Plan Review Details - Permit 14050899
Plan Review Stops For Permit 14050899
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-11-05 Cont ID  
Sent By shill Date 2014-11-05 Time 11:45 Rev Time 0.00
Received By shill Date 2014-11-05 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-22 Cont ID  
Sent By shill Date 2014-09-22 Time 19:23 Rev Time 0.00
Received By shill Date 2014-09-22 Time 19:18 Sent To E
Notes
2014-09-22 19:23:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING. PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB FBC 109.
  
 2ND REVIEW, CONTRACT IS FOR LABOR ONLY. PROVIDE THE
 RECEIPT/INVOICE FOR THE LETTERS.
  
 EMAILED CONTRACTOR ON 9/22
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-19 Cont ID  
Sent By shill Date 2014-06-19 Time 13:20 Rev Time 0.00
Received By shill Date 2014-06-19 Time 13:20 Sent To  
Notes
2014-06-19 13:23:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NO LETTER DIMENSIONS PROVIDED ON THE ENGINEERING,
 FBC 1609. FASTENERS INDICATE MINIMUM 2 PER LETTER BUT
 DOES NOT HAVE A LIMITATION AS TO LETTER SIZE. REVISE
 PLAN TO INCLUDE LETTER HEIGHTS, FBC 107.
  
 A SET HAS BEEN RETAINED.
  
 2. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING. PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB FBC 109.
  
  
2014-06-02 10:38:07 
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-23 Cont ID  
Sent By dhayes Date 2014-09-23 Time 07:42 Rev Time 0.00
Received By dhayes Date 2014-09-23 Time 07:42 Sent To  
Notes
2014-09-23 07:45:21DATE: 9/23/2014
 PROJECT: IMPACT WINDOWS SIGN
 PERMIT#: 14050899
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) NEC 600.5
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 2) 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
  
 3) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
  
 5) 600.4 MARKINGS.
 (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND
 OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE
 MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF
 IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
 (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS.
 SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR
 INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE
 MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE
 MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT
 LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE
 VISIBLE DURING RELAMPING.
 (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO
 INDICATE THAT FIELD-WIRING AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS
 TO SAME ARE UNDER A DIFFERENT PERMIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-02 Cont ID  
Sent By dhayes Date 2014-06-02 Time 10:39 Rev Time 0.00
Received By dhayes Date 2014-06-02 Time 09:44 Sent To B
Notes
2014-06-02 10:39:03ELECTRICAL PROVISO:
  
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-05 Cont ID  
Sent By shill Date 2014-11-05 Time 11:45 Rev Time 0.00
Received By shill Date 2014-10-20 Time 12:29 Sent To  
Notes
2014-10-20 12:29:57T SHILL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-24 Cont ID  
Sent By shill Date 2014-09-24 Time 09:51 Rev Time 0.00
Received By shill Date 2014-09-11 Time 08:46 Sent To  
Notes
2014-09-22 19:24:389/22 TO DAH DESK
  
2014-09-12 08:46:47SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-19 Cont ID  
Sent By shill Date 2014-06-19 Time 13:24 Rev Time 0.00
Received By shill Date 2014-06-19 Time 13:24 Sent To  
Notes
2014-05-23 11:06:57ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-23 Cont ID  
Sent By sgraham Date 2014-05-23 Time 11:49 Rev Time 0.00
Received By sgraham Date 2014-05-23 Time 11:49 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved