Plan Review Details - Permit 14060942
Plan Review Stops For Permit 14060942
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-08-26 Cont ID  
Sent By rmcdouga Date 2014-08-26 Time 18:42 Rev Time 0.00
Received By rmcdouga Date 2014-08-26 Time 18:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-08-25 Cont ID  
Sent By rmcdouga Date 2014-08-25 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2014-08-23 Time 10:28 Sent To Z
Notes
2014-08-25 07:45:002010 FBC
  
 DENIED BY BUILDING
  
 1) THE ROOFING INFORMATION THAT WAS SUBMITTED IS NOT
 CORRECT. THE PLANS SHOW AN INSULATED FLAT ROOF. THE
 SYSTEM THAT WAS SELECTED IS FOR A NON-INSULATED DECK.
 THE RAS 117 ENHANCED FASTENING CALCULATIONS THAT WERE
 SUBMITTED ARE FOR MECHANICALLY FASTENED INSULATION,
 HOWEVER, NONE OF THE INSULATED SYSTEMS IN NOA NO.
 14-0224.03 HAVE MECHANICALLY FASTENED INSULATION. ONLY
 THE ANCHOR SHEET NEEDS ENHANCED FASTENING. THE
 INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT
 ASPHALT. I'LL LET YOU KNOW IF THERE IS ANY THING ELSE
 THAT NEEDS TO BE CORRECTED. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-02 Cont ID  
Sent By rmcdouga Date 2014-08-02 Time 11:46 Rev Time 0.00
Received By rmcdouga Date 2014-08-02 Time 08:38 Sent To  
Notes
2014-08-02 08:54:252010 FBC
  
 DENIED BY BUILDING
  
 1) AN ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO
 FINAL INSPECTION SHOWING THAT THE NEW CONSTRUCTION AND
 EQUIPMENT IS IN COMPLIANCE WITH THE REQUIRED BASE FLOOD
 ELEVATION INCLUDING THE 6 IN FREE-BOARD. CITY
 AMENDMENTS 107.2.1
  
 2) SUBMIT TWO SETS OF AN ACCURATELY COMPLETED
 RESIDENTIAL BUILDING FORM 402 OR 405 SHOWING THAT THE
 RENOVATION AND ADDITION COMPLY WITH THE 2010 FBC ENERGY
 CONSERVATION.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS
 107.3.4.1
  
 4) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE CERTAINTEED BUR PRODUCT APPROVAL (NOA NO
 13-0204.14) WILL BE INSTALLED. SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING THAT IS REQUIRED FOR THE INCREASED PRESSURES
 OF THE PERIMETER AND CORNER AREAS FOR A 170 MPH WIND
 SPEED AND EXPOSURE 'D'. FBCR 301.1
  
 5) SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT HAVE BEEN
 REVIEWED AND ACCEPTED BY THE DESIGNER OF RECORD ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW PRIOR TO
 INSTALLATION. FBCR 301.1 & CITY AMENDMENTS 107.2.1
  
 6) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW.
 PLEASE PROVIDE A COST BREAKDOWN OR A COPY OF A SIGNED
 CONTRACT. CITY AMENDMENTS 109.3
  
 7) IN ORDER TO SPEED THE PLAN REVIEW TIMES, PLEASE
 SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By rmcdouga Date 2014-07-07 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2014-07-03 Time 17:01 Sent To  
Notes
2014-07-07 10:48:582010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 BFE OF 7' NGVD. THE CITY OF WEST PALM BEACH HAS A 6"
 FREEBOARD, WHICH REQUIRES THE LOWEST FINISH FLOOR
 ELEVATION TO BE 7.5' BFE OR HIGHER. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 REMODELED SPACE AND ADDITION. FBC ENERGY CONSERVATION
 401.2
  
 3) SHOW COMPLIANCE WITH FBCR 314 FOR SMOKE ALARMS THAT
 MEET THE REQUIREMENT OF THE CURRENT CODE.
  
 4) SHOW COMPLIANCE WITH FBCR 318.6 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS FOR BUILDINGS WITH EAVES OF
 LESS THAN 6 INCHES HORIZONTAL PROJECTION.
  
