Plan Review Details - Permit 14041064
Plan Review Stops For Permit 14041064 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-05-29 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-29 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-05-29 |
Time |
11:13 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-05-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-01 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-04-30 |
Time |
16:54 |
Sent To |
FIRE |
|
Notes |
2014-04-30 17:11:55 | PLEASE PROVIDE HP RATINGS OF ALL MOTORS. NEW AND OR | | EXISTING. | | PLEASE SHOW COMPLIANCE WITH THE NEC 430.32. MOTOR | | OVERLOAD DEVICE TO BE PROVIDED FOR MOTORS OVER ONE HP. | | A SEPARATE FIRE ALARM PERMIT IS REQUIRED. | | THE PLANS INDICATE NEW FIRE ALARM DEVICES. PLEASE | | PROVIDE COMPLETE F/A DRAWINGS TO INCLUDE A LOCATION OF | | THE FACP, BATTERY CALCULATIONS. AND SUBMITTALS ON | | EQUIPMENT. | | THE PLANS INDICATE A EXISTING STANDBY GENERATOR. PLEASE | | PROVIDE ADDITIONAL DETAIL ON THE GENERATOR SPECIFICALLY | | HOW IT TIES INTO THE FACILITY'S ELECTRICAL SYSTEM. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-05-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-05-30 |
Time |
10:25 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-05-05 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-05-05 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-05-05 |
Time |
16:35 |
Sent To |
PC |
|
Notes |
2014-05-05 16:49:42 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | WITH THE FOLLOWING COMMENTS. | | | | ALL FIRE ALARM SHALL BE DONE BY A CERIFIED FIRE ALARM | | CONTRACTOR UNDER SEPARATE SHOP DRAWINGS. | | | | INDICATE THE PREVIOUS COMMENT UNDER THE FIRE LARM | | SYSTEM GENERAL NOTES ON SHEET E-0. | | | | PLEASE NOTE ADDITIONAL LIFE SAFETY COMMENTS UNDER THE | | BUILDING DEPARTMENT COMMENTS. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-05-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-05-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-05-27 |
Time |
08:05 |
Sent To |
PC |
|
Notes |
2014-05-28 08:05:35 | SENT TO D HAYES |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-05-05 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-05-05 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-04-30 |
Time |
11:17 |
Sent To |
PC |
|
Notes |
2014-04-30 11:17:34 | ROUTED TO DAVID HAYES |
|
|
|