Plan Review Details - Permit 14050582
Plan Review Stops For Permit 14050582
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2014-08-08 Time   Rev Time 0.00
Received By   Date 2014-08-07 Time   Sent To  
Notes
2014-08-11 09:24:27***PROVISO****
  
 1) THIS PLAN HAS BEEN REVIEWED FOR TEMPORARY ACCESSIBLE
 PARKING/MINIMUM F.A.C REQUIREMENTS ONLY AS IT RELATES
 TO THE TEMPORARY BUILDINGS' FUNCTION.
 2) MUST PROVIDE ACCESSIBLE PARKING SIGNS COMPLYING WITH
 THE F.A.C., SECTION 502.6.1.
 3) ALL ACCESSIBLE ROUTES, CURB RAMPS LEADING TO THE
 STAIR RAMPS MUST COMPLY WITH THE F.A.C., SECTIONS
 402,403 AND 502.3.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2014-07-02 Cont ID  
Sent By skennedy Date 2014-07-02 Time 06:56 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-15 Cont ID  
Sent By shill Date 2014-06-15 Time 10:12 Rev Time 0.00
Received By shill Date 2014-06-15 Time 09:50 Sent To  
Notes
2014-06-15 09:59:52****PROVISO****
 ***ISSUED AT CONTRACTOR'S RISK***
 ***REVISION REQUIRED PRIOR TO FIRST INSPECTION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ANCHORING SHEET PREPARED BY JOHN A BODZIAK,
 ARCHITECT, IS A PHOTOCOPY. DOCUMENTS SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. FUTURE SUBMITTALS TO INCLUDE ORIGINAL
 SIGNATURE. PLEASE HAVE ARCHITECT ACKNOWLEDGE
 REQUIREMENT; THIS CAN BE DONE EITHER HARD COPY BY MAIL
 OR VIA EMAIL. NO FURTHER ACTION REQUIRED.
  
 2. IMPACT PROTECTION REQUIRED, SEE SHEET 1, SITE
 INSTALLED ITEMS. ALSO PLEASE NOTE THAT ON PAGE 1,
 APPROVED PRODUCTS LIST, THE DOOR (FL14237) STATES THAT
 SHUTTERS ARE REQUIRED. THIS IS AN IMPACT RATED DOOR PER
 WWW.FLORIDABUILDING.ORG, SO PLEASE EXCLUDE THIS FROM
 YOUR SHUTTER PERMIT APPLICATION OR REVISION AS THIS
 WOULD OBSTRUCT THE EXIT AND IS NOT NECESSARY. SEPARATE
 PERMIT REQUIRED.
  
 3. SEE FBC TABLE 705.8. DISTANCES BETWEEN BUILDINGS
 WERE NOT SHOWN ON THE SITE PLAN. REVISE SITE PLAN TO
 SHOW COMPLIANCE. PLEASE ALSO SEE FBC 705.3, EXCEPTION.
  
 4. SHEET A100, RAMP & DECK PLAN PREPARED BY MODULAR
 PLANS DESIGN, CO (MDP COMPANY ARCHITECTS), THOMAS L.
 MELTON (AR0017033) IS LACKING THE ARCHITECT BUSINESS
 LICENSE NUMBER IN THE TITLE BLOCK (FAC61G15-23.002, FS
 481). REVISE THIS SHEET TO INCLUDE THE REQUIRED
 INFORMATION. IF THIS COMPANY DOES NOT HAVE AN ARCHITECT
 BUSINESS LICENSE, PROVIDE EVIDENCE THAT THIS HAS BEEN
 APPLIED FOR (MAY BE SENT VIA EMAIL).
  
  
  
 3. WHEN RESUBMITTING, ALWAYS COLLATE SHEETS, FBC 107.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-17 Cont ID  
Sent By shill Date 2014-05-17 Time 17:03 Rev Time 0.00
Received By shill Date 2014-05-17 Time 17:03 Sent To Z
Notes
2014-05-17 17:03:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN WHICH SHOWS PROPOSED LOCATION,
 FBC 107.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-07-01 Cont ID  
Sent By skennedy Date 2014-07-02 Time 06:56 Rev Time 0.00
Received By pleduc Date 2014-07-01 Time 08:44 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-06-11 Cont ID  
Sent By pleduc Date 2014-06-11 Time   Rev Time 0.00
Received By pleduc Date 2014-06-11 Time 10:43 Sent To  
Notes
2014-06-11 10:48:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 HAVING REVIEWED THE SITE PLAN FOR THE FIRST TIME, THERE
 ARE MULTIPLE TEMPORAY TRAILERS INDICATED IN THE PARKING
 LOT AREA.
  
