Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-19 Cont ID  
Sent By dhayes Date 2014-08-19 Time 14:28 Rev Time 0.00
Received By dhayes Date 2014-08-19 Time 14:15 Sent To  
Notes
2014-08-20 08:43:42DATE: 8/19/2014
 PROJECT: VINAS M.D.
 PERMIT#: 14060133
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 THE FEEDER WIRE IS UNDERSIZED. NEC 310.16 CORRECT SIZE
 REQUIRED. SUBJECT TO FEILD INSPECTORS APPROVAL.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-07-29 Cont ID  
Sent By dhayes Date 2014-07-29 Time 08:31 Rev Time 0.00
Received By dhayes Date 2014-07-29 Time 08:31 Sent To  
Notes
2014-07-29 09:51:35DATE: 6/21/2014
 PROJECT: L.A VINAS M.D
 PERMIT#: 14060133
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 NOTE: THE RE-SUBMITTAL IS NOT OF SUFFICIENT SIZE AND
 CLARITY TO SHOW APPROPRIATE DETAIL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. FBC 107.2.1
  
 ADDITIONALLY, REQUEST THE DENIED PACKAGE WHEN YOU
 ARRIVE TO RE-SUBMIT. REPLACE THE CORRECTED PAGES INTO
 THE SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARETIVE REVIEW. .
  
 PLEASE INCLUDE ALL THE FOLLOWING DUPLICATE COMMENTS IN
 THE RESUBMITTAL:
  
 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN
 COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW:
 WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH
 517.13(A) AND (B). NEC 517.13
 (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS
 SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT
 CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM
 OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE
 METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH
 ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING
 CONDUCTOR IN ACCORDANCE WITH 250.118.
 (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND
 NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED
 ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT
 ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100
 VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER
 EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF
 LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH
 ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING
 THESE RECEPTACLES OR FIXED EQUIPMENT.
  
 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN
 DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN
 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND.
 #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD.
 **# 6 CU IS NOT THE ADAQUATE SIZE TO USE FOR A GEC WHEN
 USING 3/0 CU SERVICE ENTRANCE CONDUCTORS.** PLEASE
 REVISE THE RISER TO THE APPROPRIATE SIZE CONDUCTOR AND
 RACEWAY TO SUPPORT THE LOAD. **RESIZE ALL THE CONDUITS
 AND CONDUCTORS ON THE LINE SIDE AND ON THE LOAD SIDE
 FEEDING THE PANEL.INCLUDING THE GROUNDING ELECTRODE
 CONDUCTOR AND THE EQUIPMENT GROUND CONDUCTORS.*
  
 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH
 PROTECTION AND FOR THE PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY.
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
 A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY
 WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT
 LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE
 GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE
 SHALL BE READILY ACCESSIBLE AND LOCATED SO THE
 OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1
 B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL
 FUNCTION ON EITHER;
 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN
 INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR
 LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND
 ARE NOT MORE THAN ONE FLOOR; OR
 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR
 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES THE AREA IS UNOCCUPIED. 505.2.2,
 C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3
  
 SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE
 ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717,
 [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By dhayes Date 2014-06-21 Time 07:25 Rev Time 0.00
Received By dhayes Date 2014-06-21 Time 15:53 Sent To  
Notes
2014-06-23 07:25:18DATE: 6/21/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN
 COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW:
 WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH
 517.13(A) AND (B). NEC 517.13
 (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS
 SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT
 CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM
 OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE
 METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH
 ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING
 CONDUCTOR IN ACCORDANCE WITH 250.118.
 (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND
 NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED
 ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT
 ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100
 VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER
 EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF
 LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH
 ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING
 THESE RECEPTACLES OR FIXED EQUIPMENT.
  
 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN
 DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN
 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND.
 #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD.
 PLEASE REVISE THE RISER TO THE APPROPRIATE SIZE
 CONDUCTOR AND RACEWAY TO SUPPORT THE LOAD.
  
 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH
 PROTECTION AND FOR THE PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY.
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
 A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY
 WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT
 LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE
 GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE
 SHALL BE READILY ACCESSIBLE AND LOCATED SO THE
 OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1
 B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL
 FUNCTION ON EITHER;
 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN
 INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR
 LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND
 ARE NOT MORE THAN ONE FLOOR; OR
 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR
 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES THE AREA IS UNOCCUPIED. 505.2.2,
 C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3
  
 SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE
 ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717,
 [email protected].

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-17 Cont ID  
Sent By pleduc Date 2014-06-17 Time   Rev Time 0.00
Received By pleduc Date 2014-06-17 Time 12:52 Sent To  
Notes
2014-06-17 13:29:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-21 Cont ID  
Sent By dhayes Date 2014-08-21 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2014-08-14 Time 12:04 Sent To  
Notes
2014-08-19 14:53:30 
  
2014-08-15 12:05:00TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-29 Cont ID  
Sent By dhayes Date 2014-07-29 Time 08:32 Rev Time 0.00
Received By dhayes Date 2014-07-17 Time 13:10 Sent To  
Notes
2014-07-17 13:11:10INCOMING SENT TO D. HAYES. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-01 Cont ID  
Sent By skennedy Date 2014-07-01 Time 11:15 Rev Time 0.00
Received By skennedy Date 2014-06-04 Time 18:22 Sent To  
Notes
2014-06-04 18:22:56INCOMING TO B13. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-18 Cont ID  
Sent By jwitmer Date 2014-06-18 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2014-06-18 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-21 Cont ID  
Sent By jwitmer Date 2014-08-21 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2014-08-21 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-07-29 Cont ID  
Sent By jwitmer Date 2014-07-29 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2014-07-29 Time 13:48 Sent To  
Notes
2014-07-29 13:56:22BUILDING PLAN REVIEW
 PERMIT: 14060133
 ADD: 550 S QUADRILLE BLVD # 100A
 CONT: MAURO BROTHERS
 TEL: (561)436-3988
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 29/ 2014
 ACTION: DENIED
  
 1) THE SUBMITTED SHEET P-1.0 & P-2.0 ARE SHEETS REDUCED
 IN SIZE, NOT TO THE CITY STANDARDS, 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-18 Cont ID  
Sent By jwitmer Date 2014-06-18 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2014-06-18 Time 13:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2014-06-23 Cont ID  
Sent By aaponte Date 2014-06-23 Time 12:02 Rev Time 0.00
Received By aaponte Date 2014-06-23 Time 12:02 Sent To  
Notes
2014-06-06 11:20:246/5/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved