Plan Review Stops For Permit 14060942 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-08-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-26 |
Time |
18:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-26 |
Time |
18:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-25 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-23 |
Time |
10:28 |
Sent To |
Z |
|
Notes |
2014-08-25 07:45:00 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE ROOFING INFORMATION THAT WAS SUBMITTED IS NOT | | CORRECT. THE PLANS SHOW AN INSULATED FLAT ROOF. THE | | SYSTEM THAT WAS SELECTED IS FOR A NON-INSULATED DECK. | | THE RAS 117 ENHANCED FASTENING CALCULATIONS THAT WERE | | SUBMITTED ARE FOR MECHANICALLY FASTENED INSULATION, | | HOWEVER, NONE OF THE INSULATED SYSTEMS IN NOA NO. | | 14-0224.03 HAVE MECHANICALLY FASTENED INSULATION. ONLY | | THE ANCHOR SHEET NEEDS ENHANCED FASTENING. THE | | INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT | | ASPHALT. I'LL LET YOU KNOW IF THERE IS ANY THING ELSE | | THAT NEEDS TO BE CORRECTED. PLEASE CORRECT. CITY | | AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-08-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-02 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-02 |
Time |
08:38 |
Sent To |
|
|
Notes |
2014-08-02 08:54:25 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) AN ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO | | FINAL INSPECTION SHOWING THAT THE NEW CONSTRUCTION AND | | EQUIPMENT IS IN COMPLIANCE WITH THE REQUIRED BASE FLOOD | | ELEVATION INCLUDING THE 6 IN FREE-BOARD. CITY | | AMENDMENTS 107.2.1 | | | | 2) SUBMIT TWO SETS OF AN ACCURATELY COMPLETED | | RESIDENTIAL BUILDING FORM 402 OR 405 SHOWING THAT THE | | RENOVATION AND ADDITION COMPLY WITH THE 2010 FBC ENERGY | | CONSERVATION. | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE APPROVED IN | | WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS | | 107.3.4.1 | | | | 4) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | IN THE CERTAINTEED BUR PRODUCT APPROVAL (NOA NO | | 13-0204.14) WILL BE INSTALLED. SUBMIT TWO SETS OF | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING THAT IS REQUIRED FOR THE INCREASED PRESSURES | | OF THE PERIMETER AND CORNER AREAS FOR A 170 MPH WIND | | SPEED AND EXPOSURE 'D'. FBCR 301.1 | | | | 5) SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT HAVE BEEN | | REVIEWED AND ACCEPTED BY THE DESIGNER OF RECORD ARE | | REQUIRED TO BE SUBMITTED FOR REVIEW PRIOR TO | | INSTALLATION. FBCR 301.1 & CITY AMENDMENTS 107.2.1 | | | | 6) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW. | | PLEASE PROVIDE A COST BREAKDOWN OR A COPY OF A SIGNED | | CONTRACT. CITY AMENDMENTS 109.3 | | | | 7) IN ORDER TO SPEED THE PLAN REVIEW TIMES, PLEASE | | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE | | REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-07 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
17:01 |
Sent To |
|
|
Notes |
2014-07-07 10:48:58 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A | | BFE OF 7' NGVD. THE CITY OF WEST PALM BEACH HAS A 6" | | FREEBOARD, WHICH REQUIRES THE LOWEST FINISH FLOOR | | ELEVATION TO BE 7.5' BFE OR HIGHER. AN ELEVATION | | CERTIFICATE WILL BE REQUIRED. | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | REMODELED SPACE AND ADDITION. FBC ENERGY CONSERVATION | | 401.2 | | | | 3) SHOW COMPLIANCE WITH FBCR 314 FOR SMOKE ALARMS THAT | | MEET THE REQUIREMENT OF THE CURRENT CODE. | | | | 4) SHOW COMPLIANCE WITH FBCR 318.6 WHICH REQUIRES | | GUTTERS WITH DOWNSPOUTS FOR BUILDINGS WITH EAVES OF | | LESS THAN 6 INCHES HORIZONTAL PROJECTION. | | | | 5) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE | | SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316 | | | | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE LAMINATED VENEER LUMBER (LVL) | | | | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | MODIFIED BITUMEN ROOFING MATERIAL AND SIGNED AND SEALED | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING. ( NOA NO. | | 13-0424.14 IS SPECIFIED ON PLAN SHEET A.11) DCA RULE | | 9N-3 | | | | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SLIDING | | GLASS DOORS, SINGLE HUNG WINDOWS, FRENCH DOORS, SIMPSON | | HANGERS AND CONNECTORS AS REQUIRED BY DCA RULE 9N-3. | | | | 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | THE PROJECT. CITY AMENDMENTS 107.4.3.1 | | | | 10) SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT HAVE BEEN | | REVIEWED AND ACCEPTED BY THE DESIGNER OF RECORD ARE | | REQUIRED TO BE SUBMITTED FOR REVIEW PRIOR TO | | INSTALLATION. | | | | 11) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW. | | PLEASE PROVIDE A COST BREAKDOWN OR A COPY OF A SIGNED | | CONTRACT. CITY AMENDMENTS 109.3 | | | | 12) IN ORDER TO SPEED THE PLAN REVIEW TIMES, PLEASE | | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE | | REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-08-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-07 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-07 |
Time |
10:03 |
Sent To |
|
|
Notes |
2014-07-07 10:04:21 | SEE NOTES ON PLANS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-08-26 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-08-26 |
Time |
18:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-18 |
Time |
|
Sent To |
|
|
Notes |
2014-08-25 13:52:02 | 8/25/14 SENT TO RM. DK | | | 2014-08-23 10:28:28 | SENT TO R MCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-08-05 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-08-05 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-07-28 |
Time |
11:32 |
Sent To |
|
|
Notes |
2014-07-28 12:10:56 | IN R13 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-07 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-24 |
Time |
17:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2014-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-23 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-23 |
Time |
10:29 |
Sent To |
|
|
Notes |
2014-08-23 10:30:30 | MU2014-18591, NO FEES WERE DUE. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2014-08-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:25 |
Sent To |
|
|
Notes |
2014-08-02 09:27:07 | ONE SET OF APPROVED PLANS IS REQUIRED TO BE TAKEN TO | | PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. | | IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2014-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-07 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-07 |
Time |
10:50 |
Sent To |
|
|
Notes |
2014-07-07 10:52:29 | BECAUSE CONDITIONED SPACE IS BEING ADDED, THE PLANS ARE | | REQUIRED TO BE REVIEWED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
N |
Date |
2014-08-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-27 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-27 |
Time |
17:30 |
Sent To |
|
|
Notes |
2014-08-27 17:33:51 | THE CONTRACTOR REQUESTED THAT MECHANICAL WORK BE | | REMOVED FROM MASTER SO THAT THE MASTER PERMIT COULD BE | | ISSUED. A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | REQUIRED FOR MECHANICAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2014-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-25 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-25 |
Time |
07:03 |
Sent To |
|
|
Notes |
