFY HOW THE BOILER/PUMP ROOM WILL BE
 VENTILATED.
 10 )M101 & M102: INDICATE SEQUENCE OF OPERATION FOR THE
 O/A MOTORIZED DAMPERS FOR AC-1.1, AC-1.2, AND AC-1.3.
 11) M101 & M102: VERIFY REQUIRED 10' HORIZONTAL
 CLEARANCES FOR THE AIR INTAKES TO STREETS, PARKING,
 EXHAUST VENTS, ETC.- SECTION 401.4.1 FMC-10.
 12) M103: FLEX DUCTS ARE SHOWN IN MANY LOCATIONS OFF
 THE SERVICE CORRIDOR PENETRATING RATED WALLS, AND AT
 THE MECH. CLOSET FOR AC-2.1. FIRE DAMPERS ARE ALSO
 MISSING FOR RETURNS GRILLS IN MANY LOCATIONS: PLEASE
 CORRECT.
 13) M101- M108, M201: SHOW THE LOCATIONS OF AC PIPING
 RUNS OR CHASES. PROVIDE ON THE PLANS THE TYPE OF
 PIPING, TYPE AND THICKNESS OF PIPING INSULATION, AND
 THROUGH PENETRATION FIRE STOPPING DETAILS.
 14) M101- M106, M201: PROVIDE FSD SYMBOLS AT THE
 REQUIRED LOCATIONS- SEE SHEET 601. THE PLANS ARE
 INDICATING ONLY FD'S. PLACE A "TYPICAL" NOTE INDICATING
 REQUIRED ACCESS TO DAMPERS WILL BE PROVIDED- SECTION
 607.4 FMC-10.
 15) M104- M106: DAMPERS ARE NOT SHOWN FOR THE DUCTS
 PENETRATING THE RATED SHAFTS FOR RTU-1 & 2: PLEASE
 CORRECT.
 16) M107: SHOW LOCATIONS OF REQUIRED DAMPERS
 PENETRATING THE RATED FLOOR/CEILING ASSEMBLY.
 17) M107: INDICATE THE EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS FOR EF-6 & EF-7.
 18) M107: CLARIFY HOW THE POOL EQUIPMENT EXHAUST SYSTEM
 WAS SIZED: SHOW METHOD AND CALCULATIONS AND INDICATE
 SEQUENCE OF OPERATION
 19) M302 & 303: THE WIND LOAD TIE DOWN DETAILS SHOWN
 FOR THE AC UNITS, CURBS, STANDS, AND FANS ETC. MUST BE
 CERTIFIED BY A STRUCTURAL ENGINEER. PLEASE NOTE THAT
 ALL INSTALLATIONS SHALL WITHSTAND 170 MPH WIND LOADS
 AND ASSOCIATED UPLIFT AND LATERAL PRESSURES. PLEASE
 UPDATE THE NOTE UNDER DETAIL 1/M303.
 20) M502: O/A CALCULATIONS DO NOT INCLUDE THE ROOMS AND
 SPACES BEING SERVED BY A1.3 (MEZZANINE LOUNGE,
 ENGINEER'S OFFICE ETC.), AC-2.1 (2ND FLOOR OFFICES,
 HOUSEKEEPING ETC.), AC-2.2 (2ND FLOOR GYM), AND THE
 FCU-1'S AND FCU-2'S (GUEST ROOMS). ADDITIONALLY PROVIDE
 A CALCULATION FOR THE DIRTY LINENS ROOM PER TABLE 403.3
 FMC-10.
 21) M502: PROVIDE AIR BALANCE CALCULATIONS FOR FLOORS
 1-3.
 22) M602: PLEASE SEE SECTION 909 FBC-10 BUILDING FOR
 REQUIRED SUBMITTALS AND DOCUMENTS FOR THE PROPOSED
 SMOKE CONTROL SYSTEMS INCLUDING A RATIONAL ANALYSIS,
 AND A NARRATIVE DETAILING SPECIAL INSPECTIONS AND
 TESTING OF THE SYSTEM.
 23) PROVIDE A SUBMITTAL PACKAGE FOR THE PROJECT
 INCLUDING MANUFACTURER'S SPECIFICATIONS FOR THE RTU'S
 AND AC SYSTEMS AND ALL ASSOCIATED COMPONENTS FOR
 INSTALLATION OF COMPLETE SYSTEMS, THE SPF 1-2 AND SR-1,
 THE EXHAUST AND AIR INTAKE FANS, FIRE DAMPERS, FIRE AND
 SMOKE DAMPERS, SMOKE DETECTORS, DUCT SMOKE DETECTORS,
 MOTORIZED DAMPERS, CONTROLS, ETC.
 THE PACKAGE SHALL CONTAIN ALL REQUIRED FL. PRODUCT
 APPROVALS AND MIAMI-DADE NOA?S FOR EXTERIOR MOUNTED
 COMPONENTS SUBJECT TO WIND PRESSURES
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By hmoser Date 2014-08-07 Time 10:07 Rev Time 0.00
Received By hmoser Date 2014-08-04 Time 08:29 Sent To  
Notes
2014-08-07 09:42:41PLAN DENIED
  
 1) PAGE M-101 PROVIDE EXHAUST FAN FOR LAUNDRY ROOM
 PER TABLE 403.3 FBC (M) 2010
 2) MISSING MULTIPLE FIRE DAMPERS REFER TO SECTION
 607.5.1
 2010 FBC (M)
 3) PLEASE PROVIDE RATED WALLS ON MECHANICAL PLAN
 PER SECTION 107 FBC 2010
 4) PLAN SHOWS FRESH AIR INTAKE FOR A/C 1.2 ON NORTH
 SIDE OF THE BUILDING. REFER TO SECTION 401.4.1 2010 FBC
 (M)
 PAGE M-102
 1) MISSING MULTIPLE FIRE DAMPERS 607.5.1
 2) BATHROOM EXHAUST ROOM # M-13 M- 14 NEED FAN NUMBER
 AND
 CFM.
 3) GENERATOR REQUIRES SEPARATE APPLICATION, PLAN AND
 PERMIT.
 4) GREASE DUCT AND HOOD REQUIRE SEPARATE APPLICATION,
 PLAN
 AND PERMIT.
 5) PROVIDE INFORMATION ON CLOTHES DRYER LOCATION AND
 VENTILATION
 PER SECTION 504.8 FBC (M)
 6) PROVIDE SMOKE CONTROL ANALYSIS WITH THE PLAN
 PER SECTION 513.4 FBC (M)
 7) PROVIDE INFORMATION ON PRESSURIZED STAR TOWER
 CHAPTER 9 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-10 Cont ID  
Sent By tklarge Date 2016-04-10 Time 09:25 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 05:28 Sent To  
Notes
2016-04-09 06:34:231) SHT. A0.04 SHOWS A GENERATOR. SUBMIT MAUFACTURER'S
 SPECIFICATION SHEETS FOR THE EMERGENCY GENERATOR.
 SUBMIT COMPLETE PIPING DIAGRAMS, LOCATION & CAPACITY OF
 TANKS. FBC 107.1. THE GENERATOR SHALL COMPLY WITH NFPA
 37 & 110.
 2) SHT.C-09 - THE PLANS SHOW A 2 INCH WATER SERVICE AND
 A 2 INCH IRRIGATION LINE WITH 1 1/2 INCH BACKFLOW
 PREVENTERS INSTALLED ON THEM. THE BACKFLOW DEVICES
 SHOULD BE THE SAME SIZE AS THE WATER SERVICE.
 3) SHT.A 2.00 - A MINIMUM OF TWO DRINKING FOUNTAINS ARE
 REQUIRED FOR LEVEL 1 BUSINESS OCCUPANCY IN ACCORDANCE
 WITH THE 2010 FBC - ACCESSIBILITY SEC.211.2 AND 2010
 FBC-PLUMBING TABLE 403.1 & FOOTNOTE (E).
 4) SHT.A0.05 - WHY ARE THE DRINKING FOUNTAINS LOCATED
 IN THE GYM ROOM? THE DRINKING FOUNTAINS SHALL BE
 LOCATED IN A COMMON AREA FOR ALL TO USE. 2010 FPC SEC.
 403.3.1.
 5) SHT. A7.00 - THE PLUMBING FIXTURE REQUIREMENT TABLE
 LISTS THE OCCUPANT LOAD OF THE SUN DECK AS 96 PERSONS
 AND AT THE BOTTOM OF THE TABLE THE OCCUPANT LOAD IS
 SHOWN AS 124 PERSONS. WHICH IS IT, 96 PERSONS OR 124
 PERSONS? CLARIFY.
 6) THE HEIGHT OF THE SINK COUNTER IN THE BREAK ROOM
 #M11 SHALL BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH
 FLOOR PER 2010 ACCESSIBILITY SEC.606.3.
 7) SHT. P 4.04 - SUBMIT CONFIRMATION/VERIFICATION FROM
 SCHIER THAT THEY HAVE PERFORMED FACTORY SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTORS AND SUBMIT 2
 COPIES OF THE SIZING CALCULATIONS THAT HAVE BEEN DONE
 BY SCHIER. 2010 FBC SEC. 1003.2.
 8) PLUMBING SHEETS - THE WAY THE PLANS HAVE BEEN
 STAPLED I CANNOT SEE CERTAIN DETAILS AND CANNOT REVIEW
 THE COMPLETE PLAN. PLEASE ATTACH THE SHEETS SO THAT ALL
 DETAILS AND NOTES CAN BE READ. FBC 107.1.
 9) INDICATE THE SLOPE (PITCH) OF THE HORIZONTAL
 STORMWATER SYSTEM ON SHT.P 309. FBC 107.1. COMPLY WITH
 TABLE 1106.3 OF 2010 FPC.
 10) SHT. P 107- RWL #1 IS SHOWN AS 4 INCH AND ON SHT. P
 308 IT IS SHOWN AS 6 INCH. CLARIFY.
 11) SHT. P 107 - RWL #4 IS SHOWN AS 4 INCH BUT ON SHT.
 P 308 IT IS SHOWN AS 6 INCH. CLARIFY.
 12) SHT. P 301 - THERE IS NO COLD WATER TO THE HI-LO
 DRINKING FOUNTAIN.
 13) SHTS.107 & 108 - THE ROOF DRAIN CALCULATION TABLE
 SHOWS THE RAINWATER LEADERS AS 4 INCH BUT SHEETS 308 &
 309 SHOW SOME OF THE SAME RISERS AS 6 INCH. ALSO, ON
 SHT. P 308 THERE IS A RISER LABELED AS #6 BUT THERE IS
 NO RISER LABELED #6 IN THE ROOF DRAIN CALCULATION
 TABLE. CLARIFY.
 14) SHT. P 201 - IDENTIFY/LABEL ALL OF THE RISERS ON
 THE TYPICAL GUESTROOMS FLOOR PLAN SO A COMPREHENSIVE
 PLAN REVIEW CAN BE DDONE TO ENSURE THEY CORRELATE WITH
 THE RISER DIAGRAMS. FBC 107.3.5.1.3.
 15) SHT. P 302 - SIZE ALL THE WATER LINES ON THE LEVEL
 1 CW-HW-HWR WATER ISOMETRIC. FBC 107.1.
 16) SHT. P 306 - SUPPLY THE PLUMBING SYMBOL LEGEND AND
 CODED NOTES FOR THIS SHEET. 2ND REQUEST.
 17) SHT. P 307 - SIZE THE DRAIN AT THE INLET OF THE
 INTERCEPTOR, THE DRAIN AT THE OUTLET AND THE SECTION OF
 PIPE BETWEEN THE TWO INTERCEPTORS.
 18) SHT. P 309 - SIZE THE GAS LINES DOWNSTREAM OF THE
 SECOND STAGE REGULATORS.
 19) SHT. P 306 - SHOWS SANITARY RISER VII ON THE RISER
 DIAGRAM BUT IT IS NOT SHOWN ON THE FLOOR PLANS ON SHTS.
 P 103 & P 104. CLARIFY.
 20) SHT. P 104 - LABEL THE VENT SHOWN ON SHT. P 104,
 LOCATED IN FLEX SPACE #2, UNIT 307, LOCATED IN THE WALL
 BY THE AIRWALL #304.
 21) P 104 - LABEL THE VENT IN THE WALL BETWEEN STORAGE
 ROOMS #300 # 301.
 22) LABEL ALL VENTS THAT ARE SHOWN AS "VENT UP" OR
 "VENT DOWN."
 23) SHT. P 306 - RISERS # II, III, & IV - THE NUMBER
 AND TYPE OF FIXTURES PERMITTED ON A HORIZONTAL WET VENT
 IS EXCEEDED. REFER TO 2010 FPC DEFINITION OF A BATHROOM
 GROUP AND FPC SEC.909.1. REFER TO ROOM NUMBERS
 202,203,206, AND 207 & SHEET P 103.
 24) SHT. P 307 THE DRAIN LINE FROM THE ELEVATOR SUMP #1
 IS SHOWN AS DRAINING 100 F.U.CLARIFY. THERE IS A 4 INCH
 DRAININ THE SAME AREA DRAINING 156 F.U. CORRECT THE
 FIXTURE LOADS.
 25) SHT. P 306 - LABEL THE SANITARY RISER FOR THE GYM
 TOILET (#216) AND TOILET ROOM #222.
 26) SHT.P 307 - SANITARY GROUND FLOOR ISOMETRIC ? SHOWS
 A 6 INCH DRAIN WITH 497 FIXTURE UNITS DISCHARGING INTO
 A 4 INCH LINE FLOWING 665 UNITS. THE SIX INCH LINE
 CANNOT DISCHARGE INTO A 4 INCH LINE AND THE 4 INCH LINE
 IS UNDERSIZED. CHECK THE FIXTURE UNIT LOAD FOR THE
 SANITARY GROUND FLOOR ISOMETRIC.2010 FPC SEC.704.2.
 27) SHT. P 307 - CHECK THE FIXTURE UNIT LOAD FOR THE
 ENTIRE RISER. THERE ARE DRAINS WITH ONE FIXTURE
 DISCHARGING INTO THEM AND THE FIXTURE LOAD IS SHOWN AS
 100, 200 & 300 F.U. AND SOME LINES ARE UNDERSIZED.
 CLARIFY,
 28) SHT. P307 - THE MINIMUM SIZE VENT FOR A SIX INCH
 DRAIN SHALL COMPLY WITH 2010 FPC SEC.916.1 & TABLE
 916.1. THE DIAMETER OF THE VENT PIPE SHALL BE NO LESS
 THAN ONE-HALF THE DIAMETER OF THE DRAIN SERVED.
 29) SHT. P 303 - THE WATER RISER FOR THE MEZZANINE
 LEVEL HAS ONLY A FEW PIPE SIZES SHOWN. SIZE ALL
 SECTIONS OF THE WATER RISER. FBC SEC. 107.1.
 30) SHT. P 304 RISER C THE NUMBER AND TYPE OF FIXTURES
 ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED. SEE THE
 DEFINITION OF "BATHROOM GROUP" IN CHAPTER 2 AND ALSO
 SEC. 909.1 OF 2010 FPC.
 31) SHT. P 303 - THE WATER RISERS TO THE ROOMS ARE ONLY
 SHOWING A FEW PIPE SIZES. SIZE THE WATER RISERS IN
 THEIR ENTIRETY. NOTE: IS IT THE INTENT OF THE DESIGNER
 THAT A PIPE SIZE WILL REMAIN CONSTANT UNTIL A NEW SIZE
 IS SHOWN IN THE RISER AND THIS IS THE REASON THAT
 SECTIONS OF THE WATER RISERS ARE NOT SIZED? IF SO,
 PLACE A NOTE ON THE PLANS TO THIS EFFECT. IF NOT, THEN
 SIZE THE WATER RISERS IN THEIR ENTIRETY. FBC 107.1.
 32) SHT. P 305 - SHOWS A 2 INCH SANITARY UP TO THE
 ROOF. LABEL THE RISER IN ORDER FOR IDENTIFYING THE
 LOCATION ON THE ROOF AND ALSO ON P 107.
 33) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED
 WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC.
 606.5.5.THE RESPONSE NARRATIVE STATES THAT A NOTE WAS
 ADDED ON SHT. P 401 BUT I COULD NOT FIND THIS NOTE.
 CLARIFY.
 34) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL
 QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED.
 2010 FPC SEC. 604.9.THE NARRATIVE RESPONSE STATES THAT
 A NOTE WAS ADDED ON SHT. P 402 BUT I CANNOT FIND THE
 NOTE. CLARIFY.
 35) SHT. P 402 - THERE IS STILL A NOTE REFERRING TO A
 MIAMI - DADE ORDINANCE FOR PLUMBING FIXTURE
 REQUIREMENTS. REMOVE THE NOTE AS IT DOES NOT APPLY TO
 THIS PROJECT.
 36) THE DRAINAGE STACKS HAVE HORIZONTAL OFFSETS THAT
 OCCUR ON THE 2ND, 3RD & 4TH FLOORS AND MUST COMPLY WITH
 THE 2010 FPC SEC.915 WHERE FIVE OR MORE BRANCH
 INTERVALS ARE LOCATED ABOVE THE OFFSET. REFER ALSO TO
 FPC SECS. 915.2 & 915.3.
 37) THIS BUILDING IS OVER 10 BRANCH INTERVALS. THE 2010
 FPC SEC. 914 REQUIRES THAT SOIL AND WASTE STACKS IN
 BUILDINGS HAVING MORE THAN 10 BRANCH INTERVALS SHALL BE
 PROVIDED WITH A RELIEF VENT AT EACH TENTH INTERVAL
 INSTALLED, BEGINNING WITH THE TOP FLOOR.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 REVIEW NOT COMPLETE
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-06 Cont ID  
Sent By tklarge Date 2015-06-06 Time 11:14 Rev Time 0.00
Received By tklarge Date 2015-05-27 Time 11:07 Sent To  
Notes
2015-06-05 12:43:201) SHT. C-09 SHOWS A 2"IRRIGATION LINE EXITING A METER
 VAULT WITH A 4" FEBCO BFP DEVICE INSTALLED. IS THIS
 CORRECT? CLARIFY.
 2) SHT. P101 SHOWS AN 8" SANITARY LINE EXITING THE
 BUILDING AND SHT. C-09 SHOWS TWO 6" LATERALS. THERE IS
 NO 8" LINE SHOWN COMING INTO THE SITE. CLARIFY.
 3) SUBMIT THE CALCULATIONS FOR THE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS PER FPC TABLE 403.1.FOR THE
 OCCUPANCY TYPE FOR THE FIRST FLOOR INCLUDING THE RETAIL
 SPACE, THE MEZZANINE LEVEL, AND LEVEL 2. THE ONLY
 DRINKING FOUNTAIN CALCULATIONS THAT HAVE BEEN PROVIDED
 ARE FOR THE THIRD LEVEL AND POOL DECK.
 4) SHT. A1.01 - THE SINK IN BREAK ROOM # M11 ON THE
 MEZZANINE LEVEL SHALL COMPLY WITH THE FL. ACCESS. CODE
 SEC. 212, 606 AND 305.
 5) SHT.A7.00 - SUBMIT PLUMBING FIXTURE REQUIREMENTS FOR
 THE FIRST FLOOR INCLUDING THE RETAIL SPACE, THE
 MEZZANINE LEVEL, AND LEVEL 2.
 6) SHT. A7.00 - FIXTURE REQUIREMENTS FOR THE POOL DECK
