Plan Review Details - Permit 14050414
Plan Review Stops For Permit 14050414
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By skennedy Date 2014-06-30 Time 09:57 Rev Time 0.00
Received By skennedy Date 2014-06-30 Time 09:57 Sent To E
Notes
2014-06-30 09:58:00TO DHAYES DESK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-18 Cont ID  
Sent By skennedy Date 2014-05-18 Time 10:54 Rev Time 0.00
Received By skennedy Date 2014-05-18 Time 10:46 Sent To  
Notes
2014-05-18 10:46:431ST REVIEW:
  
 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, WINDOWS AND DOORS, THE DESIGNER OF RECORD
 JAMES EDWIN PATE JR. WHO IS RESPONSIBLE FOR THE WALL
 PRESSURES ON PAGE A-2 SHOULD REVIEW THE PRODUCTS
 SELECTED AND PROVIDE EVIDENCE OR REVIEW AND
 APPROPRIATENESS TO MEET THE DESIGN PRESSURES ON PAGE
 A-2.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-03 Cont ID  
Sent By dhayes Date 2014-07-03 Time 14:51 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By dhayes Date 2014-05-19 Time 11:11 Rev Time 0.00
Received By dhayes Date 2014-05-19 Time 08:48 Sent To  
Notes
2014-05-19 10:16:18ELECTRIC REVIEW DENIED. ALL DEFICIENCIES BASED ON THE
 2010 FBC AND THE 2008 NEC.
  
 1) ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE LIVING
 ROOM. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE
 THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE
 THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 2) THE RISER DIAGRAM INDICATES A NEW 200AMP MAIN PANEL
 INSIDE THE RESIDENCE WITH NO MAIN DISCONNECT INDICATED
 NEXT TO THE METER OUTSIDE. THE SERVICE ENTRANCE
 DISCONNECTING MEANS SHALL BE INSTALLED TO COMPLY WITH
 NEC 230.70.
  
 3) PLEASE PROVIDE THE PANEL SCHEDULES AND SHOW CIRCUITS
 ON FLOOR PLAN. FBC- 107.3.5.3
  
 4) A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 5) PROVIDE A GROUNDING ELECTRODE FOR THE GUEST HOUSE
 ELECTRIC PANEL AND INDICATE IT ON THE PLANS. NEC 250.32
  
 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3)
 LOCATION. STATES IN PART , THE MINIMUM CLEARANCE
 BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE
 NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS:
 "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES
 WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN
 THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED
 FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR
 CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION
 OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN THE
 CLOTHES CLOSET IN THE MASTER BEDROOM.
  
 7) BATHROOM GFIC OUTLET. BATHROOM BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. THE PLAN SHOWS NEW OUTLET IN THE BATHROOM FOR
 A LIGHTED MIRROR. PLEASE INDICATE COMPLIANCE WITH
 ARTICLE 210.11 (C)(3)
  
 8) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-05-13 Cont ID  
Sent By fmittner Date 2014-05-13 Time 09:45 Rev Time 0.00
Received By fmittner Date 2014-05-13 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-03 Cont ID  
Sent By dhayes Date 2014-07-03 Time 14:51 Rev Time 0.00
Received By dhayes Date 2014-06-13 Time 14:06 Sent To  
Notes
2014-06-13 14:12:50ROUTE TO SAK FOR 2ND BUILDING ROOFING AND MECHANICAL
 REVIEWS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-19 Cont ID  
Sent By dhayes Date 2014-05-19 Time 11:11 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 10:58 Sent To  
Notes
2014-05-14 10:59:13SENT TO R24 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By skennedy Date 2014-06-30 Time 09:57 Rev Time 0.00
Received By skennedy Date 2014-06-30 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-18 Cont ID  
Sent By skennedy Date 2014-05-18 Time 10:23 Rev Time 0.00
Received By skennedy Date 2014-05-18 Time 10:23 Sent To  
Notes
2014-05-18 10:38:491ST REVIEW.
  
 THE OVERALL PLAN APPEARS TO INDICATE A NEW A/C SYSTEM
 WILL BE INSTALLED. THERE IS AN ENERGY SUBMITTAL
 ALTHOUGH THIS STRUCTURE IS EXEMPT FROM ENERGY CODE
 COMPLIANCE.
 1) FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 EQUIPMENT, SUPPLY DUCTS PER FBC-R M16, BALANCED AIR
 RETURN AT BEDROOMS PER FBC-R-M 1602.4 & BATH EXHAUST
 PER FBC-R M15.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-18 Cont ID  
Sent By skennedy Date 2014-05-18 Time 10:19 Rev Time 0.00
Received By skennedy Date 2014-05-18 Time 10:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By skennedy Date 2014-06-30 Time 09:53 Rev Time 0.00
Received By skennedy Date 2014-06-30 Time 09:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-05-18 Cont ID  
Sent By skennedy Date 2014-05-18 Time 10:39 Rev Time 0.00
Received By skennedy Date 2014-05-18 Time 10:38 Sent To  
Notes
2014-05-18 10:45:261ST REVIEW:
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY,ROOFING, THE PRODUCT APPROVAL HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 OR -60.0 DEPENDING ON
 THE OPTION USED. BOTH MUST COMPLY WITH LIMITATION #7
 FOR ENHANCED FASTENING. THE DESIGNER OF RECORD JAMES
 EDWIN PATE JR. WHO IS RESPONSIBLE FOR THE WALL
 PRESSURES ON PAGE A-2 SHOULD REVIEW THE PRODUCT AND
 PROVIDE RAS 117 ENHANCED FASTENING DATA.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-13 Cont ID  
Sent By fmittner Date 2014-05-13 Time 09:45 Rev Time 0.00
Received By fmittner Date 2014-05-13 Time 09:45 Sent To  
Notes
***NONE***