2014-05-24 06:14:22 | BUILDING PLAN REVIEW |
| REVISION: 13120383 |
| ADD: 14050357 |
| CONT: 401 S DIXIE HWY |
| TEL: (561)307-4951 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. MAY 24/ 2014 |
| ACTION: DENIED |
| |
| 1) THIS PERMIT IS FOR 3RD FLOOR CORRIDOR AND COMMON |
| AREA RESTROOMS. THE REVISED SCOPE OF WORK GOES BEYOND |
| THE ORIGINAL SCOPE OF WORK WITH ADDING 3 PAIRS OF |
| DOUBLE DOORS AND NEW TENANT DEMISSING WALLS SPLITTING |
| SUITE # 301 INTO 2 SUITES, REPLACEMENT OF PLUMBING |
| FIXTURES IN BOTH RESTROOMS WITH OUT THE INCREASE IN THE |
| VALUE OF WORK . |
| |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) SHEET A-1.0 REVISION # 2 THE NEW WALL CONFIGURATION |
| IN THE CORRIDOR AS WELL AS THE NEW TENANT FIRE |
| PARTITION DOES NOT PROVIDE WALL IDENTIFICATION TAGS |
| IDENTIFYING WHICH OF THE PARTITION DETAILS FOUND ON |
| A-2.0 WILL BE USED IN CONSTRUCTING THESE WALLS. PLEASE |
| PROVIDE THIS ADDITIONAL INFORMATION 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 107.2.1.3. 2010 FBC-B 709.1.6 AND |
| 709.4 CONTINUITY, 1018.1 CORRIDOR FIRE RESISTANCE AND |
| 1018.6 CONTINUITY. |
| |
| 3) SHEET A-1.1 IN SUITE # 301 BEHIND THE NEW DOUBLE |
| DOORS THERE APPEARS TO BE A VERTICAL DUCT AND NEW |
| SHAFT, PLEASE PROVIDE ADDITIONAL INFORMATION AS IF THIS |
| IS A NEW SHAFT AND IF SO THE FIRE RATING ON THE SHAFT, |
| CONFIGURATION OF THE COMPONENTS THAT MAKE UP THE SHAFT |
| WALL ASSEMBLY. 2010 FBC-B 708.2 SHAFT ENCLOSURES |
| REQUIRED. |
| |
| 4) SHEET A-1.1 IN SUITE # 301 THE PLANS SHOW A EXIT |
| LIGHT (FBC-B 1006.3.1) AND EMERGENCY BATTERY BACK-UP |
| LIGHT (FBC-B TABLE 1006.1) , IN SUITE # 305 THE PLANS |
| ARE MISSING THE EXIT LIGHT AS WELL AS THE EMERGENCY |
| BATTERY BACK UP LIGHT. |
| |