Plan Review Details - Permit 14060052
Plan Review Stops For Permit 14060052
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-08 Cont ID  
Sent By rmcdouga Date 2014-12-08 Time 16:55 Rev Time 0.00
Received By rmcdouga Date 2014-12-08 Time 11:27 Sent To  
Notes
2014-12-08 15:53:54APPROVED WITH EXCEPTIONS.
 REVISED PLANS SHOWING WINDOWS THAT WILL FIT INTO THE 4
 FT. WIDE OPENING AT THE KITCHEN SINK, AS SHOWN ON THE
 ENGINEER'S DRAWINGS, ARE REQUIRED TO BE SUBMITTED AND
 APPROVED PRIOR TO FINAL INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2014-11-01 Time 09:32 Sent To  
Notes
2014-11-03 15:57:12PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE ARCHITECT WHOSE NAME APPEARS IN THE TITLE BLOCK
 ON SHEET A-1 IS REQUIRED TO SIGN, SEAL AND DATE THE
 PLAN SHEET. CHAPTER 481, FLORIDA STATUTES & 61G1
 FLORIDA ADMINISTRATIVE CODE.
  
 2) GIRDER TRUSS SF4GD IS SHOWN ON THE PLANS BEARING ON
 THE EXTERIOR WALL ABOVE THE KITCHEN WINDOWS (RE: WINDOW
 #10) ON SHEET A-1. THE TRUSS DRAWINGS SPECIFY A
 REACTION OF 2607 #. PROVIDE A STRUCTURAL DETAIL OF THIS
 WINDOW HEADER AND THE WALL FRAMING BELOW THE GIRDER AND
 SUBMIT CALCULATIONS THAT SHOW HOW THE GRAVITY LOADS AND
 REACTIONS FROM THE GIRDER TRUSS WILL BE SAFELY
 TRANSFERED TO THE FOUNDATION. FBC-R 301.1 BUILDINGS AND
 STRUCTURES, AND ALL PARTS THEREOF, SHALL BE CONSTRUCTED
 TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE
 LOADS, ROOF LOADS, FLOOD LOADS, AND WIND LOADS AS
 PRESCRIBED BY THIS CODE. THE CONSTRUCTION OF BUILDINGS
 AND STRUCTURES IN ACCORDANCE WITH THE PROVISIONS OF
 THIS CODE SHALL RESULT IN A SYSTEM THAT PROVIDES A
 COMPLETE LOAD PATH THAT MEETS ALL REQUIREMENTS FOR THE
 TRANSFER OF ALL LOADS FROM THEIR POINT OF ORIGIN
 THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
 SEE COMMENT #4 FROM THE PREVIOUS REVIEW. 4) THE TRUSS
 PLANS SPECIFY A 24" WOOD GIRDER THAT HAS THREE POINT
 BEARING. THE ARCHITECTURAL PLANS SHOW ONE END OF THIS
 GIRDER BEARING ON AN EXTERIOR WALL ABOVE THE KITCHEN
 WINDOWS. THE INTERMEDIATE BEARING POINT IS NOT
 IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE THE
 TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING. PROVIDE
 STRUCTURAL DETAILS AND SECTIONS OF THE BEARING WALLS
 THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL HOW THE
 LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED FROM THE
 ROOF TO THE FOUNDATION. FBC R301.1
  
 3) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED
 ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP
 APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER
 OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC
 61G15-30.005 & 61G15-31.003 (#5 FROM PREVIOUS REVIEW).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-22 Cont ID  
Sent By rmcdouga Date 2014-09-22 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2014-09-16 Time 07:40 Sent To  
Notes
2014-09-22 15:17:372010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR,
 EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1
  
 2) SHEET A-1 OF THE PLANS HAS WHITE-OUT IN TWO
 LOCATIONS. SIGNED AND SEALED PLANS ARE NOT ALLOWED TO
 BE ALTERED IN THIS MANNER. FBC 107.1, FS 471 AND FS 481
  
 3) PROVIDE A ROOF FRAMING PLAN THAT SPECIFIES THE
 ANCHORS/UPLIFT (ROOF TO WALL CONNECTIONS) FOR THE NEW
 ROOF TRUSSES AND GIRDERS. FBC 107.3.5.3
  
