Plan Review Details - Permit 14060310
Plan Review Stops For Permit 14060310
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-27 Cont ID  
Sent By rmcdouga Date 2014-06-27 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2014-06-27 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2014-06-11 Time 18:50 Sent To  
Notes
2014-06-11 19:03:092010 FBC
  
 ROOFING SUBMITTAL IS DENIED.
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR GAF MODIFIED ROOF SYSTEM (NOA NO.
 13-0424.14) AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE
 29 OF THE PRODUCT APPROVAL.
 THE CITY OF WEST PALM BEACH IS NOT LOCATED IN THE HIGH
 VELOCITY HURRICANE ZONE AND DOES NOT ACCEPT THE
 HIGH-VELOCITY HURRICANE ZONE UNIFORM PERMIT APPLICATION
 FORM THAT WAS SUBMITTED IN LIEU OF THE ACTUAL (ROOFING
 APPLICATION STANDARD) RAS 117 CALCULATIONS.
  
 2) THE REQUESTED CALCULATIONS ARE REQUIRED TO CONFORM
 WITH THE FORMAT SPECIFIED IN FAC 61G15-23.002 FOR
 SIGNED AND SEALED DOCUMENTS FROM A FLORIDA LICENSED
 ENGINEER BEING FILED FOR PUBLIC RECORD. FS 471
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-13 Cont ID  
Sent By rmcdouga Date 2014-06-13 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2014-06-09 Time 17:06 Sent To  
Notes
2014-06-11 17:07:10TO RM DESK
  