Plan Review Details - Permit 14050052
Plan Review Stops For Permit 14050052
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 13:14 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 13:07 Sent To NFIP
Notes
2014-05-28 13:14:55TO SH FOR FLOOD REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By skennedy Date 2014-05-27 Time 13:41 Rev Time 0.00
Received By skennedy Date 2014-05-27 Time 13:42 Sent To  
Notes
2014-05-27 13:52:591ST REVIEW:
  
 1) SURVEY PROVIDED INDICATES FLOOD ZONE IS AN A-6; FIRM
 MAP 120229 001 B INDICATES A5, AND DOES NOT ESTABLISH
 THE PROPOSED FINISH FLOOR ELEVATION.
 SEE 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE DESIGN
 FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY
 SHALL BE ESTABLISHED IN ACCORDANCE WITH SECTION
 1612.3.1.
 2) PROVIDE DETAILS FOR FLOOD RESISTANCE CONSTRUCTION
 TECHNIQUES TO BE INCORPORATED IN THE STEM WALL AT THE
 CRAWL SPACE AREA.
 SEE 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL:
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS NOT SUBJECT
 TO HIGH-VELOCITY WAVE ACTION:
 1.1 THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1, ASCE 24, CONSTRUCTION
 DOCUMENTS SHALL INCLUDE A STATEMENT THAT THE DESIGN
 WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD
 FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE 24.
 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-19 Cont ID  
Sent By albarran Date 2014-05-19 Time 19:33 Rev Time 0.00
Received By albarran Date 2014-05-19 Time 18:35 Sent To  
Notes
2014-05-19 20:09:07ELECTRICAL PROVIO FOR PERMIT 14050052
 THOUGH NOT REFLECTED ON THE SUBMITTED/APPROVED
 DRAWINGS, COMPLIANCE WITH THE OUTLET & LUMINAIRE
 REQUIREMENTS OF THE 2008 NEC SHALL BE REQUIRED.
 ARC-FAULT AS PER NEC 210.12 & TAMPER-RESISTANT
 RECEPTACLE AS PER NEC 406.11 SHALL BE REQUIRED.
 SMOKE DETECTORS COMPLIANCE AS PER FBC-R 314/315
 REQUIRED.
 AS PER NEC 300.5. THE INTERIOR OF A RACEWAY
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 13:36 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 13:36 Sent To  
Notes
2014-05-28 13:39:59A REVISED RISER FOR THE TANKLESS HEATER, WITH LOCATION
 AND SPEC SHEET IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-29 Cont ID  
Sent By shill Date 2014-05-29 Time 15:40 Rev Time 0.00
Received By shill Date 2014-05-28 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-27 Cont ID  
Sent By skennedy Date 2014-05-27 Time 13:41 Rev Time 0.00
Received By skennedy Date 2014-05-02 Time 09:56 Sent To  
Notes
2014-05-02 09:57:26****EXPEDITED****
  
 R14
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 13:07 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 13:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By skennedy Date 2014-05-27 Time 13:41 Rev Time 0.00
Received By skennedy Date 2014-05-27 Time 13:41 Sent To  
Notes
2014-05-27 13:42:15 
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 AFTER APPROVAL, A SET OF THE PLANS ARE TO BE CHECKED
 OUT AND TAKEN TO THE PBC IMPACT FEE OFFICE, STAMPED BY
 THAT OFFICE, AND RETURNED WITH A RECEIPT PROVIDED.
 CONTACT 561 233 5100.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-27 Cont ID  
Sent By skennedy Date 2014-05-27 Time 13:41 Rev Time 0.00
Received By skennedy Date 2014-05-27 Time 13:41 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-05-29 Cont ID  
Sent By shill Date 2014-05-29 Time 15:35 Rev Time 0.00
Received By shill Date 2014-05-29 Time 15:35 Sent To  
Notes
2014-05-29 15:40:27CUMULATIVE LIFETIME IMPROVEMENTS (INCLUDING PROPOSED
 ADDITION UNDER THIS PERMIT) = $146,162
 ADDITION IS 294 SF ($272/SF)
 PAPA IMPROVEMENT VALUE IS $302,177 (WHICH IS LIKELY
 VERY LOW FOR THIS 5400 SF HOME PURCHASED FOR
 $2,800,000.
  
 CUMULATIVE LIFETIME IMPROVEMENTS IS AT 48%; THEREFORE,
 THIS IS NOT A SUBSTANTIAL IMPROVEMENT.
  
 THE ELEVATION CERTIFICATE PROVIDED FOR THE EXISTING
 STRUCTURE SHOWS TOP OF BOTTOM FLOOR AT 9.2' (BFE IS
 7'). ADDITION WILL MATCH THE FFE OF THE EXISTING HOUSE.
  
 WORKSHEET HAS BEEN ADDED TO PERMIT FILE.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-27 Cont ID  
Sent By skennedy Date 2014-05-27 Time 13:41 Rev Time 0.00
Received By skennedy Date 2014-05-27 Time 13:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 13:15 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 13:15 Sent To  
Notes
2014-05-28 13:15:31ROOFING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By dkittred Date 2014-05-06 Time 16:20 Rev Time 0.00
Received By dkittred Date 2014-05-06 Time 15:35 Sent To  
Notes
2014-05-06 16:20:06PLANNING AND ZONING COMMENTS:
  
 5/6/2014
  
 1. TREE ALTERATION PERMIT IS REQUIRED THROUGH THE
 PLANNING DIVISION IF ANY TREES WILL NEED TO BE REMOVED
 OR RELOCATED FOR THE NEW CONSTRUCTION.
  
 2. SEPARATE PERMIT IS REQUIRED FOR THE PROPOSED POOL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-05-06 14:44:335/6/14