Plan Review Details - Permit 14050994
Plan Review Stops For Permit 14050994
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-16 Cont ID  
Sent By shill Date 2014-07-16 Time 14:09 Rev Time 0.00
Received By shill Date 2014-07-16 Time 14:09 Sent To  
Notes
2014-07-16 15:02:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CALCULATIONS PREPARED BY JUSTIN PLAISTED. AN
 ENGINEERING LICENSE IS REQUIRED TO PRACTICE ENGINEERING
 IN FLORIDA, FS471.
  
 2. DESIGNER RESPONSIBILITY NOT CLEAR. JUSTIN PLAISTED
 PREPARED THE CALCS, BUT THEY ARE SIGNED AND SEALED BY
 JOHN HOLT, PE. PLEASE CLARIFY.
  
 3. DESIGN CRITERIA NOT CLEAR, FBC 1609. JUSTIN PLAISTED
 HAS PERFORMED CALCULATIONS PER NAAMM FP 1001-07, 100
 MPH. PLEASE REFER MR. PLAISTED TO THE MAP IN NAAMM FP
 1001-07, WHICH INCLUDES THE WIND SPEED MAP FROM
 ASCE7-05. THE CITY OF WEST PALM BEACH LIES ENTIRELY IN
 THE 140MPH ZONE IN THIS MAP.
  
 JOHN HOLT, UNDER HIS SEAL, DECLARES THE DESIGN CRITERIA
 AS 180MPH EXPOSURE C. AS THE COMBINED STRESS RATION IS
 .96, THERE APPEARS TO BE A DISCREPANCY IN THE DESIGN
 CRITERA ATTESTED TO BY THE ENGINEER.
  
 NEW COMMENT:
  
 4. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD
 ZONE A8 (15' BFE). THIS PROPOSED IMPROVEMENT IS TO
 RESIST FLOOD LOADS AND FLOOD DESIGN DATA TO BE INCLUDED
 ON THE PLAN, FBC 1603.1.7.
  
 IF AVAILABLE, PLEASE PROVIDE THE ELEVATION CERTIFICATE
 FOR THIS PROPERTY. IF PROPOSED IMPROVEMENT IS HIGHER
 THAN DESIGN FLOOD ELEVATION, FLOOD DESIGN LOAD DATA IS
 NOT REQUIRED. AN ELEVATION CERTIFICATE HAS ALREADY BEEN
 REQUESTED RELATED TO ANOTHER PERMIT.
  
 A SET HAS BEEN RETAINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-19 Cont ID  
Sent By shill Date 2014-06-19 Time 15:54 Rev Time 0.00
Received By shill Date 2014-06-19 Time 15:54 Sent To  
Notes
2014-06-19 15:59:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE INFORMATION ABOUT THE SUPPORT
 OF THE 5" ALUMINUM BALL AT THE TOP OF PROPOSED
 FLAGPOLE. IT IS NOT CLEAR HOW THIS IS CONSTRUCTED OR
 HOW IT WILL RESIST WIND LOADS. SCALED, IT APPEARS THAT
 IT IS SUPPORTED BY SOMETHING THAT IS 1" BUT NO
 INFORMATION ABOUT THE THICKNESS OF THIS SUPPORT HAS
 BEEN PROVIDED.
  
 CALCULATIONS MAY BE REQUIRED. A SET HAS BEEN RETAINED.
  
  
 2. FBC 107, REVISE PLAN TO SPEC FLAGPOLE MATERIAL AND
 SIZE (THICKNESS), FBC 1609.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-06-02 Cont ID  
Sent By dhayes Date 2014-06-02 Time 12:58 Rev Time 0.00
Received By dhayes Date 2014-06-02 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-19 Cont ID  
Sent By shill Date 2014-06-19 Time 15:59 Rev Time 0.00
Received By shill Date 2014-05-28 Time 11:51 Sent To  
Notes
2014-05-28 11:51:51ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By sgraham Date 2014-05-28 Time 13:53 Rev Time 0.00
Received By sgraham Date 2014-05-28 Time 13:53 Sent To E
Notes
***NONE***