 4) THE TRUSS PLANS SPECIFY A 24" WOOD GIRDER THAT HAS
 THREE POINT BEARING. THE ARCHITECTURAL PLANS SHOW ONE
 END OF THIS GIRDER BEARING ON AN EXTERIOR WALL ABOVE
 THE KITCHEN WINDOWS. THE INTERMEDIATE BEARING POINT IS
 NOT IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE
 THE TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING.
 PROVIDE STRUCTURAL DETAILS AND SECTIONS OF THE BEARING
 WALLS THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL
 HOW THE LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED
 FROM THE ROOF TO THE FOUNDATION. FBC R301.1
  
 5) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED
 ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP
 APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER
 OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC
 61G15-30.005 & 61G15-31.003
  
 6) THE DIMENSIONS ON THE PLANS INDICATE THAT IT IS 33'
 FROM THE OUTSIDE OF THE WALLS SUPPORTING THE LONGER
 TRUSSES WHICH ARE SPECIFIED AS 32' 9" LONG (NOT
 INCLUDING THE OVERHANG). THE DIMENSIONS FOR THE OTHER
 AREA THAT IS RECEIVING THE NEW TRUSSES ARE NOT
 INDICATED ON THE PLANS.
  
 7) THE INTERIOR BEARING WALL BETWEEN THE BATHROOM AND
 BEDROOM IS NOT SPECIFIED AS SUCH ON THE PLANS. THIS
 SECTION OF WALL WAS NOT A BEARING WALL. PROVIDE DETAILS
 TO SHOW HOW IT WILL BE CONVERTED TO A BEARING WALL. FBC
 107.2.1.3
  
 8) THE COLUMN DETAIL ON SHEET A-1 IS MISSING
 INFORMATION, SUCH AS, THE POST SIZE AND WALL THICKNESS,
 THE WELD TYPES AT END PLATES, THE LENGTH / EMBED DEPTH
 OF THE ANCHOR AND LAG BOLTS. ALSO, IT IS NOT CLEAR ON
 THE PLANS WHAT THIS COLUMN IS SUPPORTING. FBC 107.2.1 &
 107.2.1.3
  
 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 POLYFOAM ROOF TILE ADHESIVE AS REQUIRED BY DCA RULE
 9N-3.
  
 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 11) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR
 THE TANK-LESS GAS WATER HEATER LOCATED IN THE UTILITY
 CLOSET. FBCR G2407 (304) THIS COMMENT NEEDS TO BE
 ADDRESSED BEFORE THIS PERMIT IS ISSUED. THE MECHANICAL
 PLANS CALL FOR A LOUVERED DOOR TO THIS ROOM AND THE
 DOOR SCHEDULE ON THE ARCHITECTURAL PLANS SPECIFY A
 SOLID DOOR. SEE MECHANICAL COMMENTS.
  
 12) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 405.4.2
  
 IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE
 REVIEW COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-24 Cont ID  
Sent By rmcdouga Date 2014-06-24 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2014-06-21 Time 09:35 Sent To  
Notes
2014-06-21 12:17:162010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. SPECIFY
 WIND SPEED AND EXPOSURE CATEGORY. ( 170 MPH, EXPOSURE C
 ) FBC R301.2.1
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR OPENINGS WHERE THE NEW WINDOWS AND EXTERIOR
 DOORS WILL BE INSTALLED. FBC R301.2.1
  
 3) SPECIFY THE SIZE OF THE NEW OVERHEAD GARAGE DOOR ON
 THE PLANS. FBC R301.2.1
  
 4) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR,
 EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1
  
 5) SUBMIT TWO SETS OF STRUCTURAL PLANS AND DETAILS FOR
 THE ROOF TRUSSES AND GIRDER. FBC R801.2
  
 6) PROVIDE AN ELEVATION PLAN FOR THE ROOF SHOWING THE
 ROOF SLOPE. CITY AMENDMENTS 107.2.1 & FBC R301.2.1
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS AS REQUIRED BY DCA RULE 9N-3.
  
 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 9) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR
 THE TANKLESS GAS WATER HEATER LOCATED IN THE UTILITY
 CLOSET. FBCR G2407 (304)
  
 10) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 405.4.2
  
 11) FLORIDA PRODUCT APPROVAL FL1112-R3 WAS SUBMITTED
 FOR A SINGLE OUTSWING DOOR. PLEASE CLARIFY THE DOOR
 THAT THIS APPROVAL IS FOR. CITY AMENDMENTS 107.2.1
  
 12) A PGT DIRECTORY WITH PGT SH 400/500 WINDOWS
 HI-LIGHTED WAS SUBMITTED. THIS IS NOT A PRODUCT
 APPROVAL. IF YOU WISH TO USE THIS PRODUCT IN ADDITION
 TO THE PGT 700 SERIES SH WINDOWS, SUBMIT TWO COPIES OF
 THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3.
  
 13) AT THE BOTTOM OF SHEET A-1 THERE IS A NOTE THAT
 READS DESIGNER OF RECORD WITH A BLANK SPACE AND THE
 NAME JOHN A. PAGLIARULO PRINTED BELOW. PLEASE REMOVE
 THIS FROM THE PLANS. THE DESIGNER OF RECORD IS THE
 ARCHITECT THAT SIGNED AND SEALED THE PLANS. FS 481
  
 14) IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE
 REVIEW COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-10-28 Cont ID  
Sent By dhayes Date 2014-10-28 Time 14:23 Rev Time 0.00
Received By dhayes Date 2014-10-28 Time 13:56 Sent To B
Notes
2014-10-28 14:55:11TO RM'S DESK
  
  
2014-10-28 14:14:2010/28/2014
 PROJECT: 249 ALPINE RD
 PERMIT#: 14060052
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
  
 PROVIDE REVISED PLANS TO INDICATE COMPLIANCE WITH THE
 FOLLOWING TWO ITEMS PRIOR TO ROUGH INSPECTION:
 1) INDICATE LOCATION OF ELECTRICAL PANELS. THE PLAN
 NOTES THE LOCATION TO BE IN THE UTILITY RM BUT THERE IS
 NO INDICATION OF AN ELECTRICAL PANEL IN THE UTILITY RM.
 THE LOCATION MUST SHOW COMPLIANCE WITH THE
 NEC 110.26
  
 2) THE LOAD CALCULATION AND PANEL SCHEDULES INDICATE
 THE EXISTANCE OF "SUB-PANEL A". INDICATE THE LOCATION
 OF SUB-PANEL A ON THE FLOOR PLAN AND HOW SUB-PANEL A IS
 FED AND WITH WHAT ON A REVISED RISER DIAGRAM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-10 Cont ID  
Sent By dhayes Date 2014-09-10 Time 10:49 Rev Time 0.00
Received By dhayes Date 2014-09-10 Time 10:48 Sent To  
Notes
2014-09-10 11:26:22DATE: 9/10/2014
 PROJECT: 249 ALPINE RD
 PERMIT#: 14060052
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) A RISER DIAGRAM IS REQUIRED TO INDICATE THE LOCATION
 OF THE SERVICE ENTRANCE DISCONNECTING MEANS. PROVIDE A
 MAIN SERVICE DISCONNECT AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS. NEC 230.70, NEC 215.5, WPB AMENDMENTS TO
 THE FBC 107.3.5,
  
 2) A PANEL SCHEDULE IS REQUIRED TO INDICATE THE CIRCUIT
 OCPD SIZE AND CIRCUIT NUMBER. FLOOR PLAN TO BE
 IDENTIFIED WITH THE CIRCUIT NUMBERS CORESPONDING TO THE
 PANEL SCHEDULE IN ORDER TO DETERMINE THE CIRCUIT AND
 WIRE SIZES CORESPONDING TO THE OUTLET OR EQUIPMENT
 CONNECTED. NEC 215.5, WPB AMENDMENTS TO THE FBC 107.3.5
  
 3) CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF
 SLEEPING AREA. FBC 315
  
 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED INCLUDING THE GDO OUTLET.
  
 5) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION
 210.11 (C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 6) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B). VERIFY THIS CRITERIA IS MET IN ALL CLOTHES CLOSETS
 WITH LUMINAIRES.
  
 7) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT
 TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF
 SUCH EQUIPMENT. NEC 110.26
 VERIFY THIS CRITERIA IS MET AT THE ELECTRICAL PANEL IN
 THE HALLWAY ENTRANCE AND AT ALL ELECTRICAL EQUIPMENT
 REQUIRING ACCESS FOR SERVICE AND MAINTENANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By albarran Date 2014-06-11 Time 16:14 Rev Time 0.00
Received By albarran Date 2014-06-11 Time 15:53 Sent To  
Notes
2014-06-11 16:17:44ELECTRICAL REVIEW PASSED WITH NOTATION. ARCHITECTURAL
 DRAWING SCALE WAS NOT IDENTIFIED THEREFORE PROPER
 OUTLET PLACEMENT IS NOT PRACTICABLE SO A NOT AS TO THE
 REQUIREMENTS WAS INCLUDED. RETURNED TO BIN "R5"
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-06-21 Cont ID  
Sent By rmcdouga Date 2014-06-21 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2014-06-21 Time 10:41 Sent To  
Notes
2014-06-21 10:45:38NO GAS PERMIT APPLICATION OR PLANS WERE SUBMITTED. A
 SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-08 Cont ID  
Sent By rmcdouga Date 2014-12-08 Time 16:55 Rev Time 0.00
Received By rmcdouga Date 2014-11-19 Time 16:45 Sent To  
Notes
2014-11-20 16:45:53RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2014-10-23 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-22 Cont ID  
Sent By rmcdouga Date 2014-09-22 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2014-09-09 Time 10:07 Sent To  
Notes
2014-09-10 10:06:51R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-24 Cont ID  
Sent By rmcdouga Date 2014-06-24 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2014-06-02 Time 11:08 Sent To  
Notes
2014-06-03 11:11:38****EXPEDITED****
 R05
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 10:11 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 10:10 Sent To  
Notes
2014-09-10 10:13:20PBC REVIEW COMPLETE. STAMP IS ON SHEET A-1 HOWEVER A
 NEW A-1 HAS BEEN SUBMITTED. PLEASE RETAIN THE THE OLD
 SHEET.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-21 Cont ID  
Sent By rmcdouga Date 2014-06-21 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2014-06-21 Time 10:34 Sent To  
Notes
2014-06-21 10:36:18ONE SET OF THE APPROVED PLANS IS REQUIRED TO BE
 REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY
 IMPACT FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2014-11-04 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-09-16 Cont ID  
Sent By rmcdouga Date 2014-09-16 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2014-09-16 Time 10:06 Sent To  
Notes
2014-09-16 10:13:21PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) FBC-R M1602.2 PROHIBITED SOURCES.
  
 OUTDOOR AND RETURN AIR FOR A FORCED-AIR HEATING OR
 COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING
 LOCATIONS:
 2. WHERE FLAMMABLE VAPORS ARE PRESENT; OR WHERE LOCATED
 LESS THAN 10 FEET (3048 MM) ABOVE THE SURFACE OF ANY
 ABUTTING PUBLIC WAY OR DRIVEWAY; OR WHERE LOCATED AT
 GRADE LEVEL BY A SIDEWALK, STREET, ALLEY OR DRIVEWAY.
 5. A ROOM OR SPACE CONTAINING A FUEL-BURNING APPLIANCE
 WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE SOURCE OF
 RETURN AIR.
 EXEPTIONS:
 1. THE FUEL-BURNING APPLIANCE IS A DIRECT-VENT
 APPLIANCE OR AN APPLIANCE NOT REQUIRING A VENT IN
 ACCORDANCE WITH SECTION M1801.1 OR CHAPTER 24.
 2. THE ROOM OR SPACE COMPLIES WITH THE FOLLOWING
 REQUIREMENTS:
 2.1. THE RETURN AIR SHALL BE TAKEN FROM A ROOM OR SPACE
 HAVING A VOLUME EXCEEDING 1 CUBIC FOOT FOR EACH 10
 BTU/H (9.6 L/W) OF COMBINED INPUT RATING OF ALL
 FUEL-BURNING APPLIANCES THEREIN.
 2.2. THE VOLUME OF SUPPLY AIR DISCHARGED BACK INTO THE
 SAME SPACE SHALL BE APPROXIMATELY EQUAL TO THE VOLUME
 OF RETURN AIR TAKEN FROM THE SPACE.
 2.3. RETURN-AIR INLETS SHALL NOT BE LOCATED WITHIN 10
 FEET (3048 MM) OF ANY APPLIANCE FIREBOX OR DRAFT HOOD
 IN THE SAME ROOM OR SPACE.
  