2014-08-25 07:25:22 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) THE MECHANICAL PLANS ARE REQUIRED TO BEAR THE NAME | | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN | | PER CITY AMENDMENTS 107.2.1. | | | | 2) THE PLANS SPECIFY EXPOSURE CATEGORY 'B' FOR THE ROOF | | TOP MOUNTING DETAIL. THE PROJECT IS LOCATED IN EXPOSURE | | 'D'. PLEASE CORRECT. FBCR 301.1 & R301.2.1.1.3 | | | | 3) PRODUCT APPROVALS OR ENGINEERED DRAWINGS DETAILING | | THE FASTENING OF THE CURB TO THE ROOF AND THE UNIT TO | | THE CURB IS REQUIRED. FBCR M1307.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2014-08-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-02 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-02 |
Time |
08:38 |
Sent To |
|
|
Notes |
2014-08-02 08:51:34 | A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED | | FOR MECHANICAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-07-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-03 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
17:53 |
Sent To |
|
|
Notes |
2014-07-03 18:02:47 | 2010 FBC | | | | 1) THE PLANS SHOW A NEW A/C PACKAGE UNIT ON THE ROOF. | | SUBMIT TWO SETS OF MECHANICAL PLANS. SHOW ALL DUCT | | SIZES AND LOCATIONS. SPECIFY ALL GRILL SIZES AND THE | | CFM AT EACH OUTLET. CITY AMENDMENTS 107.3..5.3 | | | | 2) PROVIDE TWO SETS OF EQUIPMENT SIZING CALCULATIONS. | | FBCR M1401.3 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS. CITY AMENDMENTS 107.2.1 | | | | 4) SUBMIT TWO COPIES OF THE ENGINEERING FOR THE | | MECHANICAL EQUIPMENT ROOF STANDS. FBCRM1307.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2014-09-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-15 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-15 |
Time |
16:31 |
Sent To |
|
|
Notes |
2014-09-15 16:32:10 | ****CORRECTIONS**** | | ****THIS IS A FAILED PLAN REVIEW - "N" ENTERED TO ALLOW | | CARD TO PRINT**** | | ELEVATION CERTIFICATE FOR 14060942 AND 14050331, | | PREPARED BY ROBERT J. CAJAL, WALLACE SURVEYING CORP | | DATED 12/26/13 | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PROPERTY IS NOW OWNED BY 101 CHURCHILL ROAD LLC. AS | | DISCUSSED, PLEASE HAVE A CONTRACTOR APPLY FOR ALL OPEN | | PERMITS WHICH WERE OBTAINED UNDER THE FLORIDA STATUTE | | 489 OWNER BUILDER EXEMPTION. SEE ATTORNEY GENERAL | | OPINION AGO 91-05. | | | | PRIOR TO FORM BOARD INSPECTION ("BUILDING UNDER | | CONSTRUCTION"), PLEASE CORRECT THE FOLLOWING ITEMS ON | | THE ELEVATION CERTIFICATE TO AVOID FIELD DELAYS: | | | | 1. A1, A2, A3, IT IS MY UNDERSTANDING THAT THIS PARCEL | | IS UNDERGOING A REPLAT. REVISE THE INFORMATION IN THESE | | FIELDS IF APPLICABLE. | | | | 2. A5, LATITUDE/LONGITUDE DOES NOT APPEAR TO BE | | CORRECT. THIS IS TO BE ACCURATE WITHIN 66' OF THE | | CENTER OF THE FRONT OF THE BUILDING. | | | | 3. A8C, PLEASE PROVIDE CLARIFICATION ABOUT THE NATURE | | OF THE FLOOD VENTS AND PROVIDE CALCULATIONS OR | | INFORMATION AS TO HOW NET OPENINGS HAS BEEN DETERMINED. | | IN THE PHOTOGRAPH, THE VENT APPEARS BLOCKED. YOU MAY | | FIND THE FOLLOWING DOCUMENT HELPFUL: | | | | TECHNICAL BULLETIN 1, OPENINGS IN FOUNDATIN WALLS AND | | WALLS OF ENCLOSURES (2008) | | HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/2644 | | | | VENTS ARE TO BE INSTALLED WITHIN 1' OF ADJACENT GRADE. | | PLEASE VERIFY WITH PHOTOGRAPHS. ONLY THE PORTION OF THE | | VENT WHICH IS BELOW THE BFE IS TO BE INCLUDED IN THE | | NET OPENING AREA. SEE PAGE 19 OF THE TECHNICAL | | BULLETIN; VENTS THAT CAN BE CLOSED MANUALLY OR THAT | | HAVE COVERS ARE NOT ACCEPTABLE AS FLOOD VENTS. | | | | 4. B1, NFIP COMMUNITY NAME IS "CITY OF WEST PALM BEACH" | | (REMOVE "UNINCORPORATED"). | | | | 5. B6, FIRM INDEX DATE SHOULD BE 03/01/1979. | | | | 6. C2E, AS ADVISED DURING PLAN REVIEW, MINIMUM | | ELEVATION FOR ALL EQUIPMENT SERVICING THE BUILDING IS | | 7.5'. THE EQUIPMENT WHICH IS CURRENTLY 7.1' WILL BE | | REQUIRED TO BE RAISED PRIOR TO FINAL INSPECTION. IF IT | | IS NOT RAISED PRIOR TO FORM BOARD SURVEY/BUILDING UNDER | | CONSTRUCTION ELEVATION CERTIFICATE, THIS WILL BE A | | PROVISO ITEM AT THAT TIME BUT WILL BE REQUIRED FOR | | "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE. | | | | 7. PAGE 2, BUILDING STREET ADDRESS, PLEASE REVISE IF | | ADDRESS OF STRUCTURE HAS CHANGED. | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-08-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-02 |
