Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-30 Cont ID  
Sent By jwitmer Date 2014-08-30 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2014-08-30 Time 09:58 Sent To  
Notes
2014-08-30 09:59:09BUILDING PROVISO: BEDROOMS MUST MEET THESE
 REQUIREMENTS:
  
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET.
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
 R310.1.2 MINIMUM OPENING HEIGHT. THE MINIMUM NET CLEAR
 OPENING HEIGHT SHALL BE 24 INCHES (610 MM).
 R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR
 OPENING WIDTH SHALL BE 20 INCHES (508 MM).
 R313.3 SMOKE ALARMS. LOCATION
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-06-26 Cont ID  
Sent By shill Date 2014-06-26 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2014-06-26 Time 06:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 08:55 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 08:55 Sent To  
Notes
2014-09-02 09:01:04DATE: 9/2/2014
 PROJECT: BATHROOM ADDITION
 PERMIT#: MASTER 14050971, PLUMBING 14060881, REVISION
 TRACKING #14060885
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: POVISO
  
 ELECTRICAL SCOPE FOR THIS BATHROOM ADDITION COVERED
 UNDER ELECTRICAL PERMIT APPLICATION #14080935.
 ELECTRICAL PERMIT 14080935 NOT APPROVED OR ISSUED YET.
 THEREFORE THE ELECTRICAL SCOPE OF WORK INVOLVED AND
 REQUIRED FOR THIS BATHROOM ADDITION AND INSPECTIONS FOR
 SAME CANNOT PROCEED UNTILL ELECTRICAL PERMIT#14080935
 HAS BEEN ISSUED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-06-26 Cont ID  
Sent By jwitmer Date 2014-06-26 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2014-06-26 Time 06:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 10:14 Sent To P
Notes
2014-08-25 10:15:04TO J.W.'S DESK FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-26 Cont ID  
Sent By jwitmer Date 2014-06-26 Time 06:39 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 12:41 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-26 Cont ID  
Sent By jwitmer Date 2014-06-26 Time 06:39 Rev Time 0.00
Received By jwitmer Date 2014-06-26 Time 06:38 Sent To  
Notes
2014-06-26 06:57:19PLUMBING PLAN REVIEW
 REVISION: 14060885
 PERMIT: 14050971
 ADD: 640 FOREST HILL BLVD
 CONT: DURHAM BROTHERS
 TEL: (561)315-1835
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 26/ 2014
 ACTION: DENIED
  
 REVISION (1ST REVIEW) IS FOR PLUMBING UNDER THE MASTER
 PERMIT.
  
 1A) THE PLANS SHOW THE LAV AND SINK TYING INTO THE SAME
 STACK/ VENT. 2010 FBC-R P3108.2.1 HORIZONTAL WET VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 1B) P3108.1 HORIZONTAL WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL
 CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET
 VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  