Plan Review Stops For Permit 14041028 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-05-02 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-05-02 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-05-02 |
Time |
10:16 |
Sent To |
I |
|
Notes |
2014-05-02 11:50:14 | APPROVED WITH THE FOLLOWING NOTATIONS: | | 1 PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM | | CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED | | AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY PROTECTED. | | 2. ALL DOCUMENTATION AS REQUIRED PER NFPA 72 SECTION | | 4.5 SHALL BE PROVIDED UPON COMPLETION AND BE AVAILABLE | | FOR FINAL INSPECTION. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-04-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-04-30 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-04-30 |
Time |
14:09 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-05-02 |
|
|
Cont ID |
` |
Sent By |
albarran |
Date |
2014-05-02 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-29 |
Time |
12:39 |
Sent To |
PC |
|
Notes |
2014-05-02 11:51:07 | PROCESSED TO READY RACK "A" | 2014-04-29 12:39:42 | ROUTED TO FIRE |
|
|
|