Plan Review Details - Permit 14050190
Plan Review Stops For Permit 14050190
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-14 Cont ID  
Sent By dhayes Date 2014-05-14 Time 16:33 Rev Time 0.00
Received By dhayes Date 2014-05-14 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-30 Cont ID  
Sent By jwitmer Date 2014-05-30 Time 07:49 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 07:57 Sent To  
Notes
2014-05-28 08:02:24SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-14 Cont ID  
Sent By dhayes Date 2014-05-14 Time 16:33 Rev Time 0.00
Received By dhayes Date 2014-05-06 Time 12:35 Sent To  
Notes
2014-05-07 13:11:05SENT TO <45K ELECTRIC BOX. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-30 Cont ID  
Sent By jwitmer Date 2014-05-30 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2014-05-30 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By jwitmer Date 2014-05-07 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2014-05-07 Time 12:32 Sent To E
Notes
2014-05-07 13:08:45BUILDING PLAN REVIEW
 REVISION: 14050190
 PERMIT: 13120825
 ADD: 5731 PREMIER PARK DR
 CONT: ZIRLBACH
 TEL: (941)539-4756
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 07/2014
 ACTION: DENIED
  
 1) SHEET P1.1PLUMBING DENIED:
 2010 FL ACCESSIBILITY CODE 211 DRINKING FOUNTAINS
 NO SPECIFICATIONS PROVIDED:
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE 50 PERCENT OF THE DRINKING FOUNTAINS
 YIELDS A FRACTION, 50 PERCENT SHALL BE PERMITTED TO BE
 ROUNDED UP OR DOWN PROVIDED THAT THE TOTAL NUMBER OF
 DRINKING FOUNTAINS COMPLYING WITH 211 EQUALS 100
 PERCENT OF DRINKING FOUNTAINS.
  
 2) THE NEW ELECTRIC WATER FOUNTAIN DOES NOT PROVIDE
 WHERE IT WILL TIE INTO THE SANITARY AND WHERE THE VENT
 WILL BE LOCATED. 2010
 FBC-P TABLE 709.1 DRAINAGE FIXTURE UNITS & 908.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]