Plan Review Details - Permit 14060339
Plan Review Stops For Permit 14060339
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-12 Cont ID  
Sent By albarran Date 2014-06-12 Time 18:23 Rev Time 0.00
Received By albarran Date 2014-06-12 Time 17:56 Sent To I
Notes
2014-06-12 18:22:52DUE TO THE DEFICIENT DRAWING, I CONTACTED THE EC TO
 DISCUSS THE SCOPE OF WORK. ACCORDING TO THE EC:
 1. THE SERVICE WIRES AND THE FEEDER TO THE FIRST
 EXTERIOR PANEL WERE STOLEN.
 2. IN THE PROCESS OF TAKING THE CONDUCTORS, THE METER
 JAWS AND THE MAIN BREAKER WERE DAMAGED.
  
 TO REPAIR THE SERVICE, THE EC WILL:
 1. REPLACE THE SERVICE CONDUCTORS W/3 2/0 CU
 2. REPLACE THE METER JAWS.
 3. REPLACE THE FEEDERS TO THE PANEL W/ 3 2/0 CU
 4. REPLACE THE MAIN BREAKER
 5. IN THE PROCESS THE GROUNDS WILL BE REPLACED AS WELL.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS
 (TAB ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-13 Cont ID  
Sent By albarran Date 2014-06-13 Time 11:52 Rev Time 0.00
Received By albarran Date   Time   Sent To PC
Notes
2014-06-13 11:54:51COMMUNITY PLUS LOCKED ME OUT LAST NIGHT WHEN DOING
 THIS, BUT THE CUSTOMER WAS IN THE OFFICE THIS MORNING
 TO PICK UP THE PERMIT AND THE SYSTEM WAS STILL LOCKED
 UP. I CREATED A SECOND I STOP IN AN ATTEMPT TO SOLVE
 THE MATTER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-06-10 10:06:37ROUTED TO ELECTRICAL LESS THAN $5000