Plan Review Details - Permit 14050097
Plan Review Stops For Permit 14050097
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-09-22 Cont ID  
Sent By jwitmer Date 2014-09-22 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2014-09-20 Time 11:45 Sent To  
Notes
2014-09-22 12:07:17BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. SEPT. 22/ 2014
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) THE CONTRACTOR HAVE ELECTED TO SUBMIT THE PRODUCT
 APPROVALS AFTER PERMIT ISSUANCE. THESE ITEMS WILL BE
 CONSIDERED A NO FEE DEFERRED SUBMITTAL PER 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 107.3.4.2.
  
 1A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 1B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 10:46 Sent To  
Notes
2014-08-25 12:18:18BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. AUG.25/ 2014
 ACTION: DENIED
  
 1) COMPLIED.
  
 1A) COMPLIED.
  
 1B) 3RD REQUEST. SEMI-COMPLIED. G1-101 DINING ROOM 131
 INDICATES A OCCUPANCY LOAD OF 67 TRAVELING THROUGH THE
 EXTERIOR DOUBLE DOORS. WHEN FIGURING THE OCCUPANCY LOAD
 AT 15 SQ FT / OCC WITHOUT THE BAR THE LOAD IS APPROX.
 60 OCCUPANTS WHICH WILL REQUIRE A 2ND EXIT. 2010 FBC-B
 1008.1.2.
 THE PLANS NOW SHOW THE 2ND MEANS OF EGRESS THROUGH THE
 DINING ROOM # 130 INTO VESTIBULE 127 AND A TWO WAY EXIT
 DIRECTIONAL INTO CORRIDOR 128 WHICH LEADS BACK TO THE
 FRONT ENTRY. THERE IS NO REMOTNESS BETWEEN THE (2)
 FRONT ENTRY DOORS.
  
 THE OTHER ISSUE IS WHERE THE VESTIBULE 127 LEADS YOU TO
 CORRIDOR # 128 WITH THE DOUBLE DIRECTIONAL SIGN IF YOU
 MAKE A RIGHT HAND TURN THERE IS A OCCUPANT LOAD
 DIRECTIONAL ARROW (OCC LOAD 48) POINTING TO THE FRONT
 OF THE BUILDING IF THIS WAS A DOUBLE ARROWED ALLOWING
 THE OCCUPANTS FROM THE VESTIBULE TO TRAVEL UP CORRIDOR
 128 MAKE A LEFT INTO COORIDOR 190 WHICH DOES GO TO THE
 EXTERIOR OF THE BUILDING. YOU WOULD HAVE TO STILL MEET
 THE MAXIMUM TRAVEL DISTANCE OF 250 FT. IF BOTH OF THE
 FRONT ENTRY WERE LOST BECAUSE OF FIRE YOU WOULD STILL
 BE ABLE TO USE THIS OTHER EXIT. 1015.2.2 THREE OR MORE
 EXIT ACCESS DOORWAYS.
  
 1C) COMPLIED.
  
 1D) 3RD REQUEST. IN BOTH THE CULTURAL CLASS # 125 & THE
 TRAINING ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC.
 THE 20 SQ FT IS TAKEN WITH AN EDUCATIONAL SETTING
 KINDERGADEN -12TH GRADE. FOR ADULT EDUCATION IN
 COLLEGES IT IS CONSIDERED BUSINESS OCCUPANCY. THIS IS A
 MULTI-PURPOSE ROOM WHERE AN ASSEMBLY OCCUPANCY CAN BE
 TAKEN AT 15 SQ FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 WHERE ARE DIFFERENCES WITHIN THE CODES THE MORE
 STRINGENT OF THE CODES WOULD BE WHAT WE USE. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 102.1 GENERAL. WHERE, IN ANY
 SPECIFIC CASE, DIFFERENT SECTIONS OF THIS CODE SPECIFY
 DIFFERENT MATERIALS, METHODS OF CONSTRUCTION OR OTHER
 REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE
 THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A
 SPECIFIC REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 2) SHEET AE105:
  
 2A) COMPLIED.
  
 2B) COMPLIED. 1016.1 EXC# 3.
  
 3) COMPLIED, DO NOT COMBINE RESTROOMS FOR COUNT OF 6 OR
 MORE.
  
 4)COMPLIED.
  
 5) COMPLIED, SPOKE WITH ENGINEER, SHOWED ME WHICH SHEET
 THEY WERE LOCATED.
  
  
 6) 3RD REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 PLEASE BE AWARE WHEN GIVEN WRITTEN DOCUMENTATION WHEN
 THE WIND PRESSURES ARE CORRECT, THE PRODUCT APPROVALS
 CAN BE A DEFERRED SUBMITTAL 107.3.4.2.
  
 7) 3RD REQUEST. CAN BE A DEFERRED SUBMITTAL 107.3.4.2.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) COMPLIED.
  
 9) THANK YOU FOR NARRATIVE.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-01 Cont ID  
Sent By jwitmer Date 2014-08-01 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2014-08-01 Time 05:51 Sent To  
Notes
2014-08-01 06:45:15BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 2ND REVIEW
 DATE: FRI. AUG. 01/ 2014
 ACTION: DENIED
  
 1) 2ND REQUEST. NOTE SHEET G-1 101 LIFE SAFETY SHEET
 LOWER LEVEL UNDERTHE HEADING USE & OCCUPANCY INDICATES
 THE KITCHEN AS 200 GROSS, THE FIRE COMMENT STATES THAT
 UNDER THE FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN
 THERE IS A DIFFERENCE IN CODES, THE MOST RESTRICTIVE
 SHALL APPLY. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 102.1.
  
 1A) 2ND REQUEST. THE BUILDING CODE ANALYSIS FOUND ON
 G-1-101 DOES NOT INDICATE IF THE OCCUPANCIES ARE
 DESIGNED AS SEPARATED OR NON-SEPARATED?
 2010 FBC-B 508.3 OR 508.4.
  
 1B) 2ND REQUEST. G1-101 DINING ROOM 131 INDICATES A
 OCCUPANCY LOAD OF 67 TRAVELING THROUGH THE EXTERIOR
 DOUBLE DOORS. WHEN FIGURING THE OCCUPANCY LOAD AT 15 SQ
 FT / OCC WITHOUT THE BAR THE LOAD IS APPROX. 60
 OCCUPANTS WHICH WILL REQUIRE A 2ND EXIT. 2010 FBC-B
 1008.1.2.
 PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE
 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS.
  
 1C) 2ND REQUEST. G1-101 CARD ROOM 185 HAS (2) EXIT
 DOORS THAT CONVERGE INTO A SINGLE MEANS OF EGRESS,
 THERE IS NO 2 SEPARATE MEANS OF EGRESS FROM THIS ROOM.
 A CONVERGING MENAS OF EGRESS.
  
 1D) 2ND REQUEST. IN BOTH THE CULTURAL CLASS # 125 & THE
 TRAINING ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC.
 THE 20 SQ FT IS TAKEN WITH AN EDUCATIONAL SETTING
 KINDERGADEN -12TH GRADE. FOR ADULT EDUCATION IN
 COLLEGES IT IS CONSIDERED BUSINESS OCCUPANCY. THIS IS A
 MULTI-PURPOSE ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE
 TAKEN AT 15 SQ FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 2) SHEET AE105:
  
 2A) 2ND REQUEST. MEETING ROOMS 225 A& B BOTH INDICATE
 THE USE OF A NANAWALL SYSTEM, PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATION AS TO HOW THIS SYSTEM WILL
 FOLD BACK AND NOT PROJECT INTO THE EXIT ACCESS CORRIDOR
 MORETHAN (7INCHES). 2010 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 2B) 2ND REQUEST. THE MONUMENTAL STAIR # 209 INDICATES
 SEE DETAIL #5/ AE.402 THIS DETAIL DIRECTS YOU TO DETAIL
 # 1/ A320 THIS IS A ELEVATION CUT SECTION THROUGH THE
 MONUMENTAL STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2
 EXCEPTION 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY
 SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13.
  
 3) 2ND REQUEST. AE401 PLEASE REVIEW THE 2010
 FBC-ACCESSIBILITY CODE SECTION 213.3.1 TOILET
 COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS.
 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
  
 604.8.2.2 DOORS.
 TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS
 TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM.
  
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 4) 2ND REQUEST. SHEET AE501:
 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010
 FL ACC CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 4B) 2ND REQUEST. THE GRAB BAR RANGE IS THE SAME BUT THE
 HEIGHT OF THE GRAB BAR IS NO LONGER TO THE CENTERLINE
 OF THE GRAB BAR BUT TO TOP OF THE GRIPPING SURFACE SEE
 2010 FL ACC CODE 609.4.
  
 5) COMPLIED, SPOKE WITH ENGINEER, SHOWED ME WHICH SHEET
 THEY WERE LOCATED.
  
  
 6) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2ND REQUEST. THE PLANS INDICATE THIS IS A TYPE IIIA
 BUILDING, PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B
 TABLE 601 FIRE RATINGS WILL BE ACHIEVED.
  
 9) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-12 Cont ID  
Sent By jwitmer Date 2014-07-12 Time 15:37 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 14:14 Sent To  
Notes
2014-07-05 12:43:32BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 12/ 2014
 ACTION: DENIED
  
 1) NOTE SHEET G-1 101 LIFE SAFETY SHEET LOWER LEVEL
 UNDERTHE HEADING USE & OCCUPANCY INDICATES THE KITCHEN
 AS 200 GROSS, THE FIRE COMMENT STATES THAT UNDER THE
 FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN THERE IS A
 DIFFERENCE IN CODES, THE MOST RESTRICTIVE SHALL APPLY.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 102.1.
  
 1A) THE BUILDING CODE ANALYSIS FOUND ON G-1-101 DOES
 NOT INDICATE IF THE OCCUPANCIES ARE DESIGNED AS
 SEPARATED OR NON-SEPARATED?
 2010 FBC-B 508.3 OR 508.4.
  
 1B) G1-101 DINING ROOM 131 INDICATES A OCCUPANCY LOAD
 OF 67 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS. WHEN
 FIGURING THE OCCUPANCY LOAD AT 15 SQ FT / OCC WITHOUT
 THE BAR THE LOAD IS APPROX. 60 OCCUPANTS WHICH WILL
 REQUIRE A 2ND EXIT. 2010 FBC-B 1008.1.2.
 PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE
 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS.
  
 1C) G1-101 CARD ROOM 185 HAS (2) EXIT DOORS THAT
 CONVERGE INTO A SINGLE MEANS OF EGRESS, THERE IS NO 2
 SEPARATE MEANS OF EGRESS FROM THIS ROOM. A CONVERGING
 MENAS OF EGRESS.
  
 1D) IN BOTH THE CULTURAL CLASS # 125 & THE TRAINING
 ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC. THE 20 SQ
 FT IS TAKEN WITH AN EDUCATIONAL SETTING KINDERGADEN
 -12TH GRADE. FOR ADULT EDUCATION IN COLLEGES IT IS
 CONSIDERED BUSINESS OCCUPANCY. THIS IS A MULTI-PURPOSE
 ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE TAKEN AT 15 SQ
 FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 2) SHEET AE105:
  
 2A) MEETING ROOMS 225 A& B BOTH INDICATE THE USE OF A
 NANAWALL SYSTEM, PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION AS TO HOW THIS SYSTEM WILL FOLD BACK AND
 NOT PROJECT INTO THE EXIT ACCESS CORRIDOR MORETHAN
 (7INCHES). 2010 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 2B) THE MONUMENTAL STAIR # 209 INDICATES SEE DETAIL #5/
 AE.402 THIS DETAIL DIRECTS YOU TO DETAIL # 1/ A320 THIS
 IS A ELEVATION CUT SECTION THROUGH THE MONUMENTAL
 STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2 EXCEPTION
 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY SPACED
 SPRINKLERS IN ACCORDANCE WITH NFPA 13.
  
 3) AE401 PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE
 SECTION 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS.
 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
  
 604.8.2.2 DOORS.
 TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS
 TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM.
  
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 4) SHEET AE501:
 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010
 FL ACC CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 4B) THE GRAB BAR RANGE IS THE SAME BUT THE HEIGHT OF
 THE GRAB BAR IS NO LONGER TO THE CENTERLINE OF THE GRAB
 BAR BUT TO TOP OF THE GRIPPING SURFACE SEE 2010 FL ACC
 CODE 609.4.
  
 5) THE STRUCTURAL SHEETS PROVIDE THE PRESSURES FOR THE
 ROOF IN VULT & VASD BUT THERE ARE NO PRESSURES GIVEN
 FOR THE WALL OPENINGS INTERIOR WALL ZONE 4 NOR THE
 CORNER WALL ZONE # 5. 2010 FBC-B 1609.6 .2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
  
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) THE PLANS INDICATE THIS IS A TYPE IIIA BUILDING,
 PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B TABLE 601
 FIRE RATINGS WILL BE ACHIEVED.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 10:34 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 10:34 Sent To  
Notes
2014-09-22 10:38:53DATE: 9/22/2014
 PROJECT: IBIS
 PERMIT#: 14050097
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SHEET EL103
 TERRACE AND STAIRS. LIGHTING CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. FBC 505.2.4
  
 2) SHEET EP104
 214-BAR TERRACE. FLUSH CEILING OUTLETS TO HAVE GFCI
 PROTECTION.
 212-BAR LOUNGE. PROVIDE MANUFACTURER?S PRODUCT
 SPECIFICATIONS ON FLOOR BOXES. FLOOR BOXES SHALL BE
 APPROVED TO MAINTAIN THE FIRE RATED INTEGRITY OF THE
 FLOOR.
  
