Plan Review Details - Permit 14060022
Plan Review Stops For Permit 14060022
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By jwitmer Date 2014-07-26 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2014-07-26 Time 06:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-03 Cont ID  
Sent By jwitmer Date 2014-07-03 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 08:45 Sent To  
Notes
2014-07-03 12:40:13BUILDING PLAN REVIEW
 PERMIT:14060022
 ADD: 1815 PALM BEACH LAKES SUITE # E-02
 CONT: TBD
 TEL: (561)348-4805 LEXI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. JULY 03/2014
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET T 1 INDICATES THE WIND SPEED DESIGN IS 140
 MPH. PLEASE NOTE THE WIND DESIGN SPEED FOR THIS
 LOCATION IS 170 MPH/ VULT,
 3 SECOND GUST. THIS TRANSLATES INTO 132 MPH/ VASD, 3
 SECOND GUST. THE SHELL IS COMPLETED UNDER THE 170 VASD.
 THE WIND DESIGN WILL NEED TO BE CORRECTED BEFORE THE
 MECHANICAL EXHAUST FANS AND OR OTHER ROOF TOP EQUIPMENT
 ARE ATTACHED TO THE BUILDING ENSURING THE PROPER
 ANCHORING OF SYSTEMS INTO THE MAIN WIND FORCE RESISTING
 SYSTEMS. 2010 FBC-B FIGURE 1609A ULTIMATE WIND DESIGN
 SPEEDS FOR RISK CATEGORY II BUILDINGS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-19 Cont ID  
Sent By dhayes Date 2014-06-19 Time 12:27 Rev Time 0.00
Received By dhayes Date 2014-06-19 Time 12:25 Sent To  
Notes
2014-06-19 12:28:07BACK TO C4

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-28 Cont ID  
Sent By scaldero Date 2014-07-28 Time 11:29 Rev Time 0.00
Received By scaldero Date 2014-07-28 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By pleduc Date 2014-06-06 Time   Rev Time 0.00
Received By pleduc Date 2014-06-05 Time 16:38 Sent To  
Notes
2014-06-06 12:10:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME.
  
 SHEET M1 DOES NOT SHOW LOCATIONS OF HVAC SMOKE
 DETECTORS; HOWEVER, INSTALLATION IS REFERENCED
 ELSEWHERE ON SEPARATE SHEETS. HVAC SD'S SHALL BE
 INSTALLED PER NFPA 90A AND SHALL BE INSPECTED AND
 TESTED BY A FIRE INSPECTOR.
  
 SHEET SP, THE SHADED OCCUPANY IS INDICATED AS E-2, EACH
 PLAN SHEET IS INDICATED AS "STE # 03", CLARIFICATION
 MAY BE NECESSARY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-30 Cont ID  
Sent By jwitmer Date 2014-07-30 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2014-07-16 Time   Sent To  
Notes
2014-07-17 08:13:17C7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-08 Cont ID  
Sent By hmoser Date 2014-07-08 Time 15:23 Rev Time 0.00
Received By hmoser Date 2014-06-02 Time 12:17 Sent To  
Notes
2014-06-03 12:17:42C04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By H MOSER Date 2014-07-26 Time 06:34 Rev Time 0.00
Received By jwitmer Date 2014-07-26 Time 06:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-08 Cont ID  
Sent By hmoser Date 2014-07-08 Time 15:23 Rev Time 0.00
Received By hmoser Date 2014-07-08 Time 13:11 Sent To  
Notes
2014-07-08 15:23:17PLAN DENIED
  
 1) KITCHEN EXHAUST HOODS AND COOLERS REQUIRE
 THERE SEPARATE APPLICATION, PLANS AND PERMIT.
 PER SECTION 107 FBC 2010
 2) SHOW RTU 1,2,3,AND 4 ON THE PLAN
 PER SECTION 107 FBC 2010
 3) PROVIDE AN ENGINEER DETAIL ON EXHAUST
 FAN CURB TIE DOWN TO ROOF AND EXHAUST FAN
 TO CURB TIE DOWN. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-03 Cont ID  
Sent By jwitmer Date 2014-07-03 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 08:45 Sent To  
Notes
2014-07-03 13:57:09PLUMBING PLAN REVIEW
 PERMIT:14060022
 ADD: 1815 PALM BEACH LAKES SUITE # E-02
 CONT: TBD
 TEL: (561)348-4805 LEXI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. JULY 03/2014
 ACTION: PROVISO
 PLUMBING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE FUEL GAS WILL REQUIRE A SEPARATE PERMIT. SHEET
 P4 PROVIDES A GAS ISOMETRIC PLAN, MISSING INFORMATION
 IS FUEL GAS TABLE FROM THE
 2010 FBC-FUEL GAS CODE THAT SYSTEM WAS SIZED FROM, THE
 TABLE WILL ALSO PROVIDE THE TYPE OF MATERIAL TO BE
 INSTALLED. THIS REVIEW WAS COMPLETED BY USING THE TABLE
 402.4.2 NATURAL GAS, SCHEDULE 40 METALLIC PIPE, LESS
 THAN 2 PS, GOOD FOR 300 FT/ 3 INCH = 1,800,000CFH.
 A REVISION IS REQUIRED BEFORE THE INSTALLATION OF THE
 FUEL GAS SYSTEM BEGINS.
  
 2) COMPLETED (/17/2014 PROVIDED CALCULATIONS ).
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-24 Cont ID  
Sent By ESCHNEID Date 2014-07-24 Time 13:57 Rev Time 1.00
Received By eschneid Date 2014-07-24 Time 13:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-13 Cont ID  
Sent By eschneid Date 2014-06-13 Time 10:38 Rev Time 2.00
Received By eschneid Date 2014-06-13 Time 10:38 Sent To  
Notes
2014-06-13 10:50:07FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE EXPLAIN WHY THE SHELL PERMIT FOR BAY E02
 SHOWS 3,026 SQ. FT. YET THIS PERMIT IS FOR A SPACE ONLY
 3,025 SQ. FT.?
  
 2) PLEASE VERIFY THAT THE BURLAP BANNER IS JUST BURLAP
 WITH NO TEXT OR LOGOS.
  
 3) PLEASE DESCRIBE WHAT MERCHANDISE WILL BE PLACED ON
 THE MENU TABLE FOR DISPLAY IN THE SOUTHERN WINDOW.
  
 4) STAFF HAS NOTED THAT THE MAKEUP AIR UNIT (MAU) IS
 SHOWN AT A HEIGHT, WITH CURB, OF 70 INCHES. THE HEIGHT
 OF THE UNIT, COMBINED WITH ITS LOCATION ON THE ROOF IN
 LINE WITH ONE OF THE LOWER PARAPETS, SHOWS IT EXTENDING
 ABOVE THE PARAPET ON THE ELEVATION DRAWING (SHEET A7).
 PLEASE PROVIDE VERIFICATION THAT THIS UNIT IS SCREENED
 IN ACCORDANCE WITH THE PALM BEACH OUTLETS DESIGN
 GUIDELINES. PLEASE NOTE THAT THE LANDLORD SHELL PERMIT
 ONLY SHOWED THAT THE RTUS COMPLIED WITH THE SCREENING
 IN THEIR LOCATION BEHIND THE HIGHER PARAPET, NOT THE
 MAU.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-06-06 11:15:476/5/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved