Plan Review Stops For Permit 14050208 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-05-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-05-08 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-05-08 |
Time |
07:38 |
Sent To |
|
|
Notes |
2014-05-08 07:41:54 | ****CORRECTIONS**** | | ****REVISED 5/10/14**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. 5/10/14 INFORMATIONAL ONLY - FBC R310, FBC EB 604.1, | | REVISED FLOOR PLAN NOT REQUIRED AS PREVIOUS WINDOWS | | APPEAR TO BE AWNING BASED ON PHOTOGRAPHS | | | | 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | (AVAILABLE IN THE LOBBY AND AT | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | PROVIDE CALCULATIONS. | | | | NOTE THAT ORIGINAL PERMIT WAS ISSUED WITH A REQUIREMENT | | FOR SHUTTERS. I WAS UNABLE TO LOCATE A SHUTTER PERMIT | | FOR THIS PROJECT. PLEASE PROVIDE PERMIT NUMBER IF A | | SHUTTER PERMIT WAS OBTAINED. | | | | | | |
|
|