 THE UTILITY ROOM IN WHICH THE AIR HANDLER IS LOCATED
 CONTAINS A TANKLESS GAS WATER HEATER. THE MECHANICAL
 PLANS SPECIFY A LOUVERED DOOR SO THAT RETURN AIR CAN
 ENTER THE ROOM MAKING THE ROOM CONTAINING THE GAS WATER
 HEATER A PLENUM. ( THE DOOR SCHEDULE ON THE FLOOR PLANS
 SPECIFY A HOLLOW CORE DOOR. )
  
 2) SUBMIT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 AND CONDITIONS OF THE LISTING FOR THE TANKLESS GAS
 WATER HEATER. FBC R G2406 (303.1)
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By jsaez Date 2014-06-05 Time 15:13 Rev Time 0.00
Received By jsaez Date 2014-06-05 Time 15:13 Sent To  
Notes
2014-06-05 15:15:231.PROVIDE MECHANCIAL PLANS.1. PROVIDE A.H.U./ C.U.
 DETAIL, SCHEDULES.
 2. CHASE OUT 14" DN. TO GRD. FLR.
 3. NO R/A THRU BED.RM # 2 FROM A.H.U.- 2
 4. MINI SPLIT SHON ON PLANS.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-10-28 Cont ID  
Sent By tklarge Date 2014-10-28 Time 04:50 Rev Time 0.00
Received By tklarge Date 2014-10-28 Time 04:50 Sent To  
Notes
2014-10-28 04:52:03****PROVISO****
 REVISED SANITARY RISER TO BE SUBMITTED FOR REVIEW AND
 APPROVAL PRIOR TO GROUND ROUGH INSPECTION.
 GAS TO BE UNDER SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-13 Cont ID  
Sent By tklarge Date 2014-09-13 Time   Rev Time 0.00
Received By tklarge Date 2014-09-13 Time   Sent To  
Notes
2014-09-13 07:15:57****PROVISO****
 REVISED SANITARY RISER TO BE SUBMITTED FOR REVIEW AND
 APPROVAL PRIOR TO GROUND ROUGH INSPECTION.
 GAS TO BE UNDER SEPARATE PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-21 Cont ID  
Sent By rmcdouga Date 2014-06-21 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2014-06-21 Time 09:35 Sent To  
Notes
2014-06-21 10:34:452010 FBC
  
 PLUMBING IS DENIED
  
 1) THE RISER DIAGRAM IS DRAWN INCORRECTLY AND DOES NOT
 MATCH THE PLANS. ALL OF THE FIXTURE DRAINS ( EXCEPT THE
 KITCHEN SINK ) ARE SHOWN CONNECTED TO THE VERTICAL VENT
 PIPING. FBCR P3101.2.1 SUBMIT CORRECTED DRAWINGS.
  
 2) THE EXISTING BATH DRAIN AND VENT PIPING NEEDS TO BE
 SHOWN ON THE FLOOR AND RISER PLANS. CITY AMENDMENTS
 107.1
  
 3) THE MAXIMUM DISTANCE OF THE TRAP TO THE VENT HAS
 BEEN EXCEEDED AT THE LAVATORY IN THE MASTER BATH. FBCR
 P3105.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-12-08 Cont ID  
Sent By rmcdouga Date 2014-12-08 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2014-12-08 Time 16:49 Sent To  
Notes
2014-12-08 16:55:32ROOFING MATERIAL
  
 GALENA SPANISH "S" CONCRETE TILE NOA 10-0518.04
 TILE BOND ROOF TILE ADHESIVE NOA 11-0616.03
 CERTAINTEED MODIFIED BITUMEN FL 16709

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By llouie Date 2014-09-12 Time 11:36 Rev Time 0.00
Received By llouie Date 2014-09-12 Time 11:36 Sent To  
Notes
2014-09-12 11:37:41NOTE: INTERIOR MODIFICATIONS TO PRIMARY STRUCTURE ONLY;
 NO CHANGE TO EXISTING BUILDING FOOTPRINT.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By llouie Date 2014-06-06 Time 17:43 Rev Time 0.00
Received By llouie Date 2014-06-06 Time 17:43 Sent To  
Notes
2014-06-06 17:45:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($162,00) EXCEEDS 50
 PERCENT OF THE STRUCTURE'S VALUE ($90,290) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY WITH THE
 PROPOSED LOCATION OF THE A/C UNIT(S).
  
 3.) WILL THE PROPOSED GAS FIREPLACE REQUIRE A CHIMNEY?
 IF SO, ARCHITECTURAL ELEVATIONS WILL NEED TO BE
 PROVIDED.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
2014-06-06 11:05:566/5/14