Plan Review Details - Permit 14040973
Plan Review Stops For Permit 14040973
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By skennedy Date 2014-05-23 Time 10:13 Rev Time 0.00
Received By skennedy Date 2014-05-23 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:48 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 07:47 Sent To  
Notes
2014-05-19 07:52:221ST REVIEW:
  
 PER FBC 107.3 MINIMUM PLAN REVIEW CRITERIA PROVIDE:
  
 1) SF TABLE TO INDICATE THE AMOUNT OF SPACE TO BE ADDED
 TO THE EXISTING 2641 TOTAL AREA UNDER AIR.
  
 2) DETAILS FOR THE ADDED SECOND FLOOR AREA AS TO
 SUBFLOORING AND FLORRING. THERE IS NO INFORMATION FOR
 STRUCTURAL SHEATHING ON THE NEW FLOOR TRUSSES.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:40 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-23 Cont ID  
Sent By skennedy Date 2014-05-23 Time 10:14 Rev Time 0.00
Received By skennedy Date 2014-05-23 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:53 Rev Time 0.00
Received By skennedy Date 2014-04-28 Time 13:24 Sent To  
Notes
2014-04-28 13:24:22R11
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By skennedy Date 2014-05-23 Time 10:13 Rev Time 0.00
Received By skennedy Date 2014-05-23 Time 10:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:37 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 07:37 Sent To  
Notes
2014-05-19 07:40:161ST REVIEW:
  
 SQUARE FOOTAGE IS BEING ADDED TO THE SECOND FLOOR
 INTERIOR, THEREFORE, IMPACT FEE ASSESSMENT BY PALM
 BEACH COUNTY REQUIRED. AFTER APPROVAL, A SET OF THE
 PLANS ARE TO BE CHECKED OUT AND TAKEN TO THE PBC IMPACT
 FEE OFFICE, STAMPED BY THAT OFFICE, AND RETURNED WITH A
 RECEIPT PROVIDED. CONTACT (561)233-5100.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-05-23 Cont ID  
Sent By skennedy Date 2014-05-23 Time 10:13 Rev Time 0.00
Received By skennedy Date 2014-05-23 Time 10:13 Sent To  
Notes
2014-05-23 10:14:26MECHANICAL CONTRACTOR TO BECOME DESSIGNER OF RECORD,
 ENGINEER HAS DESIGNATED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:40 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 07:40 Sent To  
Notes
2014-05-19 07:47:521ST REVIEW:
  
 THE MECHANICAL SUPPLY SYSTEM MUST BE ALTERED TO THE
 ADEQUATELY SUPPLY THE PROPOSED EXTENDED MBR. IT IS
 UNCLEAR HOW THIS IS TO BE ACCOMPLISHED. IS THE UPSTAIR
 SYSTEM TO BE EXTENDED OR IS THIS AREA TO BE SUPPLIED
 FROM A DOWMSTAIR TRUNK LINE? ADDITIONALLY, PER FBC-R-M
 1602.4 PROVIDE BALANCED AIR RETURN AT BEDROOMS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 07:52 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 07:02 Sent To  
Notes
2014-05-19 07:53:15A PLUBMING PERMIT MAY NOT BE REQUIRED IF THE SCOPE OF
 WORK IS FIXTURE REPLACEMENT ONLY.