Plan Review Stops For Permit 14060052 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-12-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-08 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-12-08 |
Time |
11:27 |
Sent To |
|
|
Notes |
2014-12-08 15:53:54 | APPROVED WITH EXCEPTIONS. | | REVISED PLANS SHOWING WINDOWS THAT WILL FIT INTO THE 4 | | FT. WIDE OPENING AT THE KITCHEN SINK, AS SHOWN ON THE | | ENGINEER'S DRAWINGS, ARE REQUIRED TO BE SUBMITTED AND | | APPROVED PRIOR TO FINAL INSPECTION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-11-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-11-01 |
Time |
09:32 |
Sent To |
|
|
Notes |
2014-11-03 15:57:12 | PLAN REVIEW COMMENTS | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) THE ARCHITECT WHOSE NAME APPEARS IN THE TITLE BLOCK | | ON SHEET A-1 IS REQUIRED TO SIGN, SEAL AND DATE THE | | PLAN SHEET. CHAPTER 481, FLORIDA STATUTES & 61G1 | | FLORIDA ADMINISTRATIVE CODE. | | | | 2) GIRDER TRUSS SF4GD IS SHOWN ON THE PLANS BEARING ON | | THE EXTERIOR WALL ABOVE THE KITCHEN WINDOWS (RE: WINDOW | | #10) ON SHEET A-1. THE TRUSS DRAWINGS SPECIFY A | | REACTION OF 2607 #. PROVIDE A STRUCTURAL DETAIL OF THIS | | WINDOW HEADER AND THE WALL FRAMING BELOW THE GIRDER AND | | SUBMIT CALCULATIONS THAT SHOW HOW THE GRAVITY LOADS AND | | REACTIONS FROM THE GIRDER TRUSS WILL BE SAFELY | | TRANSFERED TO THE FOUNDATION. FBC-R 301.1 BUILDINGS AND | | STRUCTURES, AND ALL PARTS THEREOF, SHALL BE CONSTRUCTED | | TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE | | LOADS, ROOF LOADS, FLOOD LOADS, AND WIND LOADS AS | | PRESCRIBED BY THIS CODE. THE CONSTRUCTION OF BUILDINGS | | AND STRUCTURES IN ACCORDANCE WITH THE PROVISIONS OF | | THIS CODE SHALL RESULT IN A SYSTEM THAT PROVIDES A | | COMPLETE LOAD PATH THAT MEETS ALL REQUIREMENTS FOR THE | | TRANSFER OF ALL LOADS FROM THEIR POINT OF ORIGIN | | THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION. | | SEE COMMENT #4 FROM THE PREVIOUS REVIEW. 4) THE TRUSS | | PLANS SPECIFY A 24" WOOD GIRDER THAT HAS THREE POINT | | BEARING. THE ARCHITECTURAL PLANS SHOW ONE END OF THIS | | GIRDER BEARING ON AN EXTERIOR WALL ABOVE THE KITCHEN | | WINDOWS. THE INTERMEDIATE BEARING POINT IS NOT | | IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE THE | | TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING. PROVIDE | | STRUCTURAL DETAILS AND SECTIONS OF THE BEARING WALLS | | THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL HOW THE | | LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED FROM THE | | ROOF TO THE FOUNDATION. FBC R301.1 | | | | 3) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED | | ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY | | THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP | | APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER | | OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC | | 61G15-30.005 & 61G15-31.003 (#5 FROM PREVIOUS REVIEW). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-09-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-22 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-16 |
Time |
07:40 |
Sent To |
|
|
Notes |
2014-09-22 15:17:37 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR, | | EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1 | | | | 2) SHEET A-1 OF THE PLANS HAS WHITE-OUT IN TWO | | LOCATIONS. SIGNED AND SEALED PLANS ARE NOT ALLOWED TO | | BE ALTERED IN THIS MANNER. FBC 107.1, FS 471 AND FS 481 | | | | 3) PROVIDE A ROOF FRAMING PLAN THAT SPECIFIES THE | | ANCHORS/UPLIFT (ROOF TO WALL CONNECTIONS) FOR THE NEW | | ROOF TRUSSES AND GIRDERS. FBC 107.3.5.3 | | | | 4) THE TRUSS PLANS SPECIFY A 24" WOOD GIRDER THAT HAS | | THREE POINT BEARING. THE ARCHITECTURAL PLANS SHOW ONE | | END OF THIS GIRDER BEARING ON AN EXTERIOR WALL ABOVE | | THE KITCHEN WINDOWS. THE INTERMEDIATE BEARING POINT IS | | NOT IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE | | THE TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING. | | PROVIDE