2014-06-26 13:21:45 | DATE: 6/26/2014 |
| PROJECT: FLAGLER RESIDENCE ELECTRICAL AS BUILTS-SHEET |
| E-03 |
| PERMIT#: 13070545 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| NOTE: |
| PLAN REVEIW APPROVED FOR SHEETS E-01 AND E-02 ONLY. |
| SHEET E-03 TO BE SUBMITTED AT A LATER DATE. TAKE THE |
| FOLLOWING INTP ACCOUNT WHEN RESUBMITTING SHEET E-03 |
| |
| 1) RISER DIAGRAM NEEDS TO BE REVISED TO INDICATE THE |
| FOLLOWING: |
| A) CORRECT CONDUIT LAYOUT FOR FUTURE GENERATOR. I |
| BELIEVE THE INTENT WAS TO HAVE TWO SETS OF CONDUITS |
| FROM THE FUTURE GENERATOR. ONE SET TO EACH OF THE TWO |
| ATS'S |
| B) CORRECT GROUNDING DETAIL. CURRENTLY SHOWS UFER |
| GROUND ONLY. |
| |
| 2) THE FEEDER SCHEDULE IS UNCLEAR AND CONFLICTS WITH |
| THE RISER DIAGRAM. I SUGGEST USING EITHER A FEEDER |
| SCHEDULE OR CALL OUT EACH CONDUIT AND WIRE DETAIL ON |
| THE RISER DIAGRAM ITSELF. NOT BOTH. IF BOTH ARE USED |
| THEY NEED TO MATCH AND BE CLEAR AS TO WHICH CONDUIT |
| LOCATION IS REPRESENTED BY THE "TYPE" |
| |
| 3) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE |
| RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "A" |
| FEEDS PANEL "F" BUT IS NOT INDICATED IN THE PANEL "A" |
| SCHEDULE. |
| |
| 4) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE |
| RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "B" |
| FEEDS PANEL "E" BUT IS NOT INDICATED IN THE PANEL "B" |
| SCHEDULE. |
| |
| 5) THE RISER DIAGRAM INDICATES FOUR PANELS LOCATED IN |
| THE GARAGE. THE FLOOR PLAN INDICATES ONLY THREE. |
| CORRECT ONE OR THE OTHER. |
| |
| 6) LOAD CALCULATIONS SHALL BE INCLUDED FOR EACH PANEL |
| TO INDICATE THE PANEL PROPOSED IS ADEQUATE TO SUPPORT |
| THE LOAD. |
| |
| 7) AT LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED |
| LIGHT FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 404.1. |
| PROVIDE FIXTURE SCHEDULE. |
| |
| 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. |
| FBC-R402.4.5. PROVIDE FIXTURE SCHEDULE. |
| |
| 9) THE GROUNDING ELECTRODE SYSTEM SHALL BE INDICATED ON |
| THE RISER AS IT WILL BE INSTALLED AND AS DESCRIBED IN |
| SECTION III OF THE NEC 250 |
| |
| 10) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE |
| BUILDING NEAREST THE POINT OF SERVICE ENTRANCE IN |
| ACCORDANCE WITH NEC 230.70. PLEASE INDICATE THE |
| LOCATION OF THE ELECTRICAL SERVICE ENTRANCE AND |
| DISCONNECTING MEANS. |
| |
| 11) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE |
| MAIN SERVICE GROUND. NEC 250.94 |
| |
| 12) THE INSTALLATION OF ELECTRICAL WIRING FOR, AND |
| EQUIPMENT IN AND ADJACENT TO, NATURAL OR ARTIFICIALLY |
| MADE BODIES OF WATER NOT COVERED BY OTHER ARTICLES IN |
| THIS CODE SHALL COMPLY WITH THE PROVISIONS OF THE NEC |
| 682. |
| |
| NOTE: A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE |
| SUBMITTED INCLUDING ALL DETAILED PLANS, SHOP DRAWINGS, |
| EQUIPMENT SUBMITTALS, PRODUCT APPROVALS, ETC? IS |
| REQUIRED FOR ALL OF THE FOLLOWING: SWIMMING POOL, DOCK, |
| GENERATOR, AUDIO, VIDEO, NETWORK, SECURITY, CCTV. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR AT [email protected] |
| |