Plan Review Details - Permit 14040889
Plan Review Stops For Permit 14040889
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-30 Cont ID  
Sent By albarran Date 2014-04-30 Time 10:09 Rev Time 0.00
Received By albarran Date 2014-04-30 Time 09:12 Sent To I
Notes
2014-04-30 13:29:54AS NOTED BELOW, THIS HAD INITIALLY FAILED BUT AFTER
 SPEAKING W/MIKE OF CONTRACTORS ALARMS HE EXPLAINED THE
 METHODOLOGY OF HIS BATTERY CALCS TO A POINT THAT WAS
 UNDERSTOOD AND SUBSEQUENTLY APPROVED.
2014-04-30 10:32:38THE FOLLOWING ITEMS NEED CORRECTION FOR APPROVAL:
 1. THE SUBMITTED BATTERY CALCULATIONS ARE NOT CORRECT
 AND DO NOT MATCH THE JOB OR RISER DIAGRAM. CORRECT
 ACCORDINGLY
 2. AS PER NFPA 72 SECTION 5.13.6, MANUAL FIRE ALARM
 PULL BOXES SHALL BE LOCATED WITHIN 5 FT. OF THE EXIT.
 THERE IS A PULL STATION TOWARDS THE REAR OF THE
 PREMISES THAT DOES NOT APPEAR TO BE WITHIN THE 5 FT
 REQUIREMENTS. RELOCATE ACCORDINGLY.
 I SPOKE W/ADRIANNE OF CONTRACTOR'S ALARM TO ADVISE OF
 STATUS.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-25 Cont ID  
Sent By pleduc Date 2014-04-25 Time 13:48 Rev Time 0.00
Received By pleduc Date 2014-04-25 Time 13:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-30 Cont ID  
Sent By albarran Date 2014-04-30 Time 13:29 Rev Time 0.00
Received By albarran Date 2014-04-24 Time 15:11 Sent To PC
Notes
2014-04-30 10:34:56WAITING FOR MIKE OF CONTRACTOR'S ALARM TO RETURN A
 CALL. IN THE MEAN TIME, SENT TO SMALL DENIED "C". I
 WILL PROCESS AND SEND TO READY RACK "C".
2014-04-24 15:11:59ROUTED TO FIRE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved