Plan Review Details - Permit 14060190
Plan Review Stops For Permit 14060190
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-06-30 Cont ID  
Sent By shill Date 2014-06-30 Time 12:12 Rev Time 0.00
Received By shill Date 2014-06-30 Time 12:12 Sent To  
Notes
2014-06-30 12:13:52***PROVISO****
 ***REVISION REQUIRED***
 ***ISSUED AT CONTRACTOR'S RISK***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SUBMIT A REVISED FLOOR PLAN WHICH PROVIDES THE ROOM
 DESIGNATION (SEE PREVIOUS TWO PLAN REVIEWS), FBC
 R310.4:
  
 THE MEANS OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF
 THE DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED
 WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING
 DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE
 MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 17:28 Rev Time 0.00
Received By shill Date 2014-06-20 Time 17:28 Sent To  
Notes
2014-06-20 17:31:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLEASE PROVIDE INFORMATION AS TO HOW YOU HAVE
 DETERMINED THAT THE BOTTOM SUBSTRATE IS CONCRETE. THIS
 IS TYPICALLY FILLED CELLS OR BLOCK. FBC 107
  
 2. TWO EMERGENCY MEANS OF ESCAPE WERE SHOWN ON THE
 FLOOR PLAN, FBC R310.4, BUT DID NOT INCLUDE THE ROOM
 DESIGNATION.
  
 FBC R310.4:
  
 THE MEANS OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF
 THE DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED
 WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING
 DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE
 MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-06-14 Cont ID  
Sent By shill Date 2014-06-14 Time 17:05 Rev Time 0.00
Received By shill Date 2014-06-14 Time 17:05 Sent To  
Notes
2014-06-14 17:06:04REVISION REQUIRED PRIOR TO FIRST INSPECTION
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 2. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE THE ROOM DESIGNATION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-30 Cont ID  
Sent By shill Date 2014-06-30 Time 12:14 Rev Time 0.00
Received By shill Date 2014-06-26 Time 11:59 Sent To  
Notes
2014-06-26 11:59:45SENT TO SAMANTHA'S DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 17:31 Rev Time 0.00
Received By shill Date 2014-06-17 Time   Sent To  
Notes
2014-06-17 13:32:03SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-14 Cont ID  
Sent By shill Date 2014-06-14 Time 17:06 Rev Time 0.00
Received By shill Date 2014-06-05 Time 14:56 Sent To  
Notes
2014-06-06 14:56:48SENT TO BUILDING UNDER $5000 SHELF FOR REVIEW. JG.