Plan Review Details - Permit 14050331
Plan Review Stops For Permit 14050331
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By rmcdouga Date 2014-08-23 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2014-08-23 Time 06:54 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 17:12 Rev Time 0.00
Received By rmcdouga Date 2014-06-28 Time 10:03 Sent To E
Notes
2014-06-30 17:23:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD ZONE A5 WITH A 7' BFE. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE REQUIRES NEW CONSTRUCTION TO
 HAVE A FINISH FLOOR ELEVATION OF 7.5' NGVD ( WHICH
 INCLUDES A SIX INCH FREEBOARD ). AN ELEVATION
 CERTIFICATE IS REQUIRED FOR THE PROPOSED GARAGE AND
 EQUIPMENT.
 THE PLANS ARE REQUIRED TO SHOW COMPLIANCE WITH FEMA
 REQUIREMENTS. THE ENCLOSED GARAGE CAN ONLY BE USED FOR
 THE PARKING OF VEHICLES. APPLIANCES, HEATING AND
 COOLING EQUIPMENT, PLUMBING FIXTURES, ELECTRICAL
 EQUIPMENT ( OTHER THAN THE MINIMUM REQUIRED FOR LIFE
 SAFETY AND ELECTRIC CODE REQUIREMENTS FOR BUILDING
 ACCESS AND STORAGE AREAS ) AND MATERIALS THAT ARE NOT
 FLOOD DAMAGE-RESISTANT ARE NOT ALLOWED BELOW BFE. SHOW
 THE LOCATIONS AND NUMBER OF VENT OPENINGS ON THE PLANS.
 ONLY THE AREA OF THE VENT OPENINGS THAT ARE BELOW THE
 BFE CAN BE COUNTED TOWARD THE REQUIRED AMOUNT OF FLOOD
 VENT OPENING AREA. FBC R322 SEE ALSO FEMA PUBLICATION
 TECHNICAL BULLETIN 1 / AUGUST 2008 FOR ADDITIONAL
 INFORMATION.
 - THE ELEVATION OF THE GARAGE IS GIVEN AS 7'.0" NGVD ON
 THE PLANS, WHICH IS SIX INCHES BELOW THE REQUIRED FLOOD
 ELEVATION. IF THE FLOOD VENTS ARE INSTALLED AT THE
 FINISH FLOOR ELEVATION, ONLY THE SIX INCHES OF THE VENT
 CAN BE COUNTED TOWARD THE REQUIRED FLOOD OPENING AREA.
 PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED AREA OF
 FLOOD OPENINGS WILL BE PROVIDED.
  
 2) THE STRUCTURE IS LOCATED IN AN AREA OF QUESTIONABLE
 SOIL. SUBMIT TWO SETS OF A SIGNED AND SEALED SUB
 SURFACE SOIL REPORT. FBC R401.4
 - INDICATE WHAT METHODS WILL BE USED TO RESOLVE THE
 QUESTIONABLE SOIL ISSUE BASED ON THE RECOMMENDATIONS ON
 PAGE 3 OF THE SOIL REPORT.
  
 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 SMART VENT ENGINEERED FLOOD VENTS (FL #5822.3) WITH
 INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE 9N-3.
 -THE INSTALLATION INSTRUCTION PART OF THE PRODUCT
 APPROVALS FOR THE SMART VENTS WERE NOT SUBMITTED.
 PLEASE SUBMIT REQUESTED INFORMATION. DCA RULE 9N-3
  
 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 SECOND FLOOR STUDIO. CITY AMENDMENTS 107.3.5.3
 - THESE WERE NOT IN THE RE-SUBMITTAL.
  
 5) SPECIFY THE R- VALUE OF THE INSULATION THAT WILL BE
 USED IN THE FLOOR ABOVE THE GARAGE. FBC ENERGY SECTION
 402
 - THE R-VALUE IS SPECIFIED AS R-11 FOR THE FLOOR AND
 WALLS OF SECOND FLOOR. THE MINIMUM FOR EACH USING THE
 PERSCRIPTIVE METHOD IS R-13, UNLESS THE PERFORMANCE
 METHOD IS USED.
  