 - THE CALCULATIONS ARE SHOWING AN OCCUPANT LOAD OF 96
 PERSONS FOR THE SUN DECK AND ALSO 124 PERSONS. CLARIFY.
 7) SHT. A7.00 - FIXTURE REQS. LEVEL 3 - THE TOTAL
 PERSON NUMBER IS SHOWN AS 380 AND THEN DIVIDED INTO 190
 MALES AND 297 FEMALES?? CLARIFY.
 8) A SERVICE SINK IS REQUIRED FOR THE POOL AREA PER FPC
 TABLE 403.1.
 9) SHT. A7.02 - ADA NOTE #6 - A DOOR PULL COMPLYING
 WITH FL. ACCESS. CODE SEC.404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR PER THE FAC SEC.604.8.1.2.
 10) SHT.A7.02 - SHOWER SPRAY UNIT - THE CONTROLS SHALL
 BE LOCATED A MINIMUM OF 38" ABOVE THE FINISH FLOOR, NOT
 3'-8" (44") AS SHOWN. FAC SEC.608.5.1.
 11) 11) ARCHITECTURAL SHEETS - FLOOR PLAN KEYED NOTES #
 28 REFERS TO DETAIL # 2 ON SHT.A8.03 FOR THE SCUPPER
 DETAIL. THERE IS NO SCUPPER DETAIL ON SHT.A8.03.
 DETAILS ARE ON SHT. A8.02. REVISE NOTE AND ALSO PROVIDE
 BOTH DIMENSIONS OF THE SCUPPER IN NOTE # 29.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 12) THE ROOF DRAINAGE CALCULATIONS SHALL INCLUDE
 ONE-HALF THE AREA OF THE VERTICAL WALL AT THE POOL DECK
 AND ANY OTHER AREAS THAT ARE AFFECTED BY A VERTICAL
 (PARAPET) WALL.
 13) SHT.P101 - CODED NOTES #1 REFERS TO SHT. P404 FOR
 GREASE TRAP DETAILS. THERE ARE NO GREASE TRAP DETAILS
 ON SHT. P404.
 14) SHT. P101 CODED NOTE #1 REFERS TO 2-SCHIER GB-250
 GREASE INTERCEPTORS. SUBMIT INTERCEPTOR SIZING
 CALCULATIONS IN ACCORDANCE WITH THE 2010 FPC
 SEC.1003.2, 1003.3.4. THE SIZING CALCULATIONS SHALL BE
 REVIEWED BY SCHIER IN ACCORDANCE WITH 2010 FPC SEC.
 1003.2. CONTACT LEE SCHNEEWEISS AT SCHIER AT
 1-800-538-4792.
 15) SHT.P101 - IDENTIFY/LABEL THE 3" S.S. UP IN THE
 TRASH ROOM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P101 - IDENTIFY/LABEL ALL THE CONDENSATE
 RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 17) SHT.P101 - IDENTIFY/LABEL ALL THE WATER RISERS
 (HW,CW, HWR, ).WPB AMEND. TO 2010 FBC SEC.107.2.1.
 18) SHT. P103 - RISER II UP APPEARS TO BE LOCATED
 OUTSIDE THE WALL NEXT TO A COLUMN. CLARIFY.
 19) SHT. P105 --SUPPLY THE PLUMBING SYMBOL LEGEND AND
 ANY CODE NOTES ON THE PLAN. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 20) SHTS. #107 & #108 ? ROOF DRAINAGE CALCULATION TABLE
 - SHOWS RWL #1 & #4 AS 4? & SHTS. P307 & P308 SHOW THEM
 AS 6". CLARIFY.
 21) SUBMIT THE DRAINAGE CALCULATIONS FOR THE TRENCH
 DRAINS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 22) INCLUDE DRAINS #6 & #7 ON THE DRAINAGE CALCULATION
 TABLE. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 23) THE SIZE OF THE DRAINS ON SHEETS #307 & #308 DO NOT
 CORRELATE WITH THE TABLE ON SHT. # 107. CLARIFY.
 24) SHT. P201 - IDENTIFY/LABEL ALL THE RISERS IN ORDER
 TO DO A COMPREHENSIVE REVIEW TO ENSURE THEY CORRELATE
 WITH THE DIAGRAMS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 25) SHT. P301 - THE HORIZONTAL BRANCHES FOR THE
 DOMESTIC WATER TO THE GUEST ROOMS ARE NOT SIZED, WATER
 LINES ARE NOT SHOWN TO THE PUBLIC RESTROOMS ON LEVEL 3,
 OR TO THE FUTURE KITCHEN. WATER LINES ARE NOT SHOWN TO
 THE RESTROOMS ON THE MEZZANINE LEVEL AND THE LINES ARE
 NOT SIZED TO THE RESTROOMS ON LEVEL 1. WHERE IS THE
 COLD WATER LINE TO THE RESTROOMS ON LEVEL 1? WPB AMEND.
 TO 2010 FBC SEC.107.2.1.
 26) SHT. P301 - THE WATER MAIN BRANCHES HAVE NO
 CONTINUATION/TERMINATION POINTS FOR LEVELS 1,2,3. LOOK
 AT THE WATER HEATERS ALSO. CLARIFY.
 27) SHT. P302 - IDENTIFY THE CONTINUATION /CONNECTION
 POINT OF THE HOT, COLD, AND HOT WATER RETURN LINES ON
 THE LEVEL 1 ISOMETRIC. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 28) SHT. P302 SIZE ALL THE WATER LINES ON THE ISOMETRIC
 FOR LEVEL 1 WATER RISER.
 29) SHT. P303 - THE INTERIOR WATER PIPING OF THE ROOMS
 ARE NOT SIZED. SEE ROOMS # 201-209.CLARIFY.
 30) SHT. P304 -THE SHEET IDENTIFIED AS CW & HW
 ISOMETRIC BUT IT IS SANITARY RISERS. PLEASE CORRECT.
 31) SHT. P306 - PLACE CODED NOTES ON SHEET. WPB AMEND.
 TO 2010 FBC SEC.107.2.1.
 32) SHT. P306 - SHOW THE TOTAL DFU'S FOR THE 3" S.S.UP.
 33) SHT. P306 -SIZE ALL SECTIONS OF THE DRAINAGE
 SYSTEM. SEE SECTION UPSTREAM OF STACKS III & IV, INLET
 & OUTLET AND IN BETWEEN THE GREASE INTERCEPTORS AND
 DOWNSTREAM OF THE GREASE INTERCEPTORS.
 34) SUBMIT A SANITARY RISER FOR THE MEZZANINE LEVEL.
 FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 35) P309 - SIZE THE GAS BRANCH LINES TO THE WATER
 HEATERS. FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 36) THERE ARE TWO SHEETS NUMBERED P309; ONE IS GAS AND
 ONE IS SANITARY. IS THIS A TYPO? CLARIFY.
 37) SHT. P309 SANITARY - SIZE ALL SECTIONS OF THE
 SANITARY RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 38) SHT. P309 SANITARY - RISERS II & IV ( ROOM # 206 &
 207 ) ? THE NUMBER AND TYPE OF FIXTURES PERMITTED ON A
 HORIZONTAL WET VENT IS EXCEEDED. REFER TO 2010 FPC
 DEFINITION OF A ?BATHROOM GROUP? AND FPC SEC. 909.1.
 39) RISER IV ON P309 IS LABELED AS RISER V ON P 103 &
 RISER VI ON P103 IS LABELED AS RISER IV ON P309.
 CLARIFY.
 40) THERE IS A PARTIAL RISER ON P309 THAT APPEARS TO BE
 A PRINTING ERROR AND THERE IS ANOTHER RISER THAT IS NOT
 IDENTIFIED. CLARIFY.
 41) SHT.P309 IDENTIFY THE RISER FOR THE GYM TOILET ROOM
 (216) & TOILET ROOM # 222.
 42) SHT. P305 - SIZE ALL SECTIONS OF THE SANITARY
 RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 43) SHT. P 305 - SANITARY - IDENTIFY/LABEL THE 2?
 SANITARY RISER UP TO ROOF IN ORDER FOR IDENTIFYING
 LOCATION ON ROOF.(BETWEEN ROOMS 4-4 & 4-5).
 44) SHT. P304 - RISERS A, B, C, & D - SIZE ALL SECTIONS
 OF THE SANITARY RISER FOR THE UNITS (LAVATORY STACKS,
 HORIZONTAL DRAINS, SHOWERS. ONE DIAGRAM CAN BE SIZED
 AND SHOWN AS " TYPICAL."
 45) SHT. P 304 - RISER "C" - THE NUMBER AND TYPE OF
 FIXTURES ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED.
 SEE DEFINITION OF " BATHROOM GROUP" IN FPC AND IN
 SEC.909.1.
 46) SHT. 305 - RISER " E "- THE TOTAL DFU LOAD IS 28.
 THERE ARE TWO ADDITIONAL SHOWERS NEAR THE BASE OF THE
 RISER.
 47) SHT. P306 - SHOW THE TOTAL DFU?S THAT DISCHARGING
 INTO EACH RISER SO THE SIZING OF THE HORIZONTAL
 BRANCHES CAN BE DONE. DO THE SAME ON SHT. P 305. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 48) SHTS.P304 & P305 - IDENTIFY / LABEL THE CONNECTION/
 CONTINUATION POINTS OF THE VENTS WHERE THE CONNECT TO
 THE RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 49) SHOW THE LOCATION OF THE 2ND STAGE REGULATORS ON
 THE GAS DRAWING FOR THE WATER HEATERS.
 50) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED
 WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC.606.5.5.
 51) SHT. P309 - HOW CAN THE LONGEST RUN OF THE GAS
 PIPING BE NOTED AS 50 FEET WHEN THE DIMENSIONS ADD UP
 TO 81 FEET???
 52) THE DOMESTIC WATER SYSTEM SHALL BE EQUIPPED WITH
 PRESSURE REDUCING VALVES IF THE POSSIBILITY OF THE
 PRESSURE TO EXCEED 80 PSI EXISTS FPC SEC.604.8.
 53) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL
 QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED.
 FPC SEC.604.9.
 54) SUBMIT THE SPECS/INSTALLATION MANUAL FOR THE POWER
 VENTS FOR THE GAS WATER HEATERS.
 55) SHT. P402 REFERS TO MIAMI-DADE ORDINANCE FOR
 PLUMBING FIXTURE REQUIREMENTS. REMOVE ALL REFERENCE TO
 MIAMI-DADE COUNTY.
 56) SHT. P402 - SUBMIT AN EXPLANATION ON HOW THE
 CALCULATIONS FOR THE COMBUSTION AIR FOR THE GAS WATER
 HEATERS WERE DONE. THERE IS A REFERENCE TO SEC. 706 OF
 THE FBC-MECHANICAL CODE. THIS SECTION SPECIFICALLY
 STATES THAT THE CODE SECTION DOES NOT APPLY TO DIRECT
 VENT APPLIANCES. SEC. 304.1 OF THE FBC-FUEL GAS STATES
 THAT DIRECT VENT APPLIANCES SHALL BE PROVIDED WITH
 COMBUSTION, VENTILATION AND DILUTION AIR IN ACCORDANCE
 WITH THE APPLIANCE MANUFACTURER?S INSTRUCTIONS. SUBMIT
 A COPY OF THE INSTRUCTIONS FOR REVIEW AND SUPPLY THE
 CALCS FOR COMBUSTION AIR ACCORDING TO THE MANUFACTURER.
 57) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY
 WITH THE FL. ENERGY CODE SEC. 504.6 FOR SYSTEM
 CONTROLS.
 58) THE SANITARY RISER STACKS SHALL BE VENTED TO COMPLY
 WITH THE FPC SEC. 915.1, 915.2, 915.3 FOR THE VENTING
 OF STACK OFFSETS
 59) THE RESPONSE FROM THE DESIGN PROFESSIONAL REFERS TO
 SHEET P300. THERE IS NO SHT. 300 IN THE PLANS. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-27 Cont ID  
Sent By jwitmer Date 2014-07-27 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 09:41 Sent To  
Notes
2014-07-24 12:33:50PLUMBING PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JULY 27/ 2014
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTICE TO THE DESIGNER OF RECORD:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE TO THE DESIGNER FOR PLAN REVIEW, IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1A) NEITHER SHEET A0.01 BLDG & ZONING CALCS., SHEET
 A1.00 LIFE SAFETY NOR P101 PROVIDE OCCUPANCY LOADS
 (TOTAL) NOR DOES SHEET P101 PROVIDE THE MINIMUM
 PLUMBING FIXTURES REQUIRED PER 2010 FBC-PLUMBING
 NEITHER SHEET A0.01 BLDG & ZONING CALCS., SHEET A1.00
 LIFE SAFETY NOR P101 PROVIDE OCCUPANCY LOADS NOR DOES
 SHEET P101 PROVIDE THE MINIMUM PLUMBING FIXTURES
 REQUIRED PER 2010 FBC-PLUMBING SECTION 403 AND TABLE
 403.1 FOR THEFOR THE COMMON AREAS ON THE 1ST FLOOR AND
 2ND FLOOR (MEZZANINE).
  
