Plan Review Details - Permit 14041064
Plan Review Stops For Permit 14041064
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-29 Cont ID  
Sent By dhayes Date 2014-05-29 Time 11:13 Rev Time 0.00
Received By dhayes Date 2014-05-29 Time 11:13 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By dhayes Date 2014-05-01 Time 13:20 Rev Time 0.00
Received By dhayes Date 2014-04-30 Time 16:54 Sent To FIRE
Notes
2014-04-30 17:11:55PLEASE PROVIDE HP RATINGS OF ALL MOTORS. NEW AND OR
 EXISTING.
 PLEASE SHOW COMPLIANCE WITH THE NEC 430.32. MOTOR
 OVERLOAD DEVICE TO BE PROVIDED FOR MOTORS OVER ONE HP.
 A SEPARATE FIRE ALARM PERMIT IS REQUIRED.
 THE PLANS INDICATE NEW FIRE ALARM DEVICES. PLEASE
 PROVIDE COMPLETE F/A DRAWINGS TO INCLUDE A LOCATION OF
 THE FACP, BATTERY CALCULATIONS. AND SUBMITTALS ON
 EQUIPMENT.
 THE PLANS INDICATE A EXISTING STANDBY GENERATOR. PLEASE
 PROVIDE ADDITIONAL DETAIL ON THE GENERATOR SPECIFICALLY
 HOW IT TIES INTO THE FACILITY'S ELECTRICAL SYSTEM.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-05-30 Cont ID  
Sent By pleduc Date 2014-05-30 Time   Rev Time 0.00
Received By pleduc Date 2014-05-30 Time 10:25 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By pleduc Date 2014-05-05 Time   Rev Time 0.00
Received By pleduc Date 2014-05-05 Time 16:35 Sent To PC
Notes
2014-05-05 16:49:42THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 ALL FIRE ALARM SHALL BE DONE BY A CERIFIED FIRE ALARM
 CONTRACTOR UNDER SEPARATE SHOP DRAWINGS.
  
 INDICATE THE PREVIOUS COMMENT UNDER THE FIRE LARM
 SYSTEM GENERAL NOTES ON SHEET E-0.
  
 PLEASE NOTE ADDITIONAL LIFE SAFETY COMMENTS UNDER THE
 BUILDING DEPARTMENT COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-30 Cont ID  
Sent By pleduc Date 2014-05-30 Time   Rev Time 0.00
Received By pleduc Date 2014-05-27 Time 08:05 Sent To PC
Notes
2014-05-28 08:05:35SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-05 Cont ID  
Sent By pleduc Date 2014-05-05 Time 16:50 Rev Time 0.00
Received By pleduc Date 2014-04-30 Time 11:17 Sent To PC
Notes
2014-04-30 11:17:34ROUTED TO DAVID HAYES