 6) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE PRODUCT APPROVAL FOR THE TAMKO UNDERLAYMENT NOA
 NO. 12-0406.07 WILL BE USED. CITY AMENDMENTS 107.2.1
 - THIS COMMENT WAS NOT ADDRESSED.
  
 7) SPECIFY WHICH ONE OF THE FASTENING METHODS LISTED IN
 THE PRODUCT APPROVAL FOR THE HANSON ROOF TILE NOA NO.
 12-1218.14 WILL BE USED TO INSTALL THE ROOF TILE AND
 RESIST THE OVERTURN MOMENT. FBC R905.3
 - THIS COMMENT WAS NOT ADDRESSED.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH ONE OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-30 Cont ID  
Sent By rmcdouga Date 2014-05-30 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2014-05-29 Time 17:49 Sent To  
Notes
2014-05-30 11:04:282010 FBC
  
 DENIED BY BUILDING
  
 1) THE PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD ZONE A5 WITH A 7' BFE. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE REQUIRES NEW CONSTRUCTION TO
 HAVE A FINISH FLOOR ELEVATION OF 7.5' NGVD ( WHICH
 INCLUDES A SIX INCH FREEBOARD ). AN ELEVATION
 CERTIFICATE IS REQUIRED FOR THE PROPOSED GARAGE AND
 EQUIPMENT.
 TWO COPIES OF A BROCHURE FOR SMART VENT FLOOD VENTS
 WERE IN THE PAPER WORK THAT WAS SUBMITTED. IF THE
 INTENT IS TO CONSTRUCT THE GARAGE WITH A FINISH FLOOR
 BELOW THE REQUIRED BASE FLOOD ELEVATION, THE PLANS ARE
 REQUIRED TO SHOW COMPLIANCE WITH FEMA REQUIREMENTS. THE
 ENCLOSED GARAGE CAN ONLY BE USED FOR THE PARKING OF
 VEHICLES. APPLIANCES, HEATING AND COOLING EQUIPMENT,
 PLUMBING FIXTURES, ELECTRICAL EQUIPMENT ( OTHER THAN
 THE MINIMUM REQUIRED FOR LIFE SAFETY AND ELECTRIC CODE
 REQUIREMENTS FOR BUILDING ACCESS AND STORAGE AREAS )
 AND MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE
 NOT ALLOWED BELOW BFE. SHOW THE LOCATIONS AND NUMBER OF
 VENT OPENINGS ON THE PLANS. ONLY THE AREA OF THE VENT
 OPENINGS THAT ARE BELOW THE BFE CAN BE COUNTED TOWARD
 THE REQUIRED AMOUNT OF FLOOD VENT OPENING AREA. FBC
 R322 SEE ALSO FEMA PUBLICATION TECHNICAL BULLETIN 1 /
 AUGUST 2008 FOR ADDITIONAL INFORMATION.
  
 2) THE STRUCTURE IS LOCATED IN AN AREA OF QUESTIONABLE
 SOIL. SUBMIT TWO SETS OF A SIGNED AND SEALED SUB
 SURFACE SOIL REPORT. FBC R401.4
  
 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 SMART VENT ENGINEERED FLOOD VENTS (FL #5822.3) WITH
 INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE 9N-3.
  
 4) THE WIND LOAD INFORMATION ON SHEET A.10 AND A.11 ARE
 INCORRECT. THE TWO STORY STRUCTURE IS LOCATED IN A 170
 MPH VULT , 132 VASD WINDSPEED AND EXPOSURE CATEGORY D.
 THE COMPONENT AND CLADDING PRESSURES WILL NEED TO BE
 INCREASED ACCORDINGLY. FBC R301.2.1
  
 5) THE SIMPSON MTS 12 STRAPS THAT ARE SPECIFIED FOR THE
 ROOF TRUSS TO WALL CONNECTIONS DO NOT HAVE ANY
 RESISTANCE VALUES FOR LATERAL LOADS. SPECIFY HOW THE
 LATERAL ROOF LOADS WILL BE TRANSFERED TO THE WALLS. FBC
 R802.1.6.5
  
 6) THE ROOF NAILING PATTERN DIAGRAM ON SHEET A.11 IS
 NOT CORRECT. THE CORNERS OF THE HIP ROOF ARE ROOF ZONE
 3. FBCR FIGURE R301.2(7)
  
 7) THE AREA ABOVE THE GARAGE IS SPECIFIED AS STORAGE ON
 SHEET A.03, AS A STUDIO ON A.06 AND AS LIVING SPACE ON
 A.11. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 8) SHOW COMPLIANCE WITH FBCR FOR TERMITE PROTECTION.
 FBC R318.6
  
 9) THE EGRESS DOOR TO THE SECOND FLOOR IS REQUIRED TO
 HAVE A 32" CLEAR WIDTH MEASURED FROM THE FACE OF THE
 DOOR TO THE STOP WITH THE DOOR OPEN 90 DEGREES. FBC
 R311.2
  
 10) SPECIFY THE RISER HEIGHT AND TREAD DEPTH FOR THE
 EXIT STAIRS THAT WERE NOT PROVIDED IN THE DETAIL ON
 A.11. FBC R311.7
  
 11) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 SECOND FLOOR STUDIO. CITY AMENDMENTS 107.3.5.3
  
 12) SPECIFY THE R- VALUE OF THE INSULATION THAT WILL BE
 USED IN THE FLOOR ABOVE THE GARAGE. FBC ENERGY SECTION
 402
  
 13) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE PRODUCT APPROVAL FOR THE TAMKO UNDERLAYMENT NOA
 NO. 12-0406.07 WILL BE USED. CITY AMENDMENTS 107.2.1
  
 14) SPECIFY WHICH ONE OF THE FASTENING METHODS LISTED
 IN THE PRODUCT APPROVAL FOR THE HANSON ROOF TILE NOA
 NO. 12-1218.14 WILL BE USED TO INSTALL THE ROOF TILE
 AND RESIST THE OVERTURN MOMENT. FBC R905.3
  
 15) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS.
  
 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH ONE OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 11:11 Rev Time 0.00
Received By dhayes Date 2014-07-01 Time 11:11 Sent To  
Notes
2014-07-01 11:50:28DATE: 7/1/2014
 PROJECT: CHURCHILL RESIDENCE
 PERMIT#: 14050331
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE
 CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE
 250.68(A) AND (B).
  
 2) PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES
 AND DEDICATED WORKING SPACE AND ILLUMINATION AT A/C
 DISCONNECTS. NEC 110.26,
  
 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE
 SHALL BE GFCI PROTECTED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 17:29 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 16:45 Sent To  
Notes
2014-05-12 17:29:20ELECTRICAL PROVISO:
  
 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE
 CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE
 250.68(A) AND (B).
  
 2) 2010 FBC- 107.3.5 PROVIDE SMOKE DETECTORS PURSUANT
 TO FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 3) 2010 FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-26 Cont ID  
Sent By llouie Date 2014-08-27 Time 11:27 Rev Time 0.00
Received By llouie Date 2014-08-21 Time 06:53 Sent To  
Notes
2014-08-23 06:54:11SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 11:50 Rev Time 0.00
Received By dhayes Date 2014-06-18 Time 18:09 Sent To  
Notes
2014-06-18 18:13:19INCOMING SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-30 Cont ID  
Sent By rmcdouga Date 2014-05-30 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2014-05-09 Time 14:46 Sent To  
Notes
2014-05-14 14:46:37* * * * EXPEDITED * * * *
  