 3) SHEET EP401
 207- STORAGE RM. THIS IS ELECTRICAL EQUIPMENT ROOM.
 THERE SHALL BE NO STORAGE ALLOWED AND SHALL BE
 IDENTIFIED WITH A SIGN STATING ?ELECTRIC ROOM. NO
 STORAGE ALLOWED? MAINTAIN WORKING CLEARANCE AND
 DEDICATED WORKING SPACE. NEC 110.26
  
 4) SHEET EP501
 A) INDICATE HOW THE CLUBHOUSE GROUNDING ELECTRODE
 SYSTEM TIES TO MDP BARN GROUNDING ELECTRODE SYSTEM.
 NOTE 3 THIS SHEET STATES TO BOND PANEL IT1 GROUND TO
 CLUBHOUSE GROUNDING ELECTRODE SYSTEM. THIS WOULD CREATE
 A DIFFERENCE OF POTENTIAL BETWEEN THE BARN AND
 CLUBHOUSE SYSTEMS.
 B) THE ATS AT THE NEW GENERATOR IS IDENTIFIED AS A
 4POLE ATS. I BELIEVE THIS IS MIS-LABELED AND THE INTENT
 IS FOR A STANDARD 3 POSITION ATS WITH A SOLID NEUTRAL
 FOR STANDARD OPTIONAL STANDBY SYSTEM AS ALSO NOTED THIS
 SHEET.
  
 5) SHEET ES101
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATOR, FIRE ALARM,
 SECURITY, CCTV, NETWORK, DATA/COM, AUDIO, VIDEO, AND
 SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By dhayes Date 2014-09-12 Time 15:10 Rev Time 0.00
Received By dhayes Date 2014-09-04 Time 15:39 Sent To  
Notes
2014-09-05 16:57:48DATE: 9/12/2014
 PROJECT: IBIS
 PERMIT#: 14050097
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SHEET EL103
 TERRACE AND STAIRS. LIGHTING CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. FBC 505.2.4
  
 2) SHEET EP104
 214-BAR TERRACE. FLUSH CEILING OUTLETS TO HAVE GFCI
 PROTECTION.
 212-BAR LOUNGE. PROVIDE MANUFACTURER?S PRODUCT
 SPECIFICATIONS ON FLOOR BOXES. FLOOR BOXES SHALL BE
 APPROVED TO MAINTAIN THE FIRE RATED INTEGRITY OF THE
 FLOOR.
  
 3) SHEET EP401
 207- STORAGE RM. THIS IS ELECTRICAL EQUIPMENT ROOM.
 THERE SHALL BE NO STORAGE ALLOWED AND SHALL BE
 IDENTIFIED WITH A SIGN STATING ?ELECTRIC ROOM. NO
 STORAGE ALLOWED? MAINTAIN WORKING CLEARANCE AND
 DEDICATED WORKING SPACE. NEC 110.26
  
 4) SHEET EP501
 A) INDICATE HOW THE CLUBHOUSE GROUNDING ELECTRODE
 SYSTEM TIES TO MDP BARN GROUNDING ELECTRODE SYSTEM.
 NOTE 3 THIS SHEET STATES TO BOND PANEL IT1 GROUND TO
 CLUBHOUSE GROUNDING ELECTRODE SYSTEM. THIS WOULD CREATE
 A DIFFERENCE OF POTENTIAL BETWEEN THE BARN AND
 CLUBHOUSE SYSTEMS.
 B) PROVIDE A NOTE AND ADD A SYMBOL TO THE SYMBOLS
 LEGEND FOR THE REMOTE SHUNT TRIP STATIONS TO ACTIVATE
 SHUNT TRIP MAIN BREAKERS SD 1 OF 4 AND SD 2 OF 4.
 C) INDICATE THE TYPE AND LOCATIONS FOR THE REMOTE SHUNT
 TRIP STATIONS NEXT TO THE EXISTING CHILLER PANEL SD 3
 OF 4 AND SD 4 OF 4.
 D) PROVIDE A NOTE ADDING A SIGN AT THE EXISTING CHILLER
 PANEL IDENTIFYING THE REMOTE SHUNT TRIP STATIONS AS
 TRIP UNITS FOR ADDITIONAL SERVICE ENTRANCE MAIN
 DISCONNECTS LOCATED IN ELECTRICAL ROOM 150 IN MDPA AND
 MDPB
 E) THE ATS AT THE NEW GENERATOR IS IDENTIFIED AS A
 4POLE ATS. I BELIEVE THIS IS MIS-LABELED AND THE INTENT
 IS FOR A STANDARD 3 POSITION ATS WITH A SOLID NEUTRAL
 FOR STANDARD OPTIONAL STANDBY SYSTEM AS ALSO NOTED THIS
 SHEET.
  
 5) SHEET ES101
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATOR, FIRE ALARM,
 SECURITY, CCTV, NETWORK, DATA/COM, AUDIO, VIDEO, AND
 SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-25 Cont ID  
Sent By dhayes Date 2014-07-25 Time 15:42 Rev Time 0.00
Received By dhayes Date 2014-07-23 Time 16:36 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2014-08-25 Cont ID  
Sent By Mgonzale Date 2014-08-25 Time   Rev Time 0.00
Received By   Date 2014-08-25 Time   Sent To Z
Notes
2014-08-25 09:55:02IMPROVEMENTS ARE PRIVATE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-07-08 Cont ID  
Sent By Mgonzale Date 2014-07-08 Time   Rev Time 1.00
Received By mgonzale Date 2014-07-08 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2014-09-24 Cont ID  
Sent By wjolin Date 2014-09-24 Time 09:11 Rev Time 0.00
Received By wjolin Date 2014-09-24 Time 07:41 Sent To  
Notes
2014-09-24 08:20:018100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 SHEET GI101: PROVIDE EXIT SIGNAGE ABOVE THE SECONDARY
 EXIT ACCESS DOOR IN CULTURE CLASS #125.
  
 SHEET GI101: PROVIDE ADDITIONAL EXIT SIGNAGE IN WOMENS'
 LOCKER ROOM/RESTROOM #106 CORRIDOR ROUTING OCCUPANTS TO
 THE SECONDARY EXIT LOCATED IN LOUNGE #110.
  
 SEVERAL ARCHITECTURAL AND MEPF DRAWINGS HAVE AN OLDER
 FLOOR PLAN (SHEET AE101, AE102, EL101 JUST TO NAME A
 FEW) THAT NEEDS TO BE UPDATED TO MATCH THE LIFE SAFETY
 FLOOR PLAN SHOWN ON SHEET GI101. ALSO ELECTRICAL EXIT
 SIGN LOCATIONS NEED TO BE UPDATED TO MATCH LIFE SAFETY
 EXIT STRATEGY SHOWN ON SHEET GI101.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-09-04 Cont ID  
Sent By wjolin Date 2014-09-04 Time 13:42 Rev Time 0.00
Received By wjolin Date 2014-09-02 Time 08:38 Sent To  
Notes
2014-09-03 16:05:408100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR THE ORIGINAL COMMENTS (X3) I OFFER THE FOLLOWING
 RESPONSE AND POSSIBLE SOLUTION:
 A MONUMENTAL STAIR/CONVENIENCE OPENING IS REQUIRED TO
 BE SEPARATED FROM CORRIDORS ON EITHER FLOOR LEVEL PER
 SECTION 8.6.8.2(3). THE OPENING IS NOT SEPARATED FROM
 THE CORRIDORS (GALLERY #224 & #252). ADDITIONALLY, EXIT
 SIGNAGE HAS BEEN ADDED IN ELEVATOR LOBBY #104 ROUTING
 OCCUPANTS THROUGH THE CONVENIENCE OPENING, PASSED THE
 OPEN STAIR, INTO A MERCANTILE OCCUPANCY (GOLF SHOP).
 PER SECTION 8.6.8.2(5), OPENINGS ARE NOT PERMITTED BE
 PART OF THE MEANS OF EGRESS (IN THIS CASE EXIT ACCESS).
 WHILE OCCUPANTS DO NOT NEED TO TRAVERSE THE OPEN STAIR
 FOR EGRESS PURPOSES, THEY WILL, ESPECIALLY WHEN FACED
 WITH A STRESSFUL SITUATION. SINCE THIS STAIR IS OPEN ON
 TOP AND ENCLOSED ON BOTTOM, A FIRE SITUATION COULD
 RESULT IN "COLD SMOKE" ACCUMULATION IN THIS STAIR...THE
 SAME STAIR OCCUPANTS ARE BEING DIRECTED TO FOR EXIT
 ACCESS. NO DOOR TAG PROVIDED FOR DOUBLE EXIT ACCESS
 DOORS LOCATED BETWEEN MONUMENTAL STAIR #111 AND GOLF
 SHOP. PROVIDING EXIT ACCESS THROUGH THESE DOORS WOULD
 APPEAR TO CAUSE A CONFLICT WITH TRYING TO SECURE/LOCK
 THESE DOORS FROM THE GOLF SHOP SIDE TO PREVENT THEFT.
  
 A POSSIBLE SOLUTION WOULD BE TO RELOCATE THE BOTTOM
 STAIR ENCLOSURE AND DOOR TO COLUMN INTERSECTION
 F/10-11. THIS WAY THE OPENING WOULD BE SEPARATED FROM
 THE CORRIDOR, AND OCCUPANTS WOULDN'T GET ENTICED INTO
 USING THE OPEN STAIR FOR EGRESS. THE ONLY ISSUE WOULD
 BE INSTALLING PASSAGE DOOR HARDWARE ON THE EXIT ACCESS
 DOORS LEADING THROUGH THE GOLF SHOP.
  
 ORIGINAL COMMENTS:
 SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE
 FUNCTIONING AS A "CONVENIENCE OPENING" PER NFPA 101
 SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT
 SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
  
 SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO
 EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION;
 HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY
 #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH
 DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL
 IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20
 FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS
 SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT
 LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION
 7.5.1.1.1.
  
 SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS
 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS
 AND 20 FEET FOR 51 OR MORE OCCUPANTS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-07-30 Cont ID  
Sent By wjolin Date 2014-07-30 Time 11:28 Rev Time 0.00
Received By wjolin Date 2014-07-30 Time 11:19 Sent To  
Notes
2014-07-30 11:28:238100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET GI101 & GI102 - LIFE SAFETY PLANS: INDICATE WHAT
 MEASURES WILL BE IN PLACE TO ENSURE THE ASSEMBLY AREAS
 WITHOUT SEATING (SUCH AS BAR TERRACE #214) ARE NOT
 OVERCROWDED (EXCEED 15 SQ.FT. OCCUPANT LOAD FACTOR).
  
 SHEET GI101: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2. ALSO KITCHEN #135 ONLY HAS EXIT SIGNAGE
 LEADING TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY
 MEANS OF EGRESS.
  
 SHEET GI101: FORMAL DINING #131 IS APPROXIMATELY 800
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 54 PERSONS. ONLY 1 MEANS OF EGRESS IS PROVIDED FOR
 THIS ROOM.
  
 SHEET GI101: FORMAL DINING #130 IS APPROXIMATELY 1600
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 107 PERSONS.
  
 SHEET GI101: CULTURAL CLASS #125 AND TRAINING #169
 APPEAR TO ACTUALLY BE ASSEMBLY USE (15 SQ.FT. OCCUPANT
 LOAD FACTOR) SPACES AND NOT EDUCATIONAL (20 SQ.FT.
 OCCUPANT LOAD FACTOR) USE. EDUCATIONAL USE IS DEFINED
 AS AN OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH
 THE 12TH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE
 HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK.
  
 SHEET GI102: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2.
  
 SHEET GI102: KITCHEN #245 ONLY HAS EXIT SIGNAGE LEADING
 TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY MEANS OF
 EGRESS.
  
 SHEET GI102: GRILL DINING AREA 264A/B IS APPROXIMATELY
 3,000 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE
 CLOSER TO 200 PERSONS.
  
 SHEET GI102: PROVIDE EXIT SIGNAGE LEADING TO SECONDARY
 MEANS OF EGRESS FROM LOUNGE #258 AREA.
  
 SHEET GI102: PROVIDE A SECONDARY MEANS OF EGRESS AND
 SIGNAGE FOR BAR TERRACE #214.
  
 SHEET AE101: CARD ROOM #185 (71 PERSONS) HAS TWO EXIT
 ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; HOWEVER,
 BOTH DOORS LEAD TO THE SAME CORRIDOR #186 WHEREBY ONE
 FIRE EVENT COULD COMPROMISE BOTH DOORS. PER SECTION
 12.2.5.1.2 THE COMMON PATH OF TRAVEL IS LIMITED TO 75
 FEET FOR 50 OR LESS OCCUPANTS AND 20 FEET FOR 51 OR
 MORE OCCUPANTS. THE EXIT ACCESS DOORS SHALL BE ARRANGED
 FOR OCCUPANTS TO HAVE ACCESS TO AT LEAST TWO EXITS BY
 SEPARATE WAYS OF TRAVEL PER SECTION 7.5.1.1.1.
  
 SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO
 EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION;
 HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY
 #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH
 DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL
 IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20
 FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS
 SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT
 LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION
 7.5.1.1.1.
  
 SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS
 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS
 AND 20 FEET FOR 51 OR MORE OCCUPANTS.
  
 SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE
 FUNCTIONING AS A "COMMUNICATING SPACE" PER NFPA 101
 SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT
 SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
  
 SHEET AE105: PROVIDE PANIC HARDWARE FOR UNMARKED
 SECONDARY EXIT ACCESS DOOR IN BALLROOM #248A.
  
 SHEET AE106: BAR TERRACE #214 FEATURES A FIRE PIT.
 INDICATE IF THE FIRE PIT FLAME WILL BE OPEN OR SCREENED
 FROM OCCUPANTS.
  
 SHEET FP101: RECEIVING #142, MECHANICAL #103 AND
 STORAGE #126 NOT INDICATED AS ORDINARY HAZARD GROUP 1
 PROTECTION.
  
 SHEET FP101: WILL THE "COVERED TERRACE" CEILING
 ADJACENT TO STAIR #4 BE PROTECTED WITH SPRINKLERS? WHAT
 ABOUT THE OTHER EXTERIOR OVERHAND CEILINGS, SUCH AS BAR
 TERRACE #214, WILL THEY BE PROTECTED?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-20 Cont ID  
Sent By wjolin Date 2014-06-20 Time 16:17 Rev Time 0.00
Received By wjolin Date 2014-06-12 Time 13:51 Sent To  
Notes
2014-06-12 16:23:148100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: SEVERAL SHEETS COULD NOT BE OPENED/REVIEWED AS
 THEY RESULTED IN A COMPUTER CRASH.
  
 SHEET GI101 & GI102 - LIFE SAFETY PLANS: INDICATE WHAT
 MEASURES WILL BE IN PLACE TO ENSURE THE ASSEMBLY AREAS
 WITHOUT SEATING (SUCH AS BAR TERRACE #214) ARE NOT
 OVERCROWDED (EXCEED 15 SQ.FT. OCCUPANT LOAD FACTOR).
  
 SHEET GI101: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2. ALSO KITCHEN #135 ONLY HAS EXIT SIGNAGE
 LEADING TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY
 MEANS OF EGRESS.
  
 SHEET GI101: FORMAL DINING #131 IS APPROXIMATELY 800
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 54 PERSONS. ONLY 1 MEANS OF EGRESS IS PROVIDED FOR
 THIS ROOM.
  
 SHEET GI101: FORMAL DINING #130 IS APPROXIMATELY 1600
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 107 PERSONS.
  
 SHEET GI101: CULTURAL CLASS #125 AND TRAINING #169
 APPEAR TO ACTUALLY BE ASSEMBLY USE (15 SQ.FT. OCCUPANT
 LOAD FACTOR) SPACES AND NOT EDUCATIONAL (20 SQ.FT.
 OCCUPANT LOAD FACTOR) USE. EDUCATIONAL USE IS DEFINED
 AS AN OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH
 THE 12TH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE
 HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK.
  
 SHEET GI102: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2.
  
 SHEET GI102: KITCHEN #245 ONLY HAS EXIT SIGNAGE LEADING
 TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY MEANS OF
 EGRESS.
  
 SHEET GI102: GRILL DINING AREA 264A/B IS APPROXIMATELY
 3,000 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE
 CLOSER TO 200 PERSONS.
  
 SHEET GI102: PROVIDE EXIT SIGNAGE LEADING TO SECONDARY
 MEANS OF EGRESS FROM LOUNGE #258 AREA.
  
 SHEET GI102: PROVIDE A SECONDARY MEANS OF EGRESS AND
 SIGNAGE FOR BAR TERRACE #214.
  
 SHEET AE101: CARD ROOM #185 (71 PERSONS) HAS TWO EXIT
 ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; HOWEVER,
 BOTH DOORS LEAD TO THE SAME CORRIDOR #186 WHEREBY ONE
 FIRE EVENT COULD COMPROMISE BOTH DOORS. PER SECTION
 12.2.5.1.2 THE COMMON PATH OF TRAVEL IS LIMITED TO 75
 FEET FOR 50 OR LESS OCCUPANTS AND 20 FEET FOR 51 OR
 MORE OCCUPANTS. THE EXIT ACCESS DOORS SHALL BE ARRANGED
 FOR OCCUPANTS TO HAVE ACCESS TO AT LEAST TWO EXITS BY
 SEPARATE WAYS OF TRAVEL PER SECTION 7.5.1.1.1.
  
 SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO
 EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION;
 HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY
 #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH
 DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL
 IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20
 FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS
 SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT
 LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION
 7.5.1.1.1.
  
 SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS
 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS
 AND 20 FEET FOR 51 OR MORE OCCUPANTS.
  
 SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE
 FUNCTIONING AS A "COMMUNICATING SPACE" PER NFPA 101
 SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT
 SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
  
 SHEET AE105: PROVIDE PANIC HARDWARE FOR UNMARKED
 SECONDARY EXIT ACCESS DOOR IN BALLROOM #248A.
  
 SHEET AE106: BAR TERRACE #214 FEATURES A FIRE PIT.
 INDICATE IF THE FIRE PIT FLAME WILL BE OPEN OR SCREENED
 FROM OCCUPANTS.
  
 SHEET FP101: RECEIVING #142, MECHANICAL #103 AND
 STORAGE #126 NOT INDICATED AS ORDINARY HAZARD GROUP 1
 PROTECTION.
  
 SHEET FP101: WILL THE "COVERED TERRACE" CEILING
 ADJACENT TO STAIR #4 BE PROTECTED WITH SPRINKLERS? WHAT
 ABOUT THE OTHER EXTERIOR OVERHAND CEILINGS, SUCH AS BAR
 TERRACE #214, WILL THEY BE PROTECTED?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2014-09-22 Cont ID  
Sent By jwitmer Date 2014-09-22 Time 11:25 Rev Time 0.00
Received By jwitmer Date 2014-09-22 Time 10:33 Sent To  
Notes
2014-09-22 11:24:05FUEL GAS PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 4TH REVIEW
 DATE: MON. SEPT.22/ 2014
  
 ACTION: PROVISO
 FUEL GAS APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE MANUFACTURERS SPEC SHEETS FOR THE CONSUMPTION OF
 FUEL WILL NEED TO BE SUBMITTED BEFORE THE GAS ROUGH
 INSPECTION FOR VARIFICATION OF GAS COMSUMPTION. SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 15:11 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 10:46 Sent To  
Notes
2014-08-25 15:11:21FUEL GAS PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 3D REVIEW
 DATE: MON. AUG. 25/ 2014
 ACTION: DENIED
  
 SHEET P306 GAS PIPING ISOMETRIC.
  
 GAS PERMIT APPLICATION REQUIREMENTS, MISSING
 INFORMATION:
  
  
 1. COMPLIED.
  
 2. COMPLIED.
  
 3.. COMPLIED.
  