 5) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316
  
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE LAMINATED VENEER LUMBER (LVL)
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 MODIFIED BITUMEN ROOFING MATERIAL AND SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING. ( NOA NO.
 13-0424.14 IS SPECIFIED ON PLAN SHEET A.11) DCA RULE
 9N-3
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SLIDING
 GLASS DOORS, SINGLE HUNG WINDOWS, FRENCH DOORS, SIMPSON
 HANGERS AND CONNECTORS AS REQUIRED BY DCA RULE 9N-3.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.4.3.1
  
 10) SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT HAVE BEEN
 REVIEWED AND ACCEPTED BY THE DESIGNER OF RECORD ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW PRIOR TO
 INSTALLATION.
  
 11) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW.
 PLEASE PROVIDE A COST BREAKDOWN OR A COPY OF A SIGNED
 CONTRACT. CITY AMENDMENTS 109.3
  
 12) IN ORDER TO SPEED THE PLAN REVIEW TIMES, PLEASE
 SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-02 Cont ID  
Sent By rmcdouga Date 2014-08-02 Time 09:24 Rev Time 0.00
Received By rmcdouga Date 2014-08-02 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-07 Cont ID  
Sent By rmcdouga Date 2014-07-07 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2014-07-07 Time 10:03 Sent To  
Notes
2014-07-07 10:04:21SEE NOTES ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-26 Cont ID  
Sent By dkittred Date 2014-08-26 Time 18:42 Rev Time 0.00
Received By rmcdouga Date 2014-08-18 Time   Sent To  
Notes
2014-08-25 13:52:028/25/14 SENT TO RM. DK
  
2014-08-23 10:28:28SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-05 Cont ID  
Sent By dkittred Date 2014-08-05 Time 14:06 Rev Time 0.00
Received By dkittred Date 2014-07-28 Time 11:32 Sent To  
Notes
2014-07-28 12:10:56IN R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-07 Cont ID  
Sent By rmcdouga Date 2014-07-07 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2014-06-24 Time 17:39 Sent To  
Notes
2014-06-24 17:42:41R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By rmcdouga Date 2014-08-23 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2014-08-23 Time 10:29 Sent To  
Notes
2014-08-23 10:30:30MU2014-18591, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-08-02 Cont ID  
Sent By rmcdouga Date 2014-08-02 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2014-08-02 Time 09:25 Sent To  
Notes
2014-08-02 09:27:07ONE SET OF APPROVED PLANS IS REQUIRED TO BE TAKEN TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW.
 IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By rmcdouga Date 2014-07-07 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2014-07-07 Time 10:50 Sent To  
Notes
2014-07-07 10:52:29BECAUSE CONDITIONED SPACE IS BEING ADDED, THE PLANS ARE
 REQUIRED TO BE REVIEWED

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2014-08-27 Cont ID  
Sent By rmcdouga Date 2014-08-27 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2014-08-27 Time 17:30 Sent To  
Notes
2014-08-27 17:33:51THE CONTRACTOR REQUESTED THAT MECHANICAL WORK BE
 REMOVED FROM MASTER SO THAT THE MASTER PERMIT COULD BE
 ISSUED. A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-08-25 Cont ID  
Sent By rmcdouga Date 2014-08-25 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2014-08-25 Time 07:03 Sent To  
Notes
2014-08-25 07:25:222010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS ARE REQUIRED TO BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN
 PER CITY AMENDMENTS 107.2.1.
  
 2) THE PLANS SPECIFY EXPOSURE CATEGORY 'B' FOR THE ROOF
 TOP MOUNTING DETAIL. THE PROJECT IS LOCATED IN EXPOSURE
 'D'. PLEASE CORRECT. FBCR 301.1 & R301.2.1.1.3
  
 3) PRODUCT APPROVALS OR ENGINEERED DRAWINGS DETAILING
 THE FASTENING OF THE CURB TO THE ROOF AND THE UNIT TO
 THE CURB IS REQUIRED. FBCR M1307.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-08-26 Cont ID  
Sent By rmcdouga Date 2014-08-02 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2014-08-02 Time 08:38 Sent To  
Notes
2014-08-02 08:51:34A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-03 Cont ID  
Sent By rmcdouga Date 2014-07-03 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2014-07-03 Time 17:53 Sent To  
Notes
2014-07-03 18:02:472010 FBC
  
 1) THE PLANS SHOW A NEW A/C PACKAGE UNIT ON THE ROOF.
 SUBMIT TWO SETS OF MECHANICAL PLANS. SHOW ALL DUCT
 SIZES AND LOCATIONS. SPECIFY ALL GRILL SIZES AND THE
 CFM AT EACH OUTLET. CITY AMENDMENTS 107.3..5.3
  