 1B) SHEET P104 THE 3RD FLOOR RESTUARANT AND FLEX AREAS
 PROVIDE A TABLE/ CHART IN COMPLIANCE WITH THE 2010
 FBC-P SECTION 403 AND TABLE 403.1.
  
 1C) SHEET P107 THE ROOF DECK/ POOL DECK DOES NOT
 PROVIDE A TABLE/ CHART IN COMPLIANCE WITH THE 2010
 FBC-P SECTION 403 AND TABLE 403.1.
  
 2) SHEET P101:
  
 2A) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS
 SYSTEM. THE PLANS SHOW THE NATURAL GAS SYSTEM INTRERING
 THE BUILDING WITHIN THE FPL VAULT. PLEASE CHECK WITH
 FPL, I DO NOT BELIEVE THEY WANT ANY OTHER UTILITES
 SHARING THEIR VAULT SPACE EXSPECIALLY A 2LB NATURAL GAS
 SYSTEM.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, 101.3 THE PURPOSE OF THIS CODE IS TO
 ESTABLISH THE MINIMUM REQUIREMENTS TO SAFEGUARD THE
 PUBLIC HEALTH, SAFETY AND GENERAL WELFARE THROUGH
 STRUCTURAL STRENGTH, MEANS OF EGRESS FACILITIES,
 STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION,
 ENERGY CONSERVATION, AND SAFETY TO LIFE AND PROPERTY
 FROM FIRE AND OTHER HAZARDS ATTRIBUTED TO THE BUILT
 ENVIRONMENT AND TO PROVIDE SAFETY TO FIRE FIGHTERS,
 CODE OFFICIALS, AND EMERGENCY RESPONDERS DURING
 EMERGENCY OPERATIONS.
  
