Plan Review Details - Permit 14060739
Plan Review Stops For Permit 14060739
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-02 Cont ID  
Sent By jwitmer Date 2014-07-02 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2014-07-02 Time 12:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 16:22 Rev Time 0.00
Received By dhayes Date 2014-07-14 Time 16:22 Sent To  
Notes
2014-07-14 16:25:02DATE: 7/14/2014
 PROJECT: JOHNSON FOUNDATION
 PERMIT#: 14060739
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-19 Cont ID  
Sent By pleduc Date 2014-06-19 Time   Rev Time 0.00
Received By pleduc Date 2014-06-19 Time 13:15 Sent To  
Notes
2014-06-19 13:26:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 16:22 Rev Time 0.00
Received By dhayes Date 2014-06-17 Time 18:35 Sent To  
Notes
2014-06-18 18:36:30B19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-02 Cont ID  
Sent By jwitmer Date 2014-07-02 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2014-07-02 Time 15:03 Sent To  
Notes
2014-07-02 15:04:16EXHAUST FAN FOR SHOWER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-02 Cont ID  
Sent By jwitmer Date 2014-07-02 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2014-07-02 Time 14:52 Sent To  
Notes
***NONE***