Plan Review Details - Permit 14060154
Plan Review Stops For Permit 14060154 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-01 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-07-01 |
Time |
09:02 |
Sent To |
|
|
Notes |
2014-07-01 09:06:24 | ADDRESS: 2400 N. FLAGLER DR WPB | | PERMIT#:14060154 | | 2ND ELECTRICAL REVIEW | | ACTION: PROVISO | | CODE: 2008 NEC AND 2010 FBC | | | | 1) CONTRACTOR TO PROVIDE ENGINEERING TO INDICATE | | COMPLIANCE WITH FBC WIND LOAD REQUIREMENTS AND | | INSTALLATION DETAILS PRIOR TO OR UPON 1ST INSPECTION. | | PER FBC AND NOTE ON SHEET E-2. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-06-05 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-06-05 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-06-05 |
Time |
08:08 |
Sent To |
|
|
Notes |
2014-06-05 11:33:38 | ADDRESS: 2400 N. FLAGLER DR WPB | | PERMIT#:14060154 | | 1ST ELECTRICAL REVIEW | | ACTION: DENIED. | | CODE: 2008 NEC AND 2010 FBC | | | | DEFICIENCIES: | | | | 1) PROVIDE VOLTAGE DROP CALCULATION ON PLANS PER FBC | | 107.2.1. | | 2) PROVIDE ENGINEERING TO INDICATE COMPLIANCE WITH FBC | | WIND LOAD REQUIREMENTS AND INSTALLATION DETAILS. PER | | FBC AND NOTE ON SHEET E-2. | | 3) ALTER DETAIL ON SHEET E-2 TO INDICATE ABOVE GRADE | | CONDUIT TO BE SCHEDULE 80 PER THE SPECIFICATION NOTE 20 | | ON THE SAME SHEET. | | 4) INDICATE BURIAL DEPTH ON PLANS PER, NEC 300.5 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-01 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-06-26 |
Time |
08:05 |
Sent To |
|
|
Notes |
2014-07-01 08:05:39 | RESUBMITTAL SENT TO DAVID'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-06-05 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-06-05 |
Time |
11:33 |
Rev Time |
|
Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2014-06-04 14:31:30 | ROUTED TO ELECTRICAL |
|
|
|