 THESE TEMPORAY TRAILERS SHALL MEET THE MINIMUM
 SEPARATION DISTANCE REQUIREMENTS OF NFPA 241, CHAPTER
 4, TABLE 4.2.1.
  
 SEPARATION DISTANCES SHALL BE PROVIDED ON THE SITE
 PLAN. THE TRAILERS SHALL BE SEPARATED ACCORDING TO THE
 INDICATED SEPARATION DISTANCES.
  
 A 75 PERCENT REDUCTION IN SEPARATION DISTANCE SHALL BE
 APPLIED PROVIDED AUTOMATIC SPRINKLER PROTECTION IS USED
 IN THE EXPOSING STRUCTURE.
  
 AS PROPOSED, FIRE SPRINKLER PROTECTION IS REQUIRED IN
 EACH OF THE TRAILERS ON THE SITE PLAN, SPRINKLER
 PROTECTION SHALL BE INDICATED ON THE RESUBMITTED PLAN
 UNDER SEPARATE SHOP DRAWINGS.
  
 ADA COMPLAINT STAIR/RAMP PLANS WERE NOT PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-05-20 Cont ID  
Sent By pleduc Date 2014-05-20 Time   Rev Time 0.00
Received By pleduc Date 2014-05-20 Time 11:29 Sent To PC
Notes
2014-05-20 11:30:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SITE PLAN NOT PROVIDED, INCLUDING ALL DIMENSIONS FROM
 NEAREST STRUCTURES, PARKING LOTS, DRIVEWAYS, ETC.
  
 INDICATION OF HOW LONG THE TEMPORARY TRAILER WILL BE
 THERE IS NOT PROVIDED.
  
 LIFE SAFETY PLAN NOT PROVIDED.
  
 FLOOR PLAN, FURNITURE LOCATIONS NOT PROVIDED.
  
 LIGHTWIEGHT TRUSS FLOOR AND ROOF SIGN NOT PROVIDED.
  
 STAIRS, ADA RAMP DETAILS NOT PROVIDED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-02 Cont ID  
Sent By skennedy Date 2014-07-02 Time 06:56 Rev Time 0.00
Received By skennedy Date 2014-06-26 Time 08:20 Sent To  
Notes
2014-07-01 08:20:52ADA RAMP/STAIR DRAWINGS SENT TO SAMANTHA'S DESK FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-02 Cont ID  
Sent By skennedy Date 2014-07-02 Time 06:56 Rev Time 0.00
Received By skennedy Date 2014-06-23 Time 10:54 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-15 Cont ID  
Sent By shill Date 2014-06-15 Time 10:12 Rev Time 0.00
Received By shill Date 2014-06-09 Time 18:00 Sent To  
Notes
2014-06-11 18:48:166/11 TO SH DESK
  
2014-06-09 18:00:21TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-20 Cont ID  
Sent By pleduc Date 2014-05-20 Time   Rev Time 0.00
Received By pleduc Date 2014-05-15 Time 10:14 Sent To PC
Notes
2014-05-17 17:03:525/17 TO ZONING
  
2014-05-15 10:18:43PUT IN COMM. MISC. BIN

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-10 Cont ID  
Sent By sgraham Date 2014-06-10 Time 10:43 Rev Time 0.00
Received By sgraham Date 2014-06-10 Time 10:43 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By sgraham Date 2014-05-19 Time   Rev Time  
Received By sgraham Date 2014-05-19 Time   Sent To FIRE
Notes
2014-05-19 15:24:355/19/14 ZONING FAILED
  
 1. PROVIDE 2- SITE PLANS SHOWING LOCATION OF TRAILER,
 LANDSCAPING, PARKING AND HANDICAP ACCESSIABLITY.