Plan Review Stops For Permit 14050331 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-23 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-23 |
Time |
06:54 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-06-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-30 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-28 |
Time |
10:03 |
Sent To |
E |
|
Notes |
2014-06-30 17:23:39 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD | | HAZARD ZONE A5 WITH A 7' BFE. THE CITY OF WEST PALM | | BEACH'S FLOOD ORDINANCE REQUIRES NEW CONSTRUCTION TO | | HAVE A FINISH FLOOR ELEVATION OF 7.5' NGVD ( WHICH | | INCLUDES A SIX INCH FREEBOARD ). AN ELEVATION | | CERTIFICATE IS REQUIRED FOR THE PROPOSED GARAGE AND | | EQUIPMENT. | | THE PLANS ARE REQUIRED TO SHOW COMPLIANCE WITH FEMA | | REQUIREMENTS. THE ENCLOSED GARAGE CAN ONLY BE USED FOR | | THE PARKING OF VEHICLES. APPLIANCES, HEATING AND | | COOLING EQUIPMENT, PLUMBING FIXTURES, ELECTRICAL | | EQUIPMENT ( OTHER THAN THE MINIMUM REQUIRED FOR LIFE | | SAFETY AND ELECTRIC CODE REQUIREMENTS FOR BUILDING | | ACCESS AND STORAGE AREAS ) AND MATERIALS THAT ARE NOT | | FLOOD DAMAGE-RESISTANT ARE NOT ALLOWED BELOW BFE. SHOW | | THE LOCATIONS AND NUMBER OF VENT OPENINGS ON THE PLANS. | | ONLY THE AREA OF THE VENT OPENINGS THAT ARE BELOW THE | | BFE CAN BE COUNTED TOWARD THE REQUIRED AMOUNT OF FLOOD | | VENT OPENING AREA. FBC R322 SEE ALSO FEMA PUBLICATION | | TECHNICAL BULLETIN 1 / AUGUST 2008 FOR ADDITIONAL | | INFORMATION. | | - THE ELEVATION OF THE GARAGE IS GIVEN AS 7'.0" NGVD ON | | THE PLANS, WHICH IS SIX INCHES BELOW THE REQUIRED FLOOD | | ELEVATION. IF THE FLOOD VENTS ARE INSTALLED AT THE | | FINISH FLOOR ELEVATION, ONLY THE SIX INCHES OF THE VENT | | CAN BE COUNTED TOWARD THE REQUIRED FLOOD OPENING AREA. | | PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED AREA OF | | FLOOD OPENINGS WILL BE PROVIDED. | | | | 2) THE STRUCTURE IS LOCATED IN AN AREA OF QUESTIONABLE | | SOIL. SUBMIT TWO SETS OF A SIGNED AND SEALED SUB | | SURFACE SOIL REPORT. FBC R401.4 | | - INDICATE WHAT METHODS WILL BE USED TO RESOLVE THE | | QUESTIONABLE SOIL ISSUE BASED ON THE RECOMMENDATIONS ON | | PAGE 3 OF THE SOIL REPORT. | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | SMART VENT ENGINEERED FLOOD VENTS (FL #5822.3) WITH | | INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE 9N-3. | | -THE INSTALLATION INSTRUCTION PART OF THE PRODUCT | | APPROVALS FOR THE SMART VENTS WERE NOT SUBMITTED. | | PLEASE SUBMIT REQUESTED INFORMATION. DCA RULE 9N-3 | | | | 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | SECOND FLOOR STUDIO. CITY AMENDMENTS 107.3.5.3 | | - THESE WERE NOT IN THE RE-SUBMITTAL. | | | | 5) SPECIFY THE R- VALUE OF THE INSULATION THAT WILL BE | | USED IN THE FLOOR ABOVE THE GARAGE. FBC ENERGY SECTION | | 402 | | - THE R-VALUE IS SPECIFIED AS R-11 FOR THE FLOOR AND | | WALLS OF SECOND FLOOR. THE MINIMUM FOR EACH USING THE | | PERSCRIPTIVE METHOD IS R-13, UNLESS THE PERFORMANCE | | METHOD IS USED. | | | | 6) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | IN THE PRODUCT APPROVAL FOR THE TAMKO UNDERLAYMENT NOA | | NO. 12-0406.07 WILL BE USED. CITY AMENDMENTS 107.2.1 | | - THIS COMMENT WAS NOT ADDRESSED. | | | | 7) SPECIFY WHICH ONE OF THE FASTENING METHODS LISTED IN | | THE PRODUCT APPROVAL FOR THE HANSON ROOF TILE NOA NO. | | 12-1218.14 WILL BE USED TO INSTALL THE ROOF TILE AND | | RESIST THE OVERTURN MOMENT. FBC R905.3 | | - THIS COMMENT WAS NOT ADDRESSED. | | | | 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | RESPONSE LETTER INDICATING HOW EACH ONE OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-30 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-29 |
Time |
17:49 |
Sent To |
|
|
Notes |
2014-05-30 11:04:28 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD | | HAZARD ZONE A5 WITH A 7' BFE. THE CITY OF WEST PALM | | BEACH'S FLOOD ORDINANCE REQUIRES NEW CONSTRUCTION TO | | HAVE A FINISH FLOOR ELEVATION OF 7.5' NGVD ( WHICH | | INCLUDES A SIX INCH FREEBOARD ). AN ELEVATION | | CERTIFICATE IS REQUIRED FOR THE PROPOSED GARAGE AND | | EQUIPMENT. | | TWO COPIES OF A BROCHURE FOR SMART VENT FLOOD VENTS | | WERE IN THE PAPER WORK THAT WAS SUBMITTED. IF THE | | INTENT IS TO CONSTRUCT THE GARAGE WITH A FINISH FLOOR | | BELOW THE REQUIRED BASE FLOOD ELEVATION, THE PLANS ARE | | REQUIRED TO SHOW COMPLIANCE WITH FEMA REQUIREMENTS. THE | | ENCLOSED GARAGE CAN ONLY BE USED FOR THE PARKING OF | | VEHICLES. APPLIANCES, HEATING AND COOLING EQUIPMENT, | | PLUMBING FIXTURES, ELECTRICAL EQUIPMENT ( OTHER THAN | | THE MINIMUM REQUIRED FOR LIFE SAFETY AND ELECTRIC CODE | | REQUIREMENTS FOR BUILDING ACCESS AND STORAGE AREAS ) | | AND MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE | | NOT ALLOWED BELOW BFE. SHOW THE LOCATIONS AND NUMBER OF | | VENT OPENINGS ON THE PLANS. ONLY THE AREA OF THE VENT | | OPENINGS THAT ARE BELOW THE BFE CAN BE COUNTED TOWARD | | THE REQUIRED AMOUNT OF FLOOD VENT OPENING AREA. FBC | | R322 SEE ALSO FEMA PUBLICATION TECHNICAL BULLETIN 1 / | | AUGUST 2008 FOR ADDITIONAL INFORMATION. | | | | 2) THE STRUCTURE IS LOCATED IN AN AREA OF QUESTIONABLE | | SOIL. SUBMIT TWO SETS OF A SIGNED AND SEALED SUB | | SURFACE SOIL REPORT. FBC R401.4 | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | SMART VENT ENGINEERED FLOOD VENTS (FL #5822.3) WITH | | INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE 9N-3. | | | | 4) THE WIND LOAD INFORMATION ON SHEET A.10 AND A.11 ARE | | INCORRECT. THE TWO STORY STRUCTURE IS LOCATED IN A 170 | | MPH VULT , 132 VASD WINDSPEED AND EXPOSURE CATEGORY D. | | THE COMPONENT AND CLADDING PRESSURES WILL NEED TO BE | | INCREASED ACCORDINGLY. FBC R301.2.1 | | | | 5) THE SIMPSON MTS 12 STRAPS THAT ARE SPECIFIED FOR THE | | ROOF TRUSS TO WALL CONNECTIONS DO NOT HAVE ANY | | RESISTANCE VALUES FOR LATERAL LOADS. SPECIFY HOW THE | | LATERAL ROOF LOADS WILL BE TRANSFERED TO THE WALLS. FBC | | R802.1.6.5 | | | | 6) THE ROOF NAILING PATTERN DIAGRAM ON SHEET A.11 IS | | NOT CORRECT. THE CORNERS OF THE HIP ROOF ARE ROOF ZONE | | 3. FBCR FIGURE R301.2(7) | | | | 7) THE AREA ABOVE THE GARAGE IS SPECIFIED AS STORAGE ON | | SHEET A.03, AS A STUDIO ON A.06 AND AS LIVING SPACE ON | | A.11. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 | | | | 8) SHOW COMPLIANCE WITH FBCR FOR TERMITE PROTECTION. | | FBC R318.6 | | | | 9) THE EGRESS DOOR TO THE SECOND FLOOR IS REQUIRED TO | | HAVE A 32" CLEAR WIDTH MEASURED FROM THE FACE OF THE | | DOOR TO THE STOP WITH THE DOOR OPEN 90 DEGREES. FBC | | R311.2 | | | | 10) SPECIFY THE RISER HEIGHT AND TREAD DEPTH FOR THE | | EXIT STAIRS THAT WERE NOT PROVIDED IN THE DETAIL ON | | A.11. FBC R311.7 | | | | 11) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | SECOND FLOOR STUDIO. CITY AMENDMENTS 107.3.5.3 | | | | 12) SPECIFY THE R- VALUE OF THE INSULATION THAT WILL BE | | USED IN THE FLOOR ABOVE THE GARAGE. FBC ENERGY SECTION | | 402 | | | | 13) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | IN THE PRODUCT APPROVAL FOR THE TAMKO UNDERLAYMENT NOA | | NO. 12-0406.07 WILL BE USED. CITY AMENDMENTS 107.2.1 | | | | 14) SPECIFY WHICH ONE OF THE FASTENING METHODS LISTED | | IN THE PRODUCT APPROVAL FOR THE HANSON ROOF TILE NOA | | NO. 12-1218.14 WILL BE USED TO INSTALL THE ROOF TILE | | AND RESIST THE OVERTURN MOMENT. FBC R905.3 | | | | 15) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS. | | | | 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | A RESPONSE LETTER INDICATING HOW EACH ONE OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-01 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-07-01 |
Time |
11:11 |
Sent To |
|
|
Notes |
2014-07-01 11:50:28 | DATE: 7/1/2014 | | PROJECT: CHURCHILL RESIDENCE | | PERMIT#: 14050331 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE | | CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED | | BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS | | SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE | | 250.68(A) AND (B). | | | | 2) PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES | | AND DEDICATED WORKING SPACE AND ILLUMINATION AT A/C | | DISCONNECTS. NEC 110.26, | | | | 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE | | SHALL BE GFCI PROTECTED. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-05-12 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-12 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-05-12 |
Time |
16:45 |
Sent To |
|
|
Notes |
2014-05-12 17:29:20 | ELECTRICAL PROVISO: | | | | 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE | | CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED | | BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS | | SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE | | 250.68(A) AND (B). | | | | 2) 2010 FBC- 107.3.5 PROVIDE SMOKE DETECTORS PURSUANT | | TO FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | | | 3) 2010 FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-08-26 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-08-27 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-08-21 |
Time |
06:53 |
Sent To |
|
|
Notes |
2014-08-23 06:54:11 | SENT TO R MCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-01 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-06-18 |
Time |
18:09 |
Sent To |
|
|
Notes |
2014-06-18 18:13:19 | INCOMING SENT TO ZONING |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-30 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-09 |
Time |
14:46 |
Sent To |
|
|
Notes |
2014-05-14 14:46:37 | * * * * EXPEDITED * * * * | | | | R 26 | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2014-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-23 |
Time |
07:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-23 |
Time |
07:22 |
Sent To |
|
|
Notes |