 4. 3RD REQUEST. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE FBC-2010 FUEL GAS
 APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4)
  
 2010 FBC- FUEL GAS
 A.3.1 LONGEST LENGTH METHOD.
 THIS SIZING METHOD IS CONSERVATIVE IN ITS APPROACH BY
 APPLYING THE MAXIMUM OPERATING CONDITIONS IN THE SYSTEM
 AS THE NORM FOR THE SYSTEM AND BY SETTING THE LENGTH OF
 PIPE USED TO SIZE ANY GIVEN PART OF THE PIPING SYSTEM
 TO THE MAXIMUM VALUE.
  
 TO DETERMINE THE SIZE OF EACH SECTION OF GAS PIPING IN
 A SYSTEM WITHIN THE RANGE OF THE CAPACITY TABLES,
 PROCEED AS FOLLOWS (ALSO SEE SAMPLE CALCULATIONS
 INCLUDED IN THIS APPENDIX):
  
 (1) DIVIDE THE PIPING SYSTEM INTO APPROPRIATE SEGMENTS
 CONSISTENT WITH THE PRESENCE OF TEES, BRANCH LINES AND
 MAIN RUNS. FOR EACH SEGMENT, DETERMINE THE GAS LOAD
 (ASSUMING ALL APPLIANCES OPERATE SIMULTANEOUSLY) AND
 ITS OVERALL LENGTH. AN ALLOWANCE (IN EQUIVALENT LENGTH
 OF PIPE) AS DETERMINED FROM TABLE A.2.2 SHALL BE
 CONSIDERED FOR PIPING SEGMENTS THAT INCLUDE FOUR OR
 MORE FITTINGS.
  
 (2) DETERMINE THE GAS DEMAND OF EACH APPLIANCE TO BE
 ATTACHED TO THE PIPING SYSTEM. WHERE TABLES 402.4(1)
 THROUGH 402.4(22) ARE TO BE USED TO SELECT THE PIPING
 SIZE, CALCULATE THE GAS DEMAND IN TERMS OF CUBIC FEET
 PER HOUR FOR EACH PIPING SYSTEM OUTLET . WHERE TABLES
 402.4(23) THROUGH 402.4(35) ARE TO BE USED TO SELECT
 THE PIPING SIZE, CALCULATE THE GAS DEMAND IN TERMS OF
 THOUSANDS OF BTU PER HOUR FOR EACH PIPING SYSTEM OUTLET
 .
  
 (3) WHERE THE PIPING SYSTEM IS FOR USE WITH OTHER THAN
 UNDILUTED LIQUEFIED PETROLEUM GASES, DETERMINE THE
 DESIGN SYSTEM PRESSURE, THE ALLOWABLE LOSS IN PRESSURE
 (PRESSURE DROP), AND SPECIFIC GRAVITY OF THE GAS TO BE
 USED IN THE PIPING SYSTEM.
  
 (4) DETERMINE THE LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET IN THE
 BUILDING/PIPING SYSTEM.
  
  
  
 5. COMPLIED.
 6. COMPLIED.
  
 7. COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-08-01 Cont ID  
Sent By jwitmer Date 2014-08-01 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2014-08-01 Time 06:45 Sent To  
Notes
2014-08-01 07:01:41FUEL GAS PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 3D REVIEW
 DATE: MON. AUG. 25/ 2014
 ACTION: DENIED
  
 SHEET P306 GAS PIPING ISOMETRIC.
  
 GAS PERMIT APPLICATION REQUIREMENTS, MISSING
 INFORMATION:
  
  
 1. COMPLIED.
  
 2. COMPLIED.
  
 3.. COMPLIED.
  
 4. 3RD REQUEST. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE FBC-2010 FUEL GAS
 APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4)
  
 2010 FBC- FUEL GAS
 A.3.1 LONGEST LENGTH METHOD.
 THIS SIZING METHOD IS CONSERVATIVE IN ITS APPROACH BY
 APPLYING THE MAXIMUM OPERATING CONDITIONS IN THE SYSTEM
 AS THE NORM FOR THE SYSTEM AND BY SETTING THE LENGTH OF
 PIPE USED TO SIZE ANY GIVEN PART OF THE PIPING SYSTEM
 TO THE MAXIMUM VALUE.
  
 TO DETERMINE THE SIZE OF EACH SECTION OF GAS PIPING IN
 A SYSTEM WITHIN THE RANGE OF THE CAPACITY TABLES,
 PROCEED AS FOLLOWS (ALSO SEE SAMPLE CALCULATIONS
 INCLUDED IN THIS APPENDIX):
  
 (1) DIVIDE THE PIPING SYSTEM INTO APPROPRIATE SEGMENTS
 CONSISTENT WITH THE PRESENCE OF TEES, BRANCH LINES AND
 MAIN RUNS. FOR EACH SEGMENT, DETERMINE THE GAS LOAD
 (ASSUMING ALL APPLIANCES OPERATE SIMULTANEOUSLY) AND
 ITS OVERALL LENGTH. AN ALLOWANCE (IN EQUIVALENT LENGTH
 OF PIPE) AS DETERMINED FROM TABLE A.2.2 SHALL BE
 CONSIDERED FOR PIPING SEGMENTS THAT INCLUDE FOUR OR
 MORE FITTINGS.
  
 (2) DETERMINE THE GAS DEMAND OF EACH APPLIANCE TO BE
 ATTACHED TO THE PIPING SYSTEM. WHERE TABLES 402.4(1)
 THROUGH 402.4(22) ARE TO BE USED TO SELECT THE PIPING
 SIZE, CALCULATE THE GAS DEMAND IN TERMS OF CUBIC FEET
 PER HOUR FOR EACH PIPING SYSTEM OUTLET . WHERE TABLES
 402.4(23) THROUGH 402.4(35) ARE TO BE USED TO SELECT
 THE PIPING SIZE, CALCULATE THE GAS DEMAND IN TERMS OF
 THOUSANDS OF BTU PER HOUR FOR EACH PIPING SYSTEM OUTLET
 .
  
 (3) WHERE THE PIPING SYSTEM IS FOR USE WITH OTHER THAN
 UNDILUTED LIQUEFIED PETROLEUM GASES, DETERMINE THE
 DESIGN SYSTEM PRESSURE, THE ALLOWABLE LOSS IN PRESSURE
 (PRESSURE DROP), AND SPECIFIC GRAVITY OF THE GAS TO BE
 USED IN THE PIPING SYSTEM.
  
 (4) DETERMINE THE LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET IN THE
 BUILDING/PIPING SYSTEM.
  
  
  
 5. COMPLIED.
 6. COMPLIED.
  
 7. COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-07-12 Cont ID  
Sent By jwitmer Date 2014-07-12 Time 15:37 Rev Time 0.00
Received By jwitmer Date 2014-07-12 Time 14:57 Sent To  
Notes
2014-07-12 15:37:13FUEL GAS PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 12/ 2014
 ACTION: DENIED
  
 SHEET P306 GAS PIPING ISOMETRIC.
  