 R 26
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By rmcdouga Date 2014-08-23 Time 07:22 Rev Time 0.00
Received By rmcdouga Date 2014-08-23 Time 07:22 Sent To  
Notes
2014-08-23 07:26:44MU2014-18593, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 16:17 Sent To  
Notes
2014-06-30 16:18:26AN IMPACT REVIEW FEE BY PALM BEACH COUNTY IS REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-30 Cont ID  
Sent By rmcdouga Date 2014-05-30 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2014-05-30 Time 14:49 Sent To  
Notes
2014-05-30 14:52:51AN IMPACT REVIEW FEE BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-30 Cont ID  
Sent By rmcdouga Date 2014-05-30 Time 06:41 Rev Time 0.00
Received By rmcdouga Date 2014-05-30 Time 14:09 Sent To  
Notes
2014-05-30 06:48:12A MECHANICAL PERMIT IS REQUIRED TO RELOCATED THE TWO
 EXISTING A/C CONDENSERS. NO OTHER MECHANICAL WORK SHOWN
 ON PLANS. SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2014-09-18 Cont ID  
Sent By shill Date 2014-09-15 Time 16:05 Rev Time 0.00
Received By shill Date 2014-09-15 Time 16:05 Sent To  
Notes
2014-09-15 16:31:14****CORRECTIONS****
 ****THIS IS A "FAILED" PLAN REVIEW - "N" ENTERED TO
 ALLOW PERMIT CARD TO PRINT****
 ELEVATION CERTIFICATE FOR 14060942 AND 14050331,
 PREPARED BY ROBERT J. CAJAL, WALLACE SURVEYING CORP
 DATED 12/26/13
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROPERTY IS NOW OWNED BY 101 CHURCHILL ROAD LLC. AS
 DISCUSSED, PLEASE HAVE A CONTRACTOR APPLY FOR ALL OPEN
 PERMITS WHICH WERE OBTAINED UNDER THE FLORIDA STATUTE
 489 OWNER BUILDER EXEMPTION. SEE ATTORNEY GENERAL
 OPINION AGO 91-05.
  
 PRIOR TO FORM BOARD INSPECTION ("BUILDING UNDER
 CONSTRUCTION"), PLEASE CORRECT THE FOLLOWING ITEMS ON
 THE ELEVATION CERTIFICATE TO AVOID FIELD DELAYS:
  
 1. A1, A2, A3, IT IS MY UNDERSTANDING THAT THIS PARCEL
 IS UNDERGOING A REPLAT. REVISE THE INFORMATION IN THESE
 FIELDS IF APPLICABLE.
  
 2. A5, LATITUDE/LONGITUDE DOES NOT APPEAR TO BE
 CORRECT. THIS IS TO BE ACCURATE WITHIN 66' OF THE
 CENTER OF THE FRONT OF THE BUILDING.
  
 3. A8C, PLEASE PROVIDE CLARIFICATION ABOUT THE NATURE
 OF THE FLOOD VENTS AND PROVIDE CALCULATIONS OR
 INFORMATION AS TO HOW NET OPENINGS HAS BEEN DETERMINED.
 IN THE PHOTOGRAPH, THE VENT APPEARS BLOCKED. YOU MAY
 FIND THE FOLLOWING DOCUMENT HELPFUL:
  
 TECHNICAL BULLETIN 1, OPENINGS IN FOUNDATIN WALLS AND
 WALLS OF ENCLOSURES (2008)
 HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/2644
  
 VENTS ARE TO BE INSTALLED WITHIN 1' OF ADJACENT GRADE.
 PLEASE VERIFY WITH PHOTOGRAPHS. ONLY THE PORTION OF THE
 VENT WHICH IS BELOW THE BFE IS TO BE INCLUDED IN THE
 NET OPENING AREA. SEE PAGE 19 OF THE TECHNICAL
 BULLETIN; VENTS THAT CAN BE CLOSED MANUALLY OR THAT
 HAVE COVERS ARE NOT ACCEPTABLE AS FLOOD VENTS.
  
 4. B1, NFIP COMMUNITY NAME IS "CITY OF WEST PALM BEACH"
 (REMOVE "UNINCORPORATED").
  
 5. B6, FIRM INDEX DATE SHOULD BE 03/01/1979.
  
 6. C2E, AS ADVISED DURING PLAN REVIEW, MINIMUM
 ELEVATION FOR ALL EQUIPMENT SERVICING THE BUILDING IS
 7.5'. THE EQUIPMENT WHICH IS CURRENTLY 7.1' WILL BE
 REQUIRED TO BE RAISED PRIOR TO FINAL INSPECTION. IF IT
 IS NOT RAISED PRIOR TO FORM BOARD SURVEY/BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE, THIS WILL BE A
 PROVISO ITEM AT THAT TIME BUT WILL BE REQUIRED FOR
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE.
  