2014-08-23 07:26:44 | MU2014-18593, NO FEES WERE DUE. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2014-06-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-30 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-30 |
Time |
16:17 |
Sent To |
|
|
Notes |
2014-06-30 16:18:26 | AN IMPACT REVIEW FEE BY PALM BEACH COUNTY IS REQUIRED. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-30 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-30 |
Time |
14:49 |
Sent To |
|
|
Notes |
2014-05-30 14:52:51 | AN IMPACT REVIEW FEE BY PALM BEACH COUNTY IS REQUIRED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-30 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-30 |
Time |
14:09 |
Sent To |
|
|
Notes |
2014-05-30 06:48:12 | A MECHANICAL PERMIT IS REQUIRED TO RELOCATED THE TWO | | EXISTING A/C CONDENSERS. NO OTHER MECHANICAL WORK SHOWN | | ON PLANS. SEPARATE PERMIT, APPLICATION AND REVIEW IS | | REQUIRED. |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2014-09-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-15 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-15 |
Time |
16:05 |
Sent To |
|
|
Notes |
2014-09-15 16:31:14 | ****CORRECTIONS**** | | ****THIS IS A "FAILED" PLAN REVIEW - "N" ENTERED TO | | ALLOW PERMIT CARD TO PRINT**** | | ELEVATION CERTIFICATE FOR 14060942 AND 14050331, | | PREPARED BY ROBERT J. CAJAL, WALLACE SURVEYING CORP | | DATED 12/26/13 | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PROPERTY IS NOW OWNED BY 101 CHURCHILL ROAD LLC. AS | | DISCUSSED, PLEASE HAVE A CONTRACTOR APPLY FOR ALL OPEN | | PERMITS WHICH WERE OBTAINED UNDER THE FLORIDA STATUTE | | 489 OWNER BUILDER EXEMPTION. SEE ATTORNEY GENERAL | | OPINION AGO 91-05. | | | | PRIOR TO FORM BOARD INSPECTION ("BUILDING UNDER | | CONSTRUCTION"), PLEASE CORRECT THE FOLLOWING ITEMS ON | | THE ELEVATION CERTIFICATE TO AVOID FIELD DELAYS: | | | | 1. A1, A2, A3, IT IS MY UNDERSTANDING THAT THIS PARCEL | | IS UNDERGOING A REPLAT. REVISE THE INFORMATION IN THESE | | FIELDS IF APPLICABLE. | | | | 2. A5, LATITUDE/LONGITUDE DOES NOT APPEAR TO BE | | CORRECT. THIS IS TO BE ACCURATE WITHIN 66' OF THE | | CENTER OF THE FRONT OF THE BUILDING. | | | | 3. A8C, PLEASE PROVIDE CLARIFICATION ABOUT THE NATURE | | OF THE FLOOD VENTS AND PROVIDE CALCULATIONS OR | | INFORMATION AS TO HOW NET OPENINGS HAS BEEN DETERMINED. | | IN THE PHOTOGRAPH, THE VENT APPEARS BLOCKED. YOU MAY | | FIND THE FOLLOWING DOCUMENT HELPFUL: | | | | TECHNICAL BULLETIN 1, OPENINGS IN FOUNDATIN WALLS AND | | WALLS OF ENCLOSURES (2008) | | HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/2644 | | | | VENTS ARE TO BE INSTALLED WITHIN 1' OF ADJACENT GRADE. | | PLEASE VERIFY WITH PHOTOGRAPHS. ONLY THE PORTION OF THE | | VENT WHICH IS BELOW THE BFE IS TO BE INCLUDED IN THE | | NET OPENING AREA. SEE PAGE 19 OF THE TECHNICAL | | BULLETIN; VENTS THAT CAN BE CLOSED MANUALLY OR THAT | | HAVE COVERS ARE NOT ACCEPTABLE AS FLOOD VENTS. | | | | 4. B1, NFIP COMMUNITY NAME IS "CITY OF WEST PALM BEACH" | | (REMOVE "UNINCORPORATED"). | | | | 5. B6, FIRM INDEX DATE SHOULD BE 03/01/1979. | | | | 6. C2E, AS ADVISED DURING PLAN REVIEW, MINIMUM | | ELEVATION FOR ALL EQUIPMENT SERVICING THE BUILDING IS | | 7.5'. THE EQUIPMENT WHICH IS CURRENTLY 7.1' WILL BE | | REQUIRED TO BE RAISED PRIOR TO FINAL INSPECTION. IF IT | | IS NOT RAISED PRIOR TO FORM BOARD SURVEY/BUILDING UNDER | | CONSTRUCTION ELEVATION CERTIFICATE, THIS WILL BE A | | PROVISO ITEM AT THAT TIME BUT WILL BE REQUIRED FOR | | "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE. | | | | 7. PAGE 2, BUILDING STREET ADDRESS, PLEASE REVISE IF | | ADDRESS OF STRUCTURE HAS CHANGED. | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-06-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-26 |
