Plan Review Details - Permit 14050702
Plan Review Stops For Permit 14050702
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By pleduc Date 2014-06-30 Time   Rev Time 0.00
Received By pleduc Date 2014-06-30 Time 10:53 Sent To PC
Notes
2014-06-24 11:13:56NEEDS A NEW STAMP, NEW SETS SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By pleduc Date 2014-05-20 Time   Rev Time 0.00
Received By pleduc Date 2014-05-20 Time 14:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-30 Cont ID  
Sent By pleduc Date 2014-06-30 Time   Rev Time 0.00
Received By pleduc Date 2014-06-18 Time 18:20 Sent To PC
Notes
2014-06-18 18:21:05INCOMING SENT TO MECHANICAL BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 15:32 Rev Time 0.00
Received By hmoser Date 2014-05-19 Time 17:43 Sent To  
Notes
2014-05-19 17:43:56SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-24 Cont ID  
Sent By jsaez Date 2014-06-24 Time 10:57 Rev Time 0.00
Received By jsaez Date 2014-06-24 Time 10:57 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 15:30 Rev Time 0.00
Received By hmoser Date 2014-05-27 Time 15:12 Sent To  
Notes
2014-05-27 15:30:03PLAN DENIED
 1) PROVIDE AN RFI ON EXHAUST FAN PER
 107 FBC 2010
 2) REFER TO SECTION 306.5.1 SLOPED ROOF
 2010 FBC (M)
 3) REFER TO SECTION 506.3.2.2 DUCT TO HOOD JOINTS
 2010 FBC (M)
 PLAN REVIEW BY J S
 PX1328
 OFFICE 561-805-6732
 FAX 561-805-6676