Time |
09:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-07 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
17:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2014-08-25 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-08-25 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-08-25 |
Time |
13:28 |
Sent To |
|
|
Notes |
2014-08-25 13:41:44 | PLANNING AND ZONING COMMENTS: | | | | 8/25/14 | | | | APPROVED - REQUIRED TREE ALTERATION PERMIT ISSUED TP | | 14-1388. | | | | DANIELLE KITTREDGE, AICP | | SENIOR PLANNER | | 561-822-1443 | 2014-08-25 11:23:51 | 8/25/14 ZONING SENT TO DK. SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2014-08-05 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-07-31 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-07-30 |
Time |
10:15 |
Sent To |
|
|
Notes |
2014-08-05 11:22:04 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | 8/5/13 - UPDATED COMMENTS | | | | 1. A COMPLETE TREE ALTERATION PERMIT APPLICATION WAS | | NOT SUBMITTED. (EMAILED 8/1 AND SPOKE 8/5 WITH | | APPLICANT AND SHE IS AWARE OF WHAT NEEDS TO BE | | SUBMITTED.) | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | DANIELLE J. KITTREDGE, AICP | | SENIOR PLANNER | | PLANNING & ZONING DIVISION | | PHONE: (561)-822-1443 | | EMAIL: [email protected] | | | | | | | 2014-07-31 10:11:16 | PLANNING AND ZONING COMMENTS: | | | | 7/31/14 | | | | APPLICANT SATISFIED ALL COMMENTS EXCEPT SUBMITTAL OF A | | TREE ALTERATION PERMIT. CALLED NEYITA 7/30/14 TO LET | | KNOW THE TREE ALTERATION PERMIT NEEDS TO BE SUBMITTED | | PRIOR TO A FINAL ZONING PASS ON THE PERMIT. SHE STATED | | SHE WILL SUBMIT THE APPLICATION. | | | | NOTE: PLANS ARE BEING SENT BACK TO BUILDING (R13) FOR | | OTHERS TO REVIEW WHILE WAITING FOR THE TREE ALTERATION | | PERMIT TO BE SUBMITTED. ZONING WILL UPDATE STATUS ONCE | | APPLICATION IS SUBMITTED OR ALL OTHER REVIEWS HAVE BEEN | | COMPLETED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | DANIELLE J. KITTREDGE, AICP | | SENIOR PLANNER | | PLANNING & ZONING DIVISION | | PHONE: (561)-822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-06-25 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-06-25 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-06-25 |
Time |
12:33 |
Sent To |
|
|
Notes |
2014-06-25 13:33:49 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | 6/25/14 | | | | 1. SURVEY OF THE PROPERTY WAS NOT INCLUDED IN THE | | SUBMITTAL. PLEASE PROVIDE. DIMENSIONS AND ALL | | STRUCTURES SHOWN ON THE SITE PLAN ARE NOT CONSISTENT | | WITH THE PROPERTY AS DEPICTED ON THE PROPERTY | | APPRAISER'S WEBSITE FOR PCN 74-43-44-03-23-000-0030. | | | | 2. INCLUDE SETBACKS OF NEW ADDITION ON THE SITE PLAN. | | | | 3. WILL ANY TREES NEED TO BE REMOVED OR RELOCATED FOR | | CONSTRUCTION OF THE ADDITION? IF YES, THEN A TREE | | ALTERATION PERMIT WILL NEED TO BE SUBMITTED THROUGH THE | | PLANNING DIVISION. | | | | 4. STAFF UNDERSTANDS THE THE SUBJECT PROPERTY IS IN THE | | PROCESS OF BEING SUBDIVIDED, HOWEVER, AS THE | | SUBDIVISION PROCESS HAS NOT YET BEEN COMPLETED THE | | BUILDING PERMIT REQUEST MUST BE REVIEWED AS THE | | PROPERTY EXISTS TODAY WHICH HAS NOT ACCURATELY BEEN | | REFLECTED ON THE BUILDING PERMIT REQUEST. IN ORDER TO | | SUBMIT THE BUILDING PERMIT UTILIZING THE LOT | | CONFIGURATION CURRENTLY BEING SHOWN ON THE PLANS, THE | | SUBDIVISION PROCESS (INCLUDING CONDITIONS OF APPROVAL) | | MUST BE COMPLETED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | DANIELLE J. KITTREDGE, AICP | | SENIOR PLANNER | | PLANNING & ZONING DIVISION | | PHONE: (561)-822-1443 | | EMAIL: [email protected] | | |
|
|