Time |
19:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-26 |
Time |
19:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-30 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-30 |
Time |
06:41 |
Sent To |
|
|
Notes |
2014-05-30 08:03:14 | 2010 FBC | | | | PLUMBING DENIED | | | | 1) SUBMIT TWO SETS OF A PLUMBING RISER DIAGRAM FOR THE | | "PRE-PLUMBING FOR FUTURE BATHROOM". CITY AMENDMENTS | | 107.3.5.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2014-08-26 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-08-27 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-08-26 |
Time |
11:24 |
Sent To |
I |
|
Notes |
2014-08-26 11:25:21 | NOTES: | | | | 1.) SPOKE TO ANTHONY HARRINGTON, PROJECT ARCHITECT, ON | | 8/27/2014. MR. HARRINGTON STATED THAT THERE ARE NO | | TREES TO BE REMOVED IN THE SCOPE OF WORK. | | | | 2.) SPOKE TO ANTHONY HARRINGTON, PROJECT ARCHITECT, ON | | 8/27/2014. THE 2-STORY GARAGE/STORAGE ADDITION WILL | | NEED TO MEET SETBACK REQUIREMENTS FOR A PRIMARY | | STRUCTURE PER THE REGULATIONS FOR SF7. MR. HARRINGTON | | STATED THAT THE ADDITION WILL HAVE A SIDE SETBACK OF 5 | | FT. FROM THE PROPERTY LINE IF THE PROPERTY OWNER MOVES | | FORWARD WITH THE MINOR SUBDIVISION (REFERENCE: PB1645). | | | | | | | | | 2014-08-25 11:22:57 | 8/25/14 ZONING SENT TO LL. SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2014-06-23 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-06-23 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-06-23 |
Time |
14:14 |
Sent To |
B |
|
Notes |
2014-06-23 14:15:45 | ** FAILED ** | | | | REPEAT COMMENT FROM 5/19/2014: THE CONDITIONS OF THE | | MINOR SUBDIVISION APPLICATION FOR TAYLOR ESTATES, LOT 3 | | IN CITY LETTER DATED 3/5/14 HAVE NOT BEEN ADDRESSED. | | PLEASE ADDRESS PRIOR TO PERMITTING. | | | | PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS | | MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE | | @ (561)822-1458 IF YOU HAVE QUESTIONS. | 2014-06-19 12:32:34 | 6/19/14 ZONING SENT TO LL. SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-05-19 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-05-19 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-05-19 |
Time |
16:06 |
Sent To |
|
|
Notes |
2014-05-19 16:11:49 | ** FAILED ** | | | | 1.) THE CONDITIONS OF THE MINOR SUBDIVISION APPLICATION | | FOR TAYLOR ESTATES LOT 3 IN CITY LETTER DATED 3/5/14 | | HAVE NOT BEEN ADDRESSED. PLEASE ADDRESS PRIOR TO | | PERMITTING. | | | | PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS | | MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE | | @ (561) 822-1458 IF YOU HAVE QUESTIONS. | | | | | | NOTE: | | - ALL EXISTING AND PROPOSED ACCESSORY STRUCTURES (I.E. | | PROPOSED GARAGE/STUDIO AND CABANA) CANNOT EXCEED 1,000 | | SQ. FT. (ZLDR S.94-304(B)(1)) | 2014-05-15 16:36:16 | 5/15/14 |
|
|