 GAS PERMIT APPLICATION REQUIREMENTS, MISSING
 INFORMATION:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3.. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 3A) MISSING CFH ON PK 98, PK95, PK94, PLK53 & 2 GWH (2
 GAS HEATERS).
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI. PLANS INDICATE 10-14 IN W. C. OR 1/2 LB SYSTEM.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-24 Cont ID  
Sent By cpuell Date 2014-09-24 Time 09:59 Rev Time 0.00
Received By cpuell Date 2014-09-16 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-12 Cont ID  
Sent By cpuell Date 2014-09-12 Time 16:52 Rev Time 0.00
Received By cpuell Date 2014-08-07 Time 15:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-05 Cont ID  
Sent By skennedy Date 2014-08-05 Time 11:22 Rev Time 0.00
Received By skennedy Date 2014-07-14 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-08 Cont ID  
Sent By skennedy Date 2014-07-08 Time 12:41 Rev Time 0.00
Received By skennedy Date 2014-05-09 Time 14:27 Sent To  
Notes
2014-07-08 12:44:28DELETED DRAWING FILES AND REQUESTED APPLICANT UPLOAD
 PDF VERSIONS OF FILES AS THE ORIGINAL FILES COULD NOT
 BE VIEWED EFFICIENTLY.
  
 STEVEN KENNEDY
 CHIEF PLANS EXAMINER
 561 805 6710

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-09-29 Cont ID  
Sent By jwitmer Date 2014-09-29 Time 08:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2014-09-29 08:26:41P. B. C. IMPACT FEE RECEIPT:
 TRACKING # MU-2014-014801-0000
 REC # 2014-0707-304
 FEES PAID: $8265.69

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-09-29 Cont ID  
Sent By jwitmer Date 2014-09-29 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2014-09-29 Time 08:25 Sent To  
Notes
2014-09-29 08:26:13PAID UNDER FOUNDATION PERMIT
 P. B. C. IMPACT FEE RECEIPT:
 TRACKING # MU-2014-014801-0000
 REC # 2014-0707-304
 FEES PAID: $8265.69

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-20 Cont ID  
Sent By jwitmer Date 2014-09-20 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2014-09-20 Time 11:56 Sent To  
Notes
2014-09-20 11:56:41BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-18 Cont ID  
Sent By hmoser Date 2014-08-18 Time 14:53 Rev Time 0.00
Received By hmoser Date 2014-08-18 Time 12:29 Sent To  
Notes
2014-08-18 14:53:16KITCHEN HOOD AND GREASE DUCT WAS NOT REVIEWED .
 KITCHEN HOOD AND GREASE DUCT AN COOLERS REQUIRE
 SEPARATE
 APPLICATION PLAN AND PERMIT.
 AIR CONDITIONING PLAN ONLY OK.
 REFER TO SECTION 301.12 WIND RESISTANCE
 FBC (M) 2010 FOR ROOF TOP EQUIPMENT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By hmoser Date 2014-07-17 Time 10:04 Rev Time 0.00
Received By hmoser Date 2014-07-02 Time 15:20 Sent To  
Notes
2014-07-17 10:03:51PASS PROVISO
 1) PROVIDE A DETAIL FROM THE ENGINEER FOR THE
 EXHAUST FANS AND SUPPLY FANS CURBS TIE DOWN TO ROOF
 AND FANS TIE DOWN TO CURB . PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 2) INSPECTOR WILL CHECK THE 16GA X 2IN G-90 GALV.
 STEEL EXTERIOR STRAP WHEN INSPECTING CURB TIE DOWN TO
 ROOF
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2014-09-20 Cont ID  
Sent By jwitmer Date 2014-09-20 Time 12:23 Rev Time 0.00
Received By jwitmer Date 2014-09-20 Time 11:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 10:46 Sent To  
Notes
2014-08-25 15:53:04BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:FRI. AUG. 25/ 2014
 ACTION: DENIED
  
 1) COMPLIED.
 2) COMPLIED.
  
 3) COMPLIED.
  
 4A) 3RD REQUEST. 0173-P304 RISER E GREASE WASTE, THE
 PLANS INDICATE THE GREASE WASTE FROM KITCHENS # 135 &
 #245, THE PLANS INDICATE A 4 " GREASE WASTE WITH A 184
 DFU'S TABLE 710.1.1 FOR A 4" BUILDING DRAIN AT A 1/8
 INCH SLOPE WILL HANDLE 180 DFU'S WHERE AS AT A 1/4
 SLOPE THEY DRAIN WILL HANDLE 216 DFU'S. THE NEW
 REVISION DOES STATE THE INSTALLATION OF (3) 1600 GALLON
 GREASE INTERCEPTORS. FOR A CONCRETE VAULT TYPE
 INTERCEPTOR THE FBC-P TABLE 1003.5.1 IS THE SIZING
 TABLE TO BE USED FOR THIS TYPE OF APPLICATION.
 (S) ? (GS) ? (HR/12) ? (LF) = EFFECTIVE CAPACITY OF
 GREASE INTERCEPTOR IN GALLONS.
  
 PLEASE NOTE THE GREASE INTERCEPTOR DOES REQUIRE A
 SEPARATE PERMIT , IF THE SLOPE ISSUE IS RESOLVED WE
 WILL BW ABLE TO PASS THE PLUMBING PERMIT WITH A PROVISO
 THAT THE GREASE INTERCEPTOR SIZING ISSUE TO BE REVIEWED
 UNDER THE SEPARATE INTERCEPTOR PERMIT.
  
 4B)COMPLIED.
  
 4C) COMPLIED.
  
 5) COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-08-01 Cont ID  
Sent By jwitmer Date 2014-08-01 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2014-08-01 Time 05:51 Sent To  
Notes
2014-08-01 06:49:02BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! . A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
  
 2ND REVIEW
 DATE:FRI. AUG. 01/ 2014
 ACTION: DENIED
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 1) 2ND REQUEST. SHEET P105 NOR 305 DOES NOT INDICATE
 THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS,
 BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY
 HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE
 BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN
 FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED
 FROM APPROVED LOCAL WEATHER DATA. 2010 FBC-P 1106.1.
  
 2) 2ND REQUEST. P105 DOES NOT PROVIDE WHAT AREA THE
 ROOF DRAINS ARE RECEIVING, IF THIS IS JUST THE FLAT
 AREA OR IF THIS AREA IS ALSO THE CONTRIBUTING SLOPED
 ARAES, PLEASE PROVIDE A BREAK OUT FOR EACH ROOF DRAIN
 SERVED OF FLAT AND ADJOINING SLOPED ROOFS THAT
 CONTRIBUTE TO THE ROOF DRAIN LOAD.
 2010 1106.4.
  