STRUCTURAL DETAILS AND SECTIONS OF THE BEARING | | WALLS THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL | | HOW THE LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED | | FROM THE ROOF TO THE FOUNDATION. FBC R301.1 | | | | 5) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED | | ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY | | THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP | | APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER | | OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC | | 61G15-30.005 & 61G15-31.003 | | | | 6) THE DIMENSIONS ON THE PLANS INDICATE THAT IT IS 33' | | FROM THE OUTSIDE OF THE WALLS SUPPORTING THE LONGER | | TRUSSES WHICH ARE SPECIFIED AS 32' 9" LONG (NOT | | INCLUDING THE OVERHANG). THE DIMENSIONS FOR THE OTHER | | AREA THAT IS RECEIVING THE NEW TRUSSES ARE NOT | | INDICATED ON THE PLANS. | | | | 7) THE INTERIOR BEARING WALL BETWEEN THE BATHROOM AND | | BEDROOM IS NOT SPECIFIED AS SUCH ON THE PLANS. THIS | | SECTION OF WALL WAS NOT A BEARING WALL. PROVIDE DETAILS | | TO SHOW HOW IT WILL BE CONVERTED TO A BEARING WALL. FBC | | 107.2.1.3 | | | | 8) THE COLUMN DETAIL ON SHEET A-1 IS MISSING | | INFORMATION, SUCH AS, THE POST SIZE AND WALL THICKNESS, | | THE WELD TYPES AT END PLATES, THE LENGTH / EMBED DEPTH | | OF THE ANCHOR AND LAG BOLTS. ALSO, IT IS NOT CLEAR ON | | THE PLANS WHAT THIS COLUMN IS SUPPORTING. FBC 107.2.1 & | | 107.2.1.3 | | | | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | POLYFOAM ROOF TILE ADHESIVE AS REQUIRED BY DCA RULE | | 9N-3. | | | | 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | 11) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR | | THE TANK-LESS GAS WATER HEATER LOCATED IN THE UTILITY | | CLOSET. FBCR G2407 (304) THIS COMMENT NEEDS TO BE | | ADDRESSED BEFORE THIS PERMIT IS ISSUED. THE MECHANICAL | | PLANS CALL FOR A LOUVERED DOOR TO THIS ROOM AND THE | | DOOR SCHEDULE ON THE ARCHITECTURAL PLANS SPECIFY A | | SOLID DOOR. SEE MECHANICAL COMMENTS. | | | | 12) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE | | SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | 405.4.2 | | | | IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE | | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE | | REVIEW COMMENTS WAS ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-06-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-24 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-21 |
Time |
09:35 |
Sent To |
|
|
Notes |
2014-06-21 12:17:16 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. SPECIFY | | WIND SPEED AND EXPOSURE CATEGORY. ( 170 MPH, EXPOSURE C | | ) FBC R301.2.1 | | | | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE | | EXTERIOR OPENINGS WHERE THE NEW WINDOWS AND EXTERIOR | | DOORS WILL BE INSTALLED. FBC R301.2.1 | | | | 3) SPECIFY THE SIZE OF THE NEW OVERHEAD GARAGE DOOR ON | | THE PLANS. FBC R301.2.1 | | | | 4) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR, | | EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1 | | | | 5) SUBMIT TWO SETS OF STRUCTURAL PLANS AND DETAILS FOR | | THE ROOF TRUSSES AND GIRDER. FBC R801.2 | | | | 6) PROVIDE AN ELEVATION PLAN FOR THE ROOF SHOWING THE | | ROOF SLOPE. CITY AMENDMENTS 107.2.1 & FBC R301.2.1 | | | | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | ROOFING MATERIALS AS REQUIRED BY DCA RULE 9N-3. | | | | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | 9) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR | | THE TANKLESS GAS WATER HEATER LOCATED IN THE UTILITY | | CLOSET. FBCR G2407 (304) | | | | 10) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE | | SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | 405.4.2 | | | | 11) FLORIDA PRODUCT APPROVAL FL1112-R3 WAS SUBMITTED | | FOR A SINGLE OUTSWING DOOR. PLEASE CLARIFY THE DOOR | | THAT THIS APPROVAL IS FOR. CITY AMENDMENTS 107.2.1 | | | | 12) A PGT DIRECTORY WITH PGT SH 400/500 WINDOWS | | HI-LIGHTED WAS SUBMITTED. THIS IS NOT A PRODUCT | | APPROVAL. IF YOU WISH TO USE THIS PRODUCT IN ADDITION | | TO THE PGT 700 SERIES SH WINDOWS, SUBMIT TWO COPIES OF | | THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3. | | | | 13) AT THE BOTTOM OF SHEET A-1 THERE IS A NOTE THAT | | READS DESIGNER OF RECORD WITH A BLANK SPACE AND THE | | NAME JOHN A. PAGLIARULO PRINTED BELOW. PLEASE REMOVE | | THIS FROM THE PLANS. THE DESIGNER OF RECORD IS THE | | ARCHITECT THAT SIGNED AND SEALED THE PLANS. FS 481 | | | | 14) IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE | | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE | | REVIEW COMMENTS WAS ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2014-10-28 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-10-28 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-10-28 |
Time |
13:56 |
Sent To |
B |
|
Notes |
2014-10-28 14:55:11 | TO RM'S DESK | | | | | 2014-10-28 14:14:20 | 10/28/2014 | | PROJECT: 249 ALPINE RD | | PERMIT#: 14060052 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 3RD ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | | | PROVIDE REVISED PLANS TO INDICATE COMPLIANCE WITH THE | | FOLLOWING TWO ITEMS PRIOR TO ROUGH INSPECTION: | | 1) INDICATE LOCATION OF ELECTRICAL PANELS. THE PLAN | | NOTES THE LOCATION TO BE IN THE UTILITY RM BUT THERE IS | | NO INDICATION OF AN ELECTRICAL PANEL IN THE UTILITY RM. | | THE LOCATION MUST SHOW COMPLIANCE WITH THE | | NEC 110.26 | | | | 2) THE LOAD CALCULATION AND PANEL SCHEDULES INDICATE | | THE EXISTANCE OF "SUB-PANEL A". INDICATE THE LOCATION | | OF SUB-PANEL A ON THE FLOOR PLAN AND HOW SUB-PANEL A IS | | FED AND WITH WHAT ON A REVISED RISER DIAGRAM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-09-10 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-10 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-10 |
Time |
10:48 |
Sent To |
|
|
Notes |
2014-09-10 11:26:22 | DATE: 9/10/2014 | | PROJECT: 249 ALPINE RD | | PERMIT#: 14060052 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) A RISER DIAGRAM IS REQUIRED TO INDICATE THE LOCATION | | OF THE SERVICE ENTRANCE DISCONNECTING MEANS. PROVIDE A | | MAIN SERVICE DISCONNECT AT A READILY ACCESSIBLE | | LOCATION NEAREST THE POINT OF ENTRANCE OF THE SERVICE | | CONDUCTORS. NEC 230.70, NEC 215.5, WPB AMENDMENTS TO | | THE FBC 107.3.5, | | | | 2) A PANEL SCHEDULE IS REQUIRED TO INDICATE THE CIRCUIT | | OCPD SIZE AND CIRCUIT NUMBER. FLOOR PLAN TO BE | | IDENTIFIED WITH THE CIRCUIT NUMBERS CORESPONDING TO THE | | PANEL SCHEDULE IN ORDER TO DETERMINE THE CIRCUIT AND | | WIRE SIZES CORESPONDING TO THE OUTLET OR EQUIPMENT | | CONNECTED. NEC 215.5, WPB AMENDMENTS TO THE FBC 107.3.5 | | | | 3) CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF | | SLEEPING AREA. FBC 315 | | | | 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI | | PROTECTED INCLUDING THE GDO OUTLET. | | | | 5) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION | | 210.11 (C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO | | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS | | OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT | | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. | | | | 6) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN | | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND | | (B). VERIFY THIS CRITERIA IS MET IN ALL CLOTHES CLOSETS | | WITH LUMINAIRES. | | | | 7) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE | | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT | | TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF | | SUCH EQUIPMENT. NEC 110.26 | | VERIFY THIS CRITERIA IS MET AT THE ELECTRICAL PANEL IN | | THE HALLWAY ENTRANCE AND AT ALL ELECTRICAL EQUIPMENT | | REQUIRING ACCESS FOR SERVICE AND MAINTENANCE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-06-11 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-06-11 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-06-11 |
Time |
15:53 |
Sent To |
|
|
Notes |
2014-06-11 16:17:44 | ELECTRICAL REVIEW PASSED WITH NOTATION. ARCHITECTURAL | | DRAWING SCALE WAS NOT IDENTIFIED THEREFORE PROPER | | OUTLET PLACEMENT IS NOT PRACTICABLE SO A NOT AS TO THE | | REQUIREMENTS WAS INCLUDED. RETURNED TO BIN "R5" | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2014-06-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-21 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-21 |
Time |
10:41 |
Sent To |
|
|
Notes |
2014-06-21 10:45:38 | NO GAS PERMIT APPLICATION OR PLANS WERE SUBMITTED. A | | SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-12-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-08 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-11-19 |
Time |
16:45 |
Sent To |
|
|
Notes |
2014-11-20 16:45:53 | RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-11-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-10-23 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-09-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-22 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-09 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-06-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-24 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-02 |
Time |
11:08 |
Sent To |
|
|
Notes |
2014-06-03 11:11:38 | ****EXPEDITED**** | | R05 | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2014-09-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-09-10 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-09-10 |
Time |
10:10 |
Sent To |
|
|
Notes |
2014-09-10 10:13:20 | PBC REVIEW COMPLETE. STAMP IS ON SHEET A-1 HOWEVER A | | NEW A-1 HAS BEEN SUBMITTED. PLEASE RETAIN THE THE OLD | | SHEET. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2014-06-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-21 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-21 |
Time |
10:34 |
Sent To |
|
|
Notes |
2014-06-21 10:36:18 | ONE SET OF THE APPROVED PLANS IS REQUIRED TO BE | | REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY | | IMPACT FEES ARE DUE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2014-11-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-11-04 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2014-09-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-16 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-16 |
Time |
10:06 |
Sent To |
|
|
Notes |
2014-09-16 10:13:21 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | MECHANICAL | | | | 1) FBC-R M1602.2 PROHIBITED SOURCES. | | | | OUTDOOR AND RETURN AIR FOR A FORCED-AIR HEATING OR | | COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING | | LOCATIONS: | | 2. WHERE FLAMMABLE VAPORS ARE PRESENT; OR WHERE LOCATED | | LESS THAN 10 FEET (3048 MM) ABOVE THE SURFACE OF ANY | | ABUTTING PUBLIC WAY OR DRIVEWAY; OR WHERE LOCATED AT | | GRADE LEVEL BY A SIDEWALK, STREET, ALLEY OR DRIVEWAY. | | 5. A ROOM OR SPACE CONTAINING A FUEL-BURNING APPLIANCE | | WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE SOURCE OF | | RETURN AIR. | | EXEPTIONS: | | 1. THE FUEL-BURNING APPLIANCE IS A DIRECT-VENT | | APPLIANCE OR AN APPLIANCE NOT REQUIRING A VENT IN | | ACCORDANCE WITH SECTION M1801.1 OR CHAPTER 24. | | 2. THE ROOM OR SPACE COMPLIES WITH THE FOLLOWING | | REQUIREMENTS: | | 2.1. THE RETURN AIR SHALL BE TAKEN FROM A ROOM OR SPACE | | HAVING A VOLUME EXCEEDING 1 CUBIC FOOT FOR EACH 10 | | BTU/H (9.6 L/W) OF COMBINED INPUT RATING OF ALL | | FUEL-BURNING APPLIANCES THEREIN. | | 2.2. THE VOLUME OF SUPPLY AIR DISCHARGED BACK INTO THE | | SAME SPACE SHALL BE APPROXIMATELY EQUAL TO THE VOLUME | | OF RETURN AIR TAKEN FROM THE SPACE. | | 2.3. RETURN-AIR INLETS SHALL NOT BE LOCATED WITHIN 10 | | FEET (3048 MM) OF ANY APPLIANCE FIREBOX OR DRAFT HOOD | | IN THE SAME ROOM OR SPACE. | | | | THE UTILITY ROOM IN WHICH THE AIR HANDLER IS LOCATED | | CONTAINS A TANKLESS GAS WATER HEATER. THE MECHANICAL | | PLANS SPECIFY A LOUVERED DOOR SO THAT RETURN AIR CAN | | ENTER THE ROOM MAKING THE ROOM CONTAINING THE GAS WATER | | HEATER A PLENUM. ( THE DOOR SCHEDULE ON THE FLOOR PLANS | | SPECIFY A HOLLOW CORE DOOR. ) | | | | 2) SUBMIT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | AND CONDITIONS OF THE LISTING FOR THE TANKLESS GAS | | WATER HEATER. FBC R G2406 (303.1) | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-06-05 |
