Plan Review Stops For Permit 14060754 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-06-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-23 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-23 |
Time |
07:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-06-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-17 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-17 |
Time |
17:17 |
Sent To |
|
|
Notes |
2014-06-17 17:29:05 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SPECIFY WHICH ONE OF THE METHODS OF ATTACHMENT | | LISTED IN THE NOA WILL BE USED TO FASTEN THE ROOF TILE | | AND RESIST THE OVERTURN MOMENT. FBC R905.1 | | | | 2) IF AN ADHESIVE SYSTEM IS USED, SUBMIT TWO SETS OF | | PRODUCT APPROVALS FOR THE ONE THAT WILL BE USED. DCA | | RULE 9N-3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-06-23 |
|
|
Cont ID |
|
Sent By |
RM |
Date |
2014-06-23 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-20 |
Time |
12:02 |
Sent To |
B |
|
Notes |
2014-06-21 12:04:03 | TO R M'S DESK. |
|
|
|