 3) 2ND REQUEST. SHEET P201 VERSES P301
 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A
 ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT
 SEE SECTION 2010 FBC-P 911.2.
  
 3B) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN
 THE MENS RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF
 THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 3C) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN
 THE MENS RESTROOM IS NOT VENTED AS A INDIVDUAL VENT OF
 THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 4A) 2ND REQUEST. 0173-P304 RISER E GREASE WASTE, THE
 PLANS INDICATE THE GREASE WASTE FROM KITCHENS # 135 &
 #245, THE PLANS DO NOT COMMENT ON THE DRAINAGE FIXTURE
 UNITS FOR THE GREASE WASTE NOR MENTION SIZING NOR THE
 LOCATION OF THE GREASE INTERCEPTOR. 2010 FBC-PLUMBING
 1003.2. APPROVAL. 1003.3.3 SIZED. NOTE IF A CONCRETE
 VAULT TYPE OF INTERCEPTOR IS TO BE INSTALLED PLEASE
 NOTE THAT FBC-P TABLE 1003.5.1 IS THE SIZING TABLE TO
 BE USED FOR THIS TYPE OF APPLICATION.
  
 4B) 2ND REQUEST. THE PLANS DO NOT INDICATE IF ANY FOOD
 WASTE GRINDERS ARE GOING TO BE INSTALLED. 2010
 FBC-PLUMBING 1003.3.2.
  
 4C) 2ND REQUEST. THE ARCHITECTURAL SHEETS & STRURTURAL
 SHEETS BOTH INDICATE THE ELEVATOR PIT TO HAVE A SUMP
 PIT. PLANS ARE NOT CLEAR IF THIS IS TO BE A HYDROLIC
 ELEVATOR, IF SO PLEASE INDICATE HOW COMPLIANCE WITH
 2010 FBC-PLUMBING 1003.4 OIL SPEARATOR REQUIRED WILL BE
 ACHIEVED. I DID NOT SEE A DETAIL FOR A SUMP IN THE
 ELEVATOR PIT AND WASTE CONNECTIONS.SHEET P401 DOES
 INDICATE THE USE OF ZOELLER SUBMERSIBLE SUMP PUMP
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
  
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 5) 2ND REQUEST. SHEET 0176- P401 PLUMBING SCHEDULE.
 TTRAP PRIMERS INDICATE PRECISION PLUMBING PRODUCTS BUT
 THE ACTUAL TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS
 THE CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY
 WITH ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-15 Cont ID  
Sent By jwitmer Date 2014-07-15 Time 08:18 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 12:43 Sent To  
Notes
2014-07-05 12:43:58BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 12/ 2014
 ACTION: DENIED
  
 1) SHEET P105 NOR 305 DOES NOT INDICATE THE SIZE OF THE
 VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM DRAINS,
 BUILDING STORM SEWERS, AND ANY HORIZONTAL BRANCHES OF
 SUCH DRAINS OR SEWERS SHALL BE BASED ON THE 100-YEAR
 HOURLY RAINFALL RATE INDICATED IN FIGURE 1106.1 OR ON
 OTHER RAINFALL RATES DETERMINED FROM APPROVED LOCAL
 WEATHER DATA. 2010 FBC-P 1106.1.
  
 2) P105 DOES NOT PROVIDE WHAT AREA THE ROOF DRAINS ARE
 RECEIVING, IF THIS IS JUST THE FLAT AREA OR IF THIS
 AREA IS ALSO THE CONTRIBUTING SLOPED ARAES, PLEASE
 PROVIDE A BREAK OUT FOR EACH ROOF DRAIN SERVED OF FLAT
 AND ADJOINING SLOPED ROOFS THAT CONTRIBUTE TO THE ROOF
 DRAIN LOAD.
 2010 1106.4.
  
 3) SHEET P201 VERSES P301
 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A
 ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT
 SEE SECTION 2010 FBC-P 911.2.
  
 3B) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS
 RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE
 BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 3C) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS
 RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE
 BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 4A) 0173-P304 RISER E GREASE WASTE, THE PLANS INDICATE
 THE GREASE WASTE FROM KITCHENS # 135 & #245, THE PLANS
 DO NOT COMMENT ON THE DRAINAGE FIXTURE UNITS FOR THE
 GREASE WASTE NOR MENTION SIZING NOR THE LOCATION OF THE
 GREASE INTERCEPTOR. 2010 FBC-PLUMBING 1003.2. APPROVAL.
 1003.3.3 SIZED. NOTE IF A CONCRETE VAULT TYPE OF
 INTERCEPTOR IS TO BE INSTALLED PLEASE NOTE THAT FBC-P
 TABLE 1003.5.1 IS THE SIZING TABLE TO BE USED FOR THIS
 TYPE OF APPLICATION.
  
 4B) THE PLANS DO NOT INDICATE IF ANY FOOD WASSTE
 GRINDERS ARE GOING TO BE INSTALLED. 2010 FBC-PLUMBING
 1003.3.2.
  
 4C) THE ARCHITECTURAL SHEETS & STRURTURAL SHEETS BOTH
 INDICATE THE ELEVATOR PIT TO HAVE A SUMP PIT. PLANS ARE
 NOT CLEAR IF THIS IS TO BE A HYDROLIC ELEVATOR, IF SO
 PLEASE INDICATE HOW COMPLIANCE WITH 2010 FBC-PLUMBING
 1003.4 OIL SPEARATOR REQUIRED WILL BE ACHIEVED. I DID
 NOT SEE A DETAIL FOR A SUMP IN THE ELEVATOR PIT AND
 WASTE CONNECTIONS.SHEET P401 DOES INDICATE THE USE OF
 ZOELLER SUBMERSIBLE SUMP PUMP EXCEPTION: AN OIL
 SEPARATOR IS NOT REQUIRED IN HYDRAULIC ELEVATOR PITS
 WHERE AN APPROVED ALARM SYSTEM IS INSTALLED.
  
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
  
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 5) SHEET 0176- P401 PLUMBING SCHEDULE. TTRAP PRIMERS
 INDICATE PRECISION PLUMBING PRODUCTS BUT THE ACTUAL
 TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS THE
 CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY WITH
 ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By skennedy Date 2014-09-26 Time 15:55 Rev Time 0.00
Received By skennedy Date 2014-09-25 Time 15:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-25 Cont ID  
Sent By ajones Date 2014-08-25 Time 11:03 Rev Time 0.00
Received By ajones Date 2014-08-25 Time 11:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By avann Date 2014-07-30 Time 09:37 Rev Time 0.00
Received By ajones Date 2014-07-30 Time 09:37 Sent To  
Notes
2014-07-30 09:39:267/30/14- FAILED- THE SITE PLAN SHOWN IS NOT THE CURRENT
 APPROVED SITE PLAN. PROVIDE THE CORRECT SITE PLAN.
  
 ANGELLA VANN
 561-822-1441