 2) PROVIDE TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 FBCR M1401.3
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS. CITY AMENDMENTS 107.2.1
  
 4) SUBMIT TWO COPIES OF THE ENGINEERING FOR THE
 MECHANICAL EQUIPMENT ROOF STANDS. FBCRM1307.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2014-09-18 Cont ID  
Sent By shill Date 2014-09-15 Time 16:32 Rev Time 0.00
Received By shill Date 2014-09-15 Time 16:31 Sent To  
Notes
2014-09-15 16:32:10****CORRECTIONS****
 ****THIS IS A FAILED PLAN REVIEW - "N" ENTERED TO ALLOW
 CARD TO PRINT****
 ELEVATION CERTIFICATE FOR 14060942 AND 14050331,
 PREPARED BY ROBERT J. CAJAL, WALLACE SURVEYING CORP
 DATED 12/26/13
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROPERTY IS NOW OWNED BY 101 CHURCHILL ROAD LLC. AS
 DISCUSSED, PLEASE HAVE A CONTRACTOR APPLY FOR ALL OPEN
 PERMITS WHICH WERE OBTAINED UNDER THE FLORIDA STATUTE
 489 OWNER BUILDER EXEMPTION. SEE ATTORNEY GENERAL
 OPINION AGO 91-05.
  
 PRIOR TO FORM BOARD INSPECTION ("BUILDING UNDER
 CONSTRUCTION"), PLEASE CORRECT THE FOLLOWING ITEMS ON
 THE ELEVATION CERTIFICATE TO AVOID FIELD DELAYS:
  
 1. A1, A2, A3, IT IS MY UNDERSTANDING THAT THIS PARCEL
 IS UNDERGOING A REPLAT. REVISE THE INFORMATION IN THESE
 FIELDS IF APPLICABLE.
  
 2. A5, LATITUDE/LONGITUDE DOES NOT APPEAR TO BE
 CORRECT. THIS IS TO BE ACCURATE WITHIN 66' OF THE
 CENTER OF THE FRONT OF THE BUILDING.
  
 3. A8C, PLEASE PROVIDE CLARIFICATION ABOUT THE NATURE
 OF THE FLOOD VENTS AND PROVIDE CALCULATIONS OR
 INFORMATION AS TO HOW NET OPENINGS HAS BEEN DETERMINED.
 IN THE PHOTOGRAPH, THE VENT APPEARS BLOCKED. YOU MAY
 FIND THE FOLLOWING DOCUMENT HELPFUL:
  
 TECHNICAL BULLETIN 1, OPENINGS IN FOUNDATIN WALLS AND
 WALLS OF ENCLOSURES (2008)
 HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/2644
  
 VENTS ARE TO BE INSTALLED WITHIN 1' OF ADJACENT GRADE.
 PLEASE VERIFY WITH PHOTOGRAPHS. ONLY THE PORTION OF THE
 VENT WHICH IS BELOW THE BFE IS TO BE INCLUDED IN THE
 NET OPENING AREA. SEE PAGE 19 OF THE TECHNICAL
 BULLETIN; VENTS THAT CAN BE CLOSED MANUALLY OR THAT
 HAVE COVERS ARE NOT ACCEPTABLE AS FLOOD VENTS.
  
 4. B1, NFIP COMMUNITY NAME IS "CITY OF WEST PALM BEACH"
 (REMOVE "UNINCORPORATED").
  
 5. B6, FIRM INDEX DATE SHOULD BE 03/01/1979.
  
 6. C2E, AS ADVISED DURING PLAN REVIEW, MINIMUM
 ELEVATION FOR ALL EQUIPMENT SERVICING THE BUILDING IS
 7.5'. THE EQUIPMENT WHICH IS CURRENTLY 7.1' WILL BE
 REQUIRED TO BE RAISED PRIOR TO FINAL INSPECTION. IF IT
 IS NOT RAISED PRIOR TO FORM BOARD SURVEY/BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE, THIS WILL BE A
 PROVISO ITEM AT THAT TIME BUT WILL BE REQUIRED FOR
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE.
  
 7. PAGE 2, BUILDING STREET ADDRESS, PLEASE REVISE IF
 ADDRESS OF STRUCTURE HAS CHANGED.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-02 Cont ID  
Sent By rmcdouga Date 2014-08-02 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2014-08-02 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-07 Cont ID  
Sent By rmcdouga Date 2014-07-07 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2014-07-03 Time 17:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-25 Cont ID  
Sent By dkittred Date 2014-08-25 Time 13:41 Rev Time 0.00
Received By dkittred Date 2014-08-25 Time 13:28 Sent To  
Notes
2014-08-25 13:41:44PLANNING AND ZONING COMMENTS:
  
 8/25/14
  
 APPROVED - REQUIRED TREE ALTERATION PERMIT ISSUED TP
 14-1388.
  
 DANIELLE KITTREDGE, AICP
 SENIOR PLANNER
 561-822-1443
2014-08-25 11:23:518/25/14 ZONING SENT TO DK. SG

Review Stop Z ZONING
Rev No 2 Status F Date 2014-08-05 Cont ID  
Sent By dkittred Date 2014-07-31 Time 10:11 Rev Time 0.00
Received By dkittred Date 2014-07-30 Time 10:15 Sent To  
Notes
2014-08-05 11:22:04PLANNING AND ZONING COMMENTS: ***FAILED***
  
 8/5/13 - UPDATED COMMENTS
  
 1. A COMPLETE TREE ALTERATION PERMIT APPLICATION WAS
 NOT SUBMITTED. (EMAILED 8/1 AND SPOKE 8/5 WITH
 APPLICANT AND SHE IS AWARE OF WHAT NEEDS TO BE
 SUBMITTED.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  
  
2014-07-31 10:11:16PLANNING AND ZONING COMMENTS:
  
 7/31/14
  
 APPLICANT SATISFIED ALL COMMENTS EXCEPT SUBMITTAL OF A
 TREE ALTERATION PERMIT. CALLED NEYITA 7/30/14 TO LET
 KNOW THE TREE ALTERATION PERMIT NEEDS TO BE SUBMITTED
 PRIOR TO A FINAL ZONING PASS ON THE PERMIT. SHE STATED
 SHE WILL SUBMIT THE APPLICATION.
  
 NOTE: PLANS ARE BEING SENT BACK TO BUILDING (R13) FOR
 OTHERS TO REVIEW WHILE WAITING FOR THE TREE ALTERATION
 PERMIT TO BE SUBMITTED. ZONING WILL UPDATE STATUS ONCE
 APPLICATION IS SUBMITTED OR ALL OTHER REVIEWS HAVE BEEN
 COMPLETED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-25 Cont ID  
Sent By dkittred Date 2014-06-25 Time 13:33 Rev Time 0.00
Received By dkittred Date 2014-06-25 Time 12:33 Sent To  
Notes
2014-06-25 13:33:49PLANNING AND ZONING COMMENTS: ***FAILED***
  
 6/25/14
  
 1. SURVEY OF THE PROPERTY WAS NOT INCLUDED IN THE
 SUBMITTAL. PLEASE PROVIDE. DIMENSIONS AND ALL
 STRUCTURES SHOWN ON THE SITE PLAN ARE NOT CONSISTENT
 WITH THE PROPERTY AS DEPICTED ON THE PROPERTY
 APPRAISER'S WEBSITE FOR PCN 74-43-44-03-23-000-0030.
  
 2. INCLUDE SETBACKS OF NEW ADDITION ON THE SITE PLAN.
  
 3. WILL ANY TREES NEED TO BE REMOVED OR RELOCATED FOR
 CONSTRUCTION OF THE ADDITION? IF YES, THEN A TREE
 ALTERATION PERMIT WILL NEED TO BE SUBMITTED THROUGH THE
 PLANNING DIVISION.
  
 4. STAFF UNDERSTANDS THE THE SUBJECT PROPERTY IS IN THE
 PROCESS OF BEING SUBDIVIDED, HOWEVER, AS THE
 SUBDIVISION PROCESS HAS NOT YET BEEN COMPLETED THE
 BUILDING PERMIT REQUEST MUST BE REVIEWED AS THE
 PROPERTY EXISTS TODAY WHICH HAS NOT ACCURATELY BEEN
 REFLECTED ON THE BUILDING PERMIT REQUEST. IN ORDER TO
 SUBMIT THE BUILDING PERMIT UTILIZING THE LOT
 CONFIGURATION CURRENTLY BEING SHOWN ON THE PLANS, THE
 SUBDIVISION PROCESS (INCLUDING CONDITIONS OF APPROVAL)
 MUST BE COMPLETED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  