Plan Review Details - Permit 14050143
Plan Review Stops For Permit 14050143
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By dhayes Date 2014-05-06 Time 08:33 Rev Time 0.00
Received By dhayes Date 2014-05-06 Time 08:33 Sent To PC
Notes
2014-05-06 09:12:45PER THE 2010 FBC 107.3.5.3 #9
 AND 2008 NEC 210.52
  
 PLEASE SUBMIT A REVISION INDICATING THE FOLLOWING
 INFORMATION PRIOR TO THE INITIAL INSPECTION:
  
 1) PLEASE PROVIDE A DETAILED FLOOR PLAN OF THE KITCHEN.
  
 2) A RISER DIAGRAM OF THE SERVICE INCLUDING ALL
 CONDUITS AND WIRE SIZES.
  
 3) A PANEL SCHEDULE INCLUDING ALL CIRCUIT SIZES.
  
 4) A LOAD CALCULATION.
  
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6717 OR [email protected]
 THANK YOU.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By dhayes Date 2014-05-06 Time 08:33 Rev Time 0.00
Received By dhayes Date 2014-05-05 Time 16:02 Sent To  
Notes
2014-05-05 16:03:03ROUTED TO ELECTRICAL $5000 & UNDER