Plan Review Stops For Permit 14050157 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-05-09 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-09 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-05-09 |
Time |
16:24 |
Sent To |
|
|
Notes |
2014-05-09 16:39:18 | GEC TO BE INCREASED TO #2CU PER ARTICLE 250.66 OF THE | | 2008 EDITION OF THE NEC | | | | AN INTERSYSTEM BONDING TERMINATION IS REQUIRED PER | | ARTICLE 250.94 OF THE 2008 EDITION OF THE NEC |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-05-09 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-09 |
Time |
16:39 |
Rev Time |
|
Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2014-05-06 10:10:32 | ROUTED TO ELECTRICAL LESS THAN $5000 |
|
|
|