 2B) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS
 SYSTEM. THE REST OF THE FUEL GAS COMMENTS WILL BE UNDER
 A SEPERATE GAS REVIEW.
  
 3) SHEET P101 INDICATES THE USE OF (2) NEW SCHIER 250
 GREASE INTERCEPTORS, NOTE # 1 INDICATES SEE DETAILS
 FOUND ON SHEET P400. THERE IS NO SHEET P400 IN ALL (3)
 SETS OF PLANS. THERE IS NO SHEET P400 LISTED IN THE
 INDEX EITHER. PLEAS PROVIDE THE SIZING CALCULATIONS
 USED FOR THIS INSTALATION PER 2010 FBC-P 1003.2
 APPROVAL. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR AND OF EACH SEPARATOR SHALL BE APPROVED BY
 THE PLUMBING OFFICIAL. THE INTERCEPTOR OR SEPARATOR
 SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND THE REQUIREMENTS OF
 THIS SECTION. WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR.
  
 WITHOUT THE FUTURE RESTUARANT LAYOUT, EQUIPMENT, TYPE
 OF FOODS, LOW, MEDIUM OR HIGH GREASE CONTENT HOW CAN
 THE COMMERCIAL KITCHEN AND GREASY WASTE BE SIZED?
  
 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 4) SHEET P101 NOTE # 4 INDICATES WITHIN THE ELEVATOR
 SHAFT THE USE OF SUMP PUMPS AND INDIRECT WASTE. PLEASE
 PROVIDE THE TYPE OF ELEVATORS TO BE INSTALLED. IF
 HYDROLIC ELEVATORS THEN EITHER A OIL SEPARATOR OR AN
 APPROVED ALARM SYSTEM IS INSTALLED. SEE 2010 FBC_P
 1003.4.
  
 5) SHEET P101 FIRE PUMP ROOM THE FLOOR DRAIN IS MISSING
 THE TRAP PRIMER. 2010 FBC-P 1002.4.
  
 6) SHEET P101 THE A/C CONDENSATE PIPING IS NOT SIZED
 NOR TYPE OF MATERIAL, PLEASE SIZE TO THE 2010 FBC-P
 314.2 & TABLE 314.2, THIS COMMENT IS COMMON TO ALL
 FLOORS.
  
 7) SHEET P101 A/C CONDENSATE LEADS FROM THE BUILDING TO
 THE DRIVE AND CATCH BASIN, NOT ALSO THERE ARE (2) 6"
 STORM PIPES (RAIN/ STORM) PIPES LEADING FROM UNDER THE
 BUILDING. THE MATERIAL THESE PIPES ARE MADE FROM IS NOT
 IDENTIFIED, IDENTIFY MATERIAL AND THICKNESS AND OR
 SCHUDULE.
  
 1102.4 BUILDING STORM SEWER PIPE. BUILDING STORM SEWER
 PIPE SHALL CONFORM TO ONE OF THE STANDARDS LISTED IN
 TABLE 1102.4.
  
 1102.5 SUBSOIL DRAIN PIPE. SUBSOIL DRAINS SHALL BE
 OPEN-JOINTED, HORIZONTALLY SPLIT OR PERFORATED PIPE
 CONFORMING TO ONE OF THE STANDARDS LISTED IN TABLE
 1102.5.
  
 8) SHEETS P102- P108 ARE INCOMPLETE THERE ARE NO NOTES
 ON ANY OF THESE SHEETS.
  
 9A) ) THERE ARE NO PLUMBING SANITARY RISER ISOMETRIC
 PLANS SUBMITTED. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1.3 PLUMBING 13. PLUMBING RISER.
  
 9B) THIS BUILDING IS CONSIDERED 12 STORIES TALL. PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-P:
 914.1 WHERE REQUIRED.
 SOIL AND WASTE STACKS IN BUILDINGS HAVING MORE THAN 10
 BRANCH INTERVALS SHALL BE PROVIDED WITH A RELIEF VENT
 AT EACH TENTH INTERVAL INSTALLED, BEGINNING WITH THE
 TOP FLOOR.
  
 914.2 SIZE AND CONNECTION.
 THE SIZE OF THE RELIEF VENT SHALL BE EQUAL TO THE SIZE
 OF THE VENT STACK TO WHICH IT CONNECTS. THE LOWER END
 OF EACH RELIEF VENT SHALL CONNECT TO THE SOIL OR WASTE
 STACK THROUGH A WYE BELOW THE HORIZONTAL BRANCH SERVING
 THE FLOOR, AND THE UPPER END SHALL CONNECT TO THE VENT
 STACK THROUGH A WYE NOT LESS THAN 3 FEET (914 MM) ABOVE
 THE FLOOR.
  
 SECTION 915
 VENTS FOR STACK OFFSETS
  
 915.1 VENT FOR HORIZONTAL OFFSET OF DRAINAGE STACK.
 HORIZONTAL OFFSETS OF DRAINAGE STACKS SHALL BE VENTED
 WHERE FIVE OR MORE BRANCH INTERVALS ARE LOCATED ABOVE
 THE OFFSET. THE OFFSET SHALL BE VENTED BY VENTING THE
 UPPER SECTION OF THE DRAINAGE STACK AND THE LOWER
 SECTION OF THE DRAINAGE STACK.
  
 10A) THERE IS NO PLUMBING STORM/ ROOF DRAINAGE RISER
 ISOMETRIC DIAGRAM SUBMITTED. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS 107.3.5.1.3 PLUMBING 13.
 PLUMBING RISER.
  
 10B) THIS BUILDING IS OVER 12 STORIES TALL. PROVIDE
 COMPLIANCE WITH 2010 FBC-P:
  
 914.1 WHERE REQUIRED.
 SOIL AND WASTE STACKS IN BUILDINGS HAVING MORE THAN 10
 BRANCH INTERVALS SHALL BE PROVIDED WITH A RELIEF VENT
 AT EACH TENTH INTERVAL INSTALLED, BEGINNING WITH THE
 TOP FLOOR.
  
 914.2 SIZE AND CONNECTION.
 THE SIZE OF THE RELIEF VENT SHALL BE EQUAL TO THE SIZE
 OF THE VENT STACK TO WHICH IT CONNECTS. THE LOWER END
 OF EACH RELIEF VENT SHALL CONNECT TO THE SOIL OR WASTE
 STACK THROUGH A WYE BELOW THE HORIZONTAL BRANCH SERVING
 THE FLOOR, AND THE UPPER END SHALL CONNECT TO THE VENT
 STACK THROUGH A WYE NOT LESS THAN 3 FEET (914 MM) ABOVE
 THE FLOOR.
  
 SECTION 915
 VENTS FOR STACK OFFSETS
  
 915.1 VENT FOR HORIZONTAL OFFSET OF DRAINAGE STACK.
 HORIZONTAL OFFSETS OF DRAINAGE STACKS SHALL BE VENTED
 WHERE FIVE OR MORE BRANCH INTERVALS ARE LOCATED ABOVE
 THE OFFSET. THE OFFSET SHALL BE VENTED BY VENTING THE
 UPPER SECTION OF THE DRAINAGE STACK AND THE LOWER
 SECTION OF THE DRAINAGE STACK.
  
 11) MISSING: ROOF & DECK DRAINAGE PLANS.
 11A) A203/ P104 A- SHEET 3RD FLOOR TERRACE/ RETUARANT
 NOTE# (20) PROVIDE 4 INCH CONTINIOUS DECK DRAIN, NO
 OVER FLOW PLUMBING SHEET NO NOTES
 11B) A2.11/ P107 A-SHEET POOL DECK NOTE# (20) PROVIDE 4
 INCH CONTINIOUS DECK DRAIN, NO OVER FLOW, PLUMBING
 SHEET NO NOTES.
 11C) A2.12/ P1.108 A-SHEET UPPER ROOF DRAINAGE NOTE 15
 REFFERS TO PLUMBING SHEETS, PLUMBING SHEETS NO NOTES.
  
 THE ROOF AND DECK DRAINAGE ARE TO BE SIZED, BASED ON
 THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN FIGURE
 1106.1 OR ON OTHER RAINFALL RATES DETERMINED FROM
 APPROVED LOCAL WEATHER DATA. 2010 FBC-P 1106.1 FOR THE
 CITY OF WEST PALM BEACH THIS IS 4.5 INCHES. 100-YEAR,
 1-HOUR RAINFALL (INCHES).
  
 11B) PLEASE PROVIDE CALCULATIONS FOR SIZING OF THE ROOF
 DRAINS, & DECK DRAINS FOR THE FLAT AREAS SERVED PLUS
 THE VERTICAL WALL AREA AS REQUIRED BY
 1106.4. IF THERE ARE CONTRIBUTING SLOPED ROOFS THAT ADD
 TO THE DRAIN BEING SERVED PROVIDE THE SQ FOOTAGE OF
 THAT AREA AS WELL.
  
 11C) 1106.2 VERTICAL CONDUCTORS AND LEADERS. VERTICAL
 CONDUCTORS AND LEADERS SHALL BE SIZED FOR THE MAXIMUM
 PROJECTED ROOF AREA, IN ACCORDANCE WITH TABLES
 1106.2(1) AND 1106.2(2).
  
 11D) 1106.3 BUILDING STORM DRAINS AND SEWERS.
 THE SIZE OF THE BUILDING STORM DRAIN, BUILDING STORM
 SEWER AND THEIR HORIZONTAL BRANCHES HAVING A SLOPE OF
 ONE-HALF UNIT OR LESS VERTICAL IN 12 UNITS HORIZONTAL
 (4-PERCENT SLOPE) SHALL BE BASED ON THE MAXIMUM
 PROJECTED ROOF AREA IN ACCORDANCE WITH TABLE 1106.3.
 THE MINIMUM SLOPE OF HORIZONTAL BRANCHES SHALL BE
 ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE) UNLESS OTHERWISE APPROVED.
  
 11E) 1110.4 MINIMUM NUMBER OF ROOF DRAINS.
 NOT LESS THAN TWO ROOF DRAINS SHALL BE INSTALLED IN
 ROOF AREAS 10,000 SQUARE FEET (929 M2) OR LESS AND NOT
 LESS THAN FOUR ROOF DRAINS SHALL BE INSTALLED IN ROOFS
 OVER 10,000 SQUARE FEET (929 M2) IN AREA.
  
 12) FOR BOTH THE 3RD FLOOR TERRACE (P104) AND POOL DECK
 (P107) NEITHER OF THSE PLANS INDICATE HOW COMPLIANCE
 WITH :
 2010 FBC-PLUMBING SECTION 1107/ SECONDARY (EMERGENCY)
 ROOF DRAINS
  
 12A)1107.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
  
 12B)1107.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT
 OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM.
 DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT
 WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONNEL.
  
 12C)1107.3 SIZING OF SECONDARY DRAINS.
 SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 1106 BASED ON THE RAINFALL
 RATE FOR WHICH THE PRIMARY SYSTEM IS SIZED IN TABLES
 1106.2(1), 1106.2(2), 1106.3 AND 1106.6. SCUPPERS SHALL
 BE SIZED TO PREVENT THE DEPTH OF PONDING WATER FROM
 EXCEEDING THAT FOR WHICH THE ROOF WAS DESIGNED AS
 DETERMINED BY SECTION 1101.7 . SCUPPERS SHALL NOT HAVE
 AN OPENING DIMENSION OF LESS THAN 4 INCHES (102 MM).
 THE FLOW THROUGH THE PRIMARY SYSTEM SHALL NOT BE
 CONSIDERED WHEN SIZING THE SECONDARY ROOF DRAIN SYSTEM.
  
 12D) NOTE SHEET A212 DOES PROVIDE OVER FLOW SCUPPERS
 AND SIZED PROPERLY FOR A 5 INCH /PER HOUR RAINFALL. THE
 PLANS DO NEED TO MAKE A CORRECTION. THE PLANS INDICATE
 A 5 FOOT RAIN FALL/ HOUR. 107.2.1.3 TYPO
  
 13) WITHIN THE POOL DECK THERE WILL PLANTERS THAT WILL
 REQUIRE ADDITIONAL DRAINAGE, NO DETAILS WERE SUBMITTED
 WITHIN THIS REVIEW. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIED.
  
 14) NOTE TO DATE THERE HAS BEEN NO IRRIGATION DRAWINGS
 BEING SUBMITTED. IRRIGATION DOES REQUIRE A SEPARATE
 PERMIT AND ASSOCIATED FEES.
  
 15) POOL DECK SHEET P107:
 15A) POOL BAR IS MISSING THE WATER SERVICE (POTTABLE
 WATER REQUIRED 602.2) TO THE BAR AREA.
  
 15B) POOL PIPING TO BE REVIEWED UNDER THE POOL PERMIT,
 WILL THERE BE GAS POOL HEATERS? 107.2.1.3 ADDITIONAL
 INFORMATION.
  
 15C) MISSING 424.1.6.1.4 HOSE BIBB. A HOSE BIBB WITH
 VACUUM BREAKER SHALL BE PROVIDED IN OR WITHIN 25 FEET
 (7620 MM) OF EACH RESTROOM TO ALLOW FOR EASE OF
 CLEANING.
  
 15D) MISSING 424.1.6.2 RINSE SHOWER. A MINIMUM OF ONE
 RINSE SHOWER SHALL BE PROVIDED ON THE POOL DECK OF ALL
 OUTDOOR POOLS WITHIN 20 FEET (60 960 MM) OF THE NEAREST
 POOL WATER?S EDGE.
  
 15E) THE PLANS INDICATE A 1" WATER SERVICE INTO THE
 POOL EQUIPMENT ROOM, PLANS SHOW A VALVE BUT IT APPEARS
 THERE IS NO PROTECTION TO THE POTTABLE WATER SUPPLY.
 2010 FBC-P 608.3.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 .
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2017-05-15 Cont ID  
Sent By shill Date 2016-06-23 Time 11:13 Rev Time 0.00
Received By shill Date 2016-03-22 Time 10:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2015-05-22 Time   Sent To  
Notes
2015-05-22 14:15:402ND REVIEW. DEFERRED SUBMITTALS: ROOFING: THIS
 SUBMITTAL NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-07-24 Cont ID  
Sent By jwitmer Date 0201-07-24 Time 05:58 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 05:57 Sent To  
Notes
2015-05-19 05:59:58ROOFING: THIS SUBMITTAL NO ROOFING PRODUCT APPROVALS
 WERE SUBMITTED.

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2015-01-23 Cont ID  
Sent By rbrown Date 2015-01-23 Time 20:38 Rev Time 0.00
Received By rbrown Date 2015-01-23 Time 20:38 Sent To  
Notes
2015-01-23 20:42:13OWNER REQUESTED EXTENSION ON THE PERMIT APPLICATION TO
 ALLOW TIME FOR OBTAINING TRANSFER DEVELOPMENT RIGHTS
 (TDRS). PERMIT APPLICATION EXTENDED UNTIL 4/22/15.

Review Stop Z ZONING
Rev No 3 Status F Date 2016-06-22 Cont ID  
Sent By aaponte Date 2016-06-22 Time 15:36 Rev Time 0.00
Received By aaponte Date 2016-06-22 Time 15:36 Sent To  
Notes
2016-06-22 16:39:401-THE PROPOSED HOTEL IS REQUIRED TO PURCHASE A TOTAL OF
 32,509 SF OF TDR. THE TDR TRANSFER SHALL BE APPROVED BY
 THE DAC BEFORE A BUILDING PERMIT CAN BE ISSUED.
 2- COMPLIED-THE CALCULATION FOR THE MEZZANINE AREA
 SHALL BE DONE BASED ON THE GROSS AREA FOR THE GROUND
 FLOOR AND THE MEZZANINE. AS PROPOSED MEZZANINE AREA
 EXCEEDS THE MAXIMUM 50% OF THE GROUND LEVEL GROSS AREA,
 AND IT SHALL BE REDUCED OR IT WILL COUNT AS A FLOOR.
 3- COMPLIED - PROPOSED LOADING AREA ALONG THE ALLEY
 DOES NOT HAVE DIMENSIONS TO WORK AS A PARALELL LOADING
 AREA. PARALELL SPACE SHALL BE AT LEAST THE MINIMUM 8
 FEET REQUIRED FOR PARALELL PARKING. LOADING IS NOT
 REQUIRED FOR THIS PROJECT. AS THE PROPOSED SPACE ALONG
 THE ALLEY DOES NOT MEET THE MINIMUM WITH FOR A PARALELL
 PARKING, IT SHALL NOT BE IDENTIFIED AS LOADING OR
 PARKING.
 4- PLEASE PROVIDE A SECTION TO CONFIRM- SIDEWALK
 CROSSING THE DRIVEWAY SHALL BE MAINTAINED AT SIDEWALK
 GRADE, AND SHALL BE THE SAME MATERIAL OF THE SIDEWALK.
 5- COMPLIED- CIVIL DRAWINGS AND SITE PLAN ARE NOT
 CONSISTENT REGARDING THE PORTE COCHERE APRON AND DRIVE.
 6- PROPOSED PAVER TREATMENT ALONG DIXIE HWAY WILL
 REQUIRE A MAINTENANCE AGREEMENT, WHERE THE HOTEL
 BECOMES RESPONSIBLE FOR THE MAINTENANCE OF THE PAVERS.
 7- COMPLIED-PROPOSED STOP BAR SHALL BE MOVED AWAY FROM
 THE SIDEWALK TRAVEL PATH AND INTO THE PORTE COCHERE
 AREA.
 8- COMPLIED-THE PORTE COCHERE TRAFFIC FLOW SHALL FOLLOW
 THE DIXIE HWAY DIRECTION OF TRAFFIC ( ENTRANCE ON NORTH
 DRIVEWAY, AND EXIT ON SOUTH DRIVEWAY).
 9- COMPLIED- PROPOSED CATCH BASINS CANNOT GO IN THE
 MIDDLE OF THE SIDEWALK.
 10- LANDSCAPE IN ROOFTOP TERRRACE NEED AUTOMATIC
 IRRIGATION. THERE ARE PLANTER URNS LOCATED IN AREAS
 DIFFICULT TO REACH FOR HAND WATERING.
 11- COMPLIED- SIDEWALK ALONG DIXIE HIWAY BETWEEN THE
 TWO PORTE COCHERE DRIVEWAYS IS SHOWN HALF IN PARVER AND
 HALF IN CONCRETE. WHAT IS THE REASON FOR THAT?
 12- COMPLIED - TREE GRATES SHALL BE INSTALLED ALONG
 DIXIE HWAY FOLLOWING THE RHYTHM AND PATTERN OF THE ONES
 ON THE WEST SIDE.
 13- COMPLIED- RESTAURANT DOOR ON CLEMATIS SHALL BE
 RECESSED SO IT DOES NOT ENCROACH MORE THAN 12" INTO THE
 SIDEWALK.
 14- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH THE MINIMUM LANDSCAPE REQUIREMENTS FOR THE ROOFTOP
 GARDEN ON TOP OF THE 2ND FLOOR (TABLE IV-7). PLEASE
 CORRECT THE TITLES AS IT INDICATES A TERRACE ON THE
 17TH FLOOR. PLEASE BREAK OUT THE LIST OF TREES PROVIDED
 TO COMPLY WITH CANOPY REQUIREMENT.
 15. GARBAGE COLLECTION OPERATION SHALL BE APPROVED BY
 THE SANITATION DEPARTMENT. PLEASE CONTACT FERDINAND
 RIVERA AT 561-822-2076. PROVIDE APPROVAL LETTER FROM
 SANITATION.
 16. PLEASE LABEL ALL MECHANICAL ROOMS NOT COUNTED AS
 PART OF THE FAR IN THE FLOOR PLANS, AND IDENTIFIED THE
 TYPE OF MECHANICAL USE INTENDED FOR THE ROOM.
 17. PROPOSED BASE PLANTING INDICATED ON THE SIDEWALK
 BETWEEN THE TWO CURB CUTS IS NOT PERMITTED. SPACE SHALL
 BE MAINTAINED AS SIDEWALK.
 18. PLEASE SEPARATE THE LANDSCAPE DRAWINGS AND SUBMIT
 FOR LANDSCAPE PERMIT.
 19. COMPLIED-NEW HALLWAY CONNECTING 3RD LEVEL ROOF TOP
 ELEVATOR WITH PORCH HAS RESULTED IN ADDITIONAL BLANK
 FACADE TOWARDS THE EAST. SPACE SHALL BE OPEN TO ALLOW
 FOR ARCHITECTURAL ELEMENTS. ANY ENCLOSED AREA SHALL BE
 COUNTED AS PART OF THE FAR.
 20. ACCORDING TO DAC FINAL ORDER NO. 12-01, THE PORCH
 SHALL NOT EXPAND BEYOND DIMENSIONS PRESENTED TO THE
 BOARD AT THE TIME OF THE HEARING.
 21. LANDSCAPING ALONG DIXIE HWAY SHALL MATCH THE
 EXISTING ON THE WEST SIDE OF DIXIE HWAY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-07-14 Cont ID  
Sent By aaponte Date 2015-07-14 Time 15:29 Rev Time 0.00
Received By aaponte Date 2015-07-14 Time 14:25 Sent To  
Notes
2015-07-14 15:29:491-THE PROPOSED HOTEL IS REQUIRED TO PURCHASE A TOTAL OF
 31,963 SF OF TDR. THE TDR TRANSFER SHALL BE APPROVED BY
 THE DAC BEFORE A BUILDING PERMIT CAN BE ISSUED.
 2- COMPLIED-THE CALCULATION FOR THE MEZZANINE AREA
 SHALL BE DONE BASED ON THE GROSS AREA FOR THE GROUND
 FLOOR AND THE MEZZANINE. AS PROPOSED MEZZANINE AREA
 EXCEEDS THE MAXIMUM 50% OF THE GROUND LEVEL GROSS AREA,
 AND IT SHALL BE REDUCED OR IT WILL COUNT AS A FLOOR.
 3- PROPOSED LOADING AREA ALONG THE ALLEY DOES NOT HAVE
 DIMENSIONS TO WORK AS A PARALELL LOADING AREA. PARALELL
 SPACE SHALL BE AT LEAST THE MINIMUM 8 FEET REQUIRED FOR
 PARALELL PARKING. LOADING IS NOT REQUIRED FOR THIS
 PROJECT. AS THE PROPOSED SPACE ALONG THE ALLEY DOES NOT
 MEET THE MINIMUM WITH FOR A PARALELL PARKING, IT SHALL
 NOT BE IDENTIFIED AS LOADING OR PARKING.
 4- SIDEWALK CROSSING THE DRIVEWAY SHALL BE MAINTAINED
 AT SIDEWALK GRADE, AND SHALL BE THE SAME MATERIAL OF
 THE SIDEWALK.
 5- CIVIL DRAWINGS AND SITE PLAN ARE NOT CONSISTENT
 REGARDING THE PORTE COCHERE APRON AND DRIVE.
 6- PROPOSED PAVER TREATMENT ALONG DIXIE HWAY WILL
 REQUIRE A MAINTENANCE AGREEMENT, WHERE THE HOTEL
 BECOMES RESPONSIBLE FOR THE MAINTENANCE OF THE PAVERS.
 7- COMPLIED-PROPOSED STOP BAR SHALL BE MOVED AWAY FROM
 THE SIDEWALK TRAVEL PATH AND INTO THE PORTE COCHERE
 AREA.
 8- COMPLIED-THE PORTE COCHERE TRAFFIC FLOW SHALL FOLLOW
 THE DIXIE HWAY DIRECTION OF TRAFFIC ( ENTRANCE ON NORTH
 DRIVEWAY, AND EXIT ON SOUTH DRIVEWAY).
 9- COMPLIED- PROPOSED CATCH BASINS CANNOT GO IN THE
 MIDDLE OF THE SIDEWALK.
 10- LANDSCAPE IN ROOFTOP TERRRACES NEED AUTHOMATIC
 IRRIGATION. THERE ARE PLANTER URNS LOCATED IN AREAS
 DIFFICULT TO REACH FOR HAND WATERING.
 11- COMPLIED- SIDEWALK ALONG DIXIE HIWAY BETWEEN THE
 TWO PORTE COCHERE DRIVEWAYS IS SHOWN HALF IN PARVER AND
 HALF IN CONCRETE. WHAT IS THE REASON FOR THAT?
 12- TREE GRATES SHALL BE INSTALLED ALONG DIXIE HWAY
 FOLLOWING THE RHYTHM AND PATTERN OF THE ONES ON THE
 WEST SIDE. PLEASE FOLLOW THE SAME PLANT MATERIALS ALSO.
 13- COMPLIED- RESTAURANT DOOR ON CLEMATIS SHALL BE