|
|
Cont ID |
|
Sent By |
jsaez |
Date |
2014-06-05 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
jsaez |
Date |
2014-06-05 |
Time |
15:13 |
Sent To |
|
|
Notes |
2014-06-05 15:15:23 | 1.PROVIDE MECHANCIAL PLANS.1. PROVIDE A.H.U./ C.U. | | DETAIL, SCHEDULES. | | 2. CHASE OUT 14" DN. TO GRD. FLR. | | 3. NO R/A THRU BED.RM # 2 FROM A.H.U.- 2 | | 4. MINI SPLIT SHON ON PLANS. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2014-10-28 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-10-28 |
Time |
04:50 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-10-28 |
Time |
04:50 |
Sent To |
|
|
Notes |
2014-10-28 04:52:03 | ****PROVISO**** | | REVISED SANITARY RISER TO BE SUBMITTED FOR REVIEW AND | | APPROVAL PRIOR TO GROUND ROUGH INSPECTION. | | GAS TO BE UNDER SEPARATE PERMIT. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-09-13 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-09-13 |
Time |
|
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-09-13 |
Time |
|
Sent To |
|
|
Notes |
2014-09-13 07:15:57 | ****PROVISO**** | | REVISED SANITARY RISER TO BE SUBMITTED FOR REVIEW AND | | APPROVAL PRIOR TO GROUND ROUGH INSPECTION. | | GAS TO BE UNDER SEPARATE PERMIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-06-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-21 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-21 |
Time |
09:35 |
Sent To |
|
|
Notes |
2014-06-21 10:34:45 | 2010 FBC | | | | PLUMBING IS DENIED | | | | 1) THE RISER DIAGRAM IS DRAWN INCORRECTLY AND DOES NOT | | MATCH THE PLANS. ALL OF THE FIXTURE DRAINS ( EXCEPT THE | | KITCHEN SINK ) ARE SHOWN CONNECTED TO THE VERTICAL VENT | | PIPING. FBCR P3101.2.1 SUBMIT CORRECTED DRAWINGS. | | | | 2) THE EXISTING BATH DRAIN AND VENT PIPING NEEDS TO BE | | SHOWN ON THE FLOOR AND RISER PLANS. CITY AMENDMENTS | | 107.1 | | | | 3) THE MAXIMUM DISTANCE OF THE TRAP TO THE VENT HAS | | BEEN EXCEEDED AT THE LAVATORY IN THE MASTER BATH. FBCR | | P3105.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2014-12-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-08 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-12-08 |
Time |
16:49 |
Sent To |
|
|
Notes |
2014-12-08 16:55:32 | ROOFING MATERIAL | | | | GALENA SPANISH "S" CONCRETE TILE NOA 10-0518.04 | | TILE BOND ROOF TILE ADHESIVE NOA 11-0616.03 | | CERTAINTEED MODIFIED BITUMEN FL 16709 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2014-09-12 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-09-12 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-09-12 |
Time |
11:36 |
Sent To |
|
|
Notes |
2014-09-12 11:37:41 | NOTE: INTERIOR MODIFICATIONS TO PRIMARY STRUCTURE ONLY; | | NO CHANGE TO EXISTING BUILDING FOOTPRINT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-06-06 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-06-06 |
Time |
17:43 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-06-06 |
Time |
17:43 |
Sent To |
|
|
Notes |
2014-06-06 17:45:57 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE VALUE OF THE CONSTRUCTION ($162,00) EXCEEDS 50 | | PERCENT OF THE STRUCTURE'S VALUE ($90,290) ACCORDING TO | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | TO BRING THE SITE INTO CONFORMITY. | | | | 2.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY WITH THE | | PROPOSED LOCATION OF THE A/C UNIT(S). | | | | 3.) WILL THE PROPOSED GAS FIREPLACE REQUIRE A CHIMNEY? | | IF SO, ARCHITECTURAL ELEVATIONS WILL NEED TO BE | | PROVIDED. | | | | PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS | | MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE | | @ (561) 822-1458 IF YOU HAVE QUESTIONS. | | | 2014-06-06 11:05:56 | 6/5/14 |
|
|