 7. PAGE 2, BUILDING STREET ADDRESS, PLEASE REVISE IF
 ADDRESS OF STRUCTURE HAS CHANGED.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-26 Cont ID  
Sent By rmcdouga Date 2014-06-26 Time 19:01 Rev Time 0.00
Received By rmcdouga Date 2014-06-26 Time 19:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-30 Cont ID  
Sent By rmcdouga Date 2014-05-30 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2014-05-30 Time 06:41 Sent To  
Notes
2014-05-30 08:03:142010 FBC
  
 PLUMBING DENIED
  
 1) SUBMIT TWO SETS OF A PLUMBING RISER DIAGRAM FOR THE
 "PRE-PLUMBING FOR FUTURE BATHROOM". CITY AMENDMENTS
 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-26 Cont ID  
Sent By llouie Date 2014-08-27 Time 11:24 Rev Time 0.00
Received By llouie Date 2014-08-26 Time 11:24 Sent To I
Notes
2014-08-26 11:25:21NOTES:
  
 1.) SPOKE TO ANTHONY HARRINGTON, PROJECT ARCHITECT, ON
 8/27/2014. MR. HARRINGTON STATED THAT THERE ARE NO
 TREES TO BE REMOVED IN THE SCOPE OF WORK.
  
 2.) SPOKE TO ANTHONY HARRINGTON, PROJECT ARCHITECT, ON
 8/27/2014. THE 2-STORY GARAGE/STORAGE ADDITION WILL
 NEED TO MEET SETBACK REQUIREMENTS FOR A PRIMARY
 STRUCTURE PER THE REGULATIONS FOR SF7. MR. HARRINGTON
 STATED THAT THE ADDITION WILL HAVE A SIDE SETBACK OF 5
 FT. FROM THE PROPERTY LINE IF THE PROPERTY OWNER MOVES
 FORWARD WITH THE MINOR SUBDIVISION (REFERENCE: PB1645).
  
  
  
  
2014-08-25 11:22:578/25/14 ZONING SENT TO LL. SG

Review Stop Z ZONING
Rev No 2 Status F Date 2014-06-23 Cont ID  
Sent By llouie Date 2014-06-23 Time 14:14 Rev Time 0.00
Received By llouie Date 2014-06-23 Time 14:14 Sent To B
Notes
2014-06-23 14:15:45** FAILED **
  
 REPEAT COMMENT FROM 5/19/2014: THE CONDITIONS OF THE
 MINOR SUBDIVISION APPLICATION FOR TAYLOR ESTATES, LOT 3
 IN CITY LETTER DATED 3/5/14 HAVE NOT BEEN ADDRESSED.
 PLEASE ADDRESS PRIOR TO PERMITTING.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561)822-1458 IF YOU HAVE QUESTIONS.
2014-06-19 12:32:346/19/14 ZONING SENT TO LL. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By llouie Date 2014-05-19 Time 16:06 Rev Time 0.00
Received By llouie Date 2014-05-19 Time 16:06 Sent To  
Notes
2014-05-19 16:11:49** FAILED **
  
 1.) THE CONDITIONS OF THE MINOR SUBDIVISION APPLICATION
 FOR TAYLOR ESTATES LOT 3 IN CITY LETTER DATED 3/5/14
 HAVE NOT BEEN ADDRESSED. PLEASE ADDRESS PRIOR TO
 PERMITTING.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
  
 NOTE:
 - ALL EXISTING AND PROPOSED ACCESSORY STRUCTURES (I.E.
 PROPOSED GARAGE/STUDIO AND CABANA) CANNOT EXCEED 1,000
 SQ. FT. (ZLDR S.94-304(B)(1))
2014-05-15 16:36:165/15/14