 RECESSED SO IT DOES NOT ENCROACH MORE THAN 12" INTO THE
 SIDEWALK.
 14- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH THE MINIMUM LANDSCAPE REQUIREMENTS FOR THE ROOFTOP
 GARDEN ON TOP OF THE 2ND FLOOR (TABLE IV-7).
 15. GARBAGE COLLECTION OPERATION SHALL BE APPROVED BY
 THE SANITATION DEPARTMENT. PLEASE CONTACT FERDINAND
 RIVERA AT 561-822-2076. PROVIDE APPROVAL LETTER FROM
 SANITATION.
 16. PLEASE LABEL ALL MECHANICAL ROOMS NOT COUNTED AS
 PART OF THE FAR IN THE FLOOR PLANS, AND IDENTIFIED THE
 TYPE OF MECHANICAL USE INTENDED FOR THE ROOM.
 17. PROPOSED BASE PLANTING INDICATED ON THE SIDEWALK
 BETWEEN THE TWO CURB CUTS IS NOT PERMITTED. SPACE SHALL
 BE MAINTAINED AS SIDEWALK.
 18. PLEASE SEPARATE THE LANDSCAPE DRAWINGS AND SUBMIT
 FOR LANDSCAPE PERMIT.
 19. NEW HALLWAY CONNECTING 3RD LEVEL ROOF TOP ELEVATOR
 WITH PORCH HAS RESULTED IN ADDITIONAL BLANK FACADE
 TOWARDS THE EAST.SPACE SHALL BE OPEN TO ALLOW FOR
 ARCHITECTURAL ELEMENTS. ANY ENCLOSED AREA SHALL BE
 COUNTED AS PART OF THE FAR.
 20. ACCORDING TO DAC FINAL ORDER NO. 12-01, THE PORCH
 SHALL NOT EXPAND BEYOND DIMENSIONS PRESENTED TO THE
 BOARD AT THE TIME OF THE HEARING.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-20 Cont ID  
Sent By aaponte Date 2014-08-19 Time 09:11 Rev Time 0.00
Received By aaponte Date 2014-08-19 Time 09:11 Sent To  
Notes
2015-07-14 15:27:311-THE PROPOSED HOTEL IS REQUIRED TO PURCHASE A TOTAL OF
 31,963 SF OF TDR. THE TDR TRANSFER SHALL BE APPROVED BY
 THE DAC BEFORE A BUILDING PERMIT CAN BE ISSUED.
 2- THE CALCULATION FOR THE MEZZANINE AREA SHALL BE DONE
 BASED ON THE GROSS AREA FOR THE GROUND FLOOR AND THE
 MEZZANINE. AS PROPOSED MEZZANINE AREA EXCEEDS THE
 MAXIMUM 50% OF THE GROUND LEVEL GROSS AREA, AND IT
 SHALL BE REDUCED OR IT WILL COUNT AS A FLOOR.
 3- PROPOSED LOADING AREA ALONG THE ALLEY DOES NOT HAVE
 DIMENSIONS TO WORK AS A PARALELL LOADING AREA. PARALELL
 SPACE SHALL BE AT LEAST THE MINIMUM 8 FEET REQUIRED FOR
 PARALELL PARKING.
 4- SIDEWALK CROSSING THE DRIVEWAY SHALL BE MAINTAINED
 AT SIDEWALK GRADE, AND SHALL BE THE SAME MATERIAL OF
 THE SIDEWALK.
 5- CIVIL DRAWINGS AND SITE PLAN ARE NOT CONSISTENT
 REGARDING THE PORTE COCHERE APRON AND DRIVE.
 6- PROPOSED PAVER TREATMENT ALONG DIXIE HWAY WILL
 REQUIRE A MAINTENANCE AGREEMENT, WHERE THE HOTEL
 BECOMES RESPONSIBLE FOR THE MAINTENANCE OF THE PAVERS.
 7- PROPOSED STOP BAR SHALL BE MOVED AWAY FROM THE
 SIDEWALK TRAVEL PATH AND INTO THE PORTE COCHERE AREA.
 8- THE PORTE COCHERE TRAFFIC FLOW SHALL FOLLOW THE
 DIXIE HWAY DIRECTION OF TRAFFIC ( ENTRANCE ON NORTH
 DRIVEWAY, AND EXIT ON SOUTH DRIVEWAY).
 9- PROPOSED CATCH BASINS CANNOT GO IN THE MIDDLE OF THE
 SIDEWALK.
 10- LANDSCAPE IN ROOFTOP TERRRACES NEED AUTHOMATIC
 IRRIGATION. THERE ARE PLANTER URNS LOCATED IN AREAS
 DIFFICULT TO REACH FOR HAND WATERING.
 11- SIDEWALK ALONG DIXIE HIWAY BETWEEN THE TWO PORTE
 COCHERE DRIVEWAYS IS SHOWN HALF IN PARVER AND HALF IN
 CONCRETE. WHAT IS THE REASON FOR THAT?
 12- TREE GRATES SHALL BE INSTALLED ALONG DIXIE HWAY
 FOLLOWING THE RHYTHM AND PATTERN OF THE ONES ON THE
 WEST SIDE. PLEASE FOLLOW THE SAME PLANT MATERIALS ALSO.
 13- RESTAURANT DOOR ON CLEMATIS SHALL BE RECESSED SO IT
 DOES NOT ENCROACH MORE THAN 12" INTO THE SIDEWALK.
 14- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH THE MINIMUM LANDSCAPE REQUIREMENTS FOR THE ROOFTOP
 GARDEN ON TOP OF THE 2ND FLOOR (TABLE IV-7).
 15. GARBAGE COLLECTION OPERATION SHALL BE APPROVED BY
 THE SANITATION DEPARTMENT. PLEASE CONTACT FERDINAND
 RIVERA AT 561-822-2076. PROVIDE APPROVAL LETTER FROM
 SANITATION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2014-08-19 10:52:261-THE PROPOSED HOTEL IS REQUIRED TO PURCHASE A TOTAL OF
 31,963 SF OF TDR. THE TDR TRANSFER SHALL BE APPROVED BY
 THE DAC BEFORE A BUILDING PERMIT CAN BE ISSUED.
 2- THE CALCULATION FOR THE MEZZANINE AREA SHALL BE DONE
 BASED ON THE GROSS AREA FOR THE GROUND FLOOR AND THE
 MEZZANINE. AS PROPOSED MEZZANINE AREA EXCEEDS THE
 MAXIMUM 50% OF THE GROUND LEVEL GROSS AREA, AND IT
 SHALL BE REDUCED OR IT WILL COUNT AS A FLOOR.
 3- PROPOSED LOADING AREA ALONG THE ALLEY DOES NOT HAVE
 DIMENSIONS TO WORK AS A PARALELL LOADING AREA. PARALELL
 SPACE SHALL BE AT LEAST THE MINIMUM 8 FEET REQUIRED FOR
 PARALELL PARKING.IS THE PROPOSED AREA SUFFICIENT FOR A
 HOTEL LOADING AREA?
 4- SIDEWALK CROSSING THE DRIVEWAY SHALL BE MAINTAINED
 AT SIDEWALK GRADE, AND SHALL BE THE SAME MATERIAL OF
 THE SIDEWALK.
 5- CIVIL DRAWINGS AND SITE PLAN ARE NOT CONSISTENT
 REGARDING THE PORTE COCHERE APRON AND DRIVE.
 6- PROPOSED PAVER TREATMENT ALONG DIXIE HWAY WILL
 REQUIRE A MAINTENANCE AGREEMENT, WHERE THE HOTEL
 BECOMES RESPONSIBLE FOR THE MAINTENANCE OF THE PAVERS.
 7- PROPOSED STOP BAR SHALL BE MOVED AWAY FROM THE
 SIDEWALK TRAVEL PATH AND INTO THE PORTE COCHERE AREA.
 8- THE PORTE COCHERE TRAFFIC FLOW SHALL FOLLOW THE
 DIXIE HWAY DIRECTION OF TRAFFIC ( ENTRANCE ON NORTH
 DRIVEWAY, AND EXIT ON SOUTH DRIVEWAY).
 9- PROPOSED CATCH BASINS CANNOT GO IN THE MIDDLE OF THE
 SIDEWALK.
 10- LANDSCAPE IN ROOFTOP TERRRACES NEED AUTHOMATIC
 IRRIGATION. THERE ARE PLANTER URNS LOCATED IN AREAS
 DIFFICULT TO REACH FOR HAND WATERING.
 11- SIDEWALK ALONG DIXIE HIWAY BETWEEN THE TWO PORTE
 COCHERE DRIVEWAYS IS SHOWN HALF IN PARVER AND HALF IN
 CONCRETE. WHAT IS THE REASON FOR THAT?
 12- TREE GRATES SHALL BE INSTALLED ALONG DIXIE HWAY
 FOLLOWING THE RHYTHM AND PATTERN OF THE ONES ON THE
 WEST SIDE. PLEASE FOLLOW THE SAME PLANT MATERIALS ALSO.
 13- RESTAURANT DOOR ON CLEMATIS SHALL BE RECESSES SO IT
 DOES NOT ENCROACH MORE THAN 12" INTO THE SIDEWALK.
 14- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH THE MINIMUM LANDSCAPE REQUIREMENTS FOR THE ROOFTOP
 GARDEN ON TOP OF THE 2ND FLOOR (TABLE IV-7).
 15. GARBAGE COLLECTION OPERATION SHALL BE APPROVED BY
 THE SANITATION DEPARTMENT. PLEASE CONTACT FERDINAND
 RIVERA AT 561-822-2076.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2014-07